Function Block; Functionality; Operation Principle - ABB RED615 Technical Manual

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
4.1.3.2
4.1.3.3
4.1.3.4
615 series
Technical Manual

Function block

GUID-9EB77066-518A-4CCC-B973-7EEE31FAE4F1 V3 EN
Figure 84:

Function block

Functionality

The three-phase overcurrent protection DPHxPDOC is used as one-phase, two-
phase or three-phase directional overcurrent and short-circuit protection for feeders.
DPHxPDOC starts up when the value of the current exceeds the set limit and
directional criterion is fulfilled. The operate time characteristics for low stage
DPHLPDOC and high stage DPHHPDOC can be selected to be either definite time
(DT) or inverse definite minimum time (IDMT).
In the DT mode, the function operates after a predefined operate time and resets
when the fault current disappears. The IDMT mode provides current-dependent
timer characteristics.
The function contains a blocking functionality. It is possible to block function
outputs, timers or the function itself, if desired.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of directional overcurrent protection can be described using a
module diagram. All the modules in the diagram are explained in the next sections.
Section 4
Protection functions
177