hit counter code

Installation Dimensions; Installing The Unit - Fujitsu AIRSTAGE AUXD18GALH Installation Manual

Indoor unit cassette type
Hide thumbs Also See for AIRSTAGE AUXD18GALH:
Table of Contents

Advertisement

3.2. Installation dimensions

Ceiling height is as shown in the fi gure.
256 mm or more (AUXD18,24)
298 mm or more (AUXA18,24,30,34,36,54)
Strong and durable ceiling
3,000 mm or more
1,800 mm to H
1,000 mm or more
Floor
H: Maximum height from fl oor to ceiling
Function setting
AUXD
AUXD
18
24
Standard mode
3,000
3,000
High Ceiling mode
3,500
3,500
* Be sure to make the function settings with the remote controller according to the
installed ceiling height.
Discharge Direction Setting
• The discharge direction can be selected as shown below.
4 direction
* Select the most appropriate airfl ow direction from 3 or 4 directions according to the
shape of the room and the installation position.
* When changing the number of outlets, we recommend using the optional AIR
OUTLET SHUTTER PLATE KIT to close the outlet.
* For the specifi c closing pattern, please refer to the attached AIR OUTLET SHUTTER
PLATE KIT'S MANUAL. (Do so before installing the cassette grille as it will be
installed on the body.)

3.3. Installing the unit

Install the air conditioner in a location which can withstand a load of at least 5 times
the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come
loose. Please take care.
En-3
1,500 mm
or more
Obstruction
H (mm)
AUXA
AUXA
AUXA
AUXA
AUXA
18
24
30
34
36
3,200
3,200
3,200
3,200
3,200
3,600
3,600
3,600
3,600
4,200
3 direction
100 mm or more
WARNING
3.3.1. Position the ceiling hole and hanging bolts
(1) Positions of the ceiling opening, hanging bolt pitch, piping and ducts. (unit: mm)
• Ceiling opening and hanging bolt pitch.
20 to
45 mm
AUXA
AUXA
45
54
3,200
3,200
4,200
4,200
130 mm
Model
AUXD18/24
AUXA18/24/30/34/36/45/54
• Refrigerant piping and drain piping positions.
Drain pipe
Drain pipe
(Connect the attached
drain hose)
950 mm (Cassette grille)
860 to 910 mm (Ceiling opening)
840 mm (Indoor unit)
795 mm (Hanging bolt pitch)
200 mm
A
B
256
246
298
288
Liquid pipe
358 mm
278 mm
20 to
45 mm
50 mm
Gas pipe
60 mm

Advertisement

Table of Contents
loading

Table of Contents