Page 3
___________________ Terminal Module 150 (TM150) Safety information ___________________ General information ___________________ Mechanical installation SINAMICS ___________________ Electrical installation SINAMICS G130 ___________________ Terminal Module 150 (TM150) Technical specifications Operating Instructions Control version V4.5 03/2012 A5E03758735A...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Safety information............................5 Warnings ............................5 Safety and application instructions ....................6 Components that can be destroyed by electrostatic discharge (ESD) ..........7 General information ........................... 9 Safety information ..........................9 Mechanical installation..........................11 Electrical installation ..........................13 Overview ............................13 Interface description........................14 4.2.1 X524 electronics power supply ....................14 4.2.2...
Safety information Warnings WARNING Hazardous voltages are present when electrical equipment is in operation. Severe personal injury or substantial material damage may result if these warnings are not observed. Only qualified personnel are permitted to work on or around the equipment. This personnel must be thoroughly familiar with all the warnings and maintenance procedures described in these operating instructions.
The operating manual and machine documentation are written in different languages as specified in the delivery contracts. Note We recommend engaging the support and services of your local Siemens service center for all planning, installation, commissioning and maintenance work. Terminal Module 150 (TM150)
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Components that can be destroyed by electrostatic discharge (ESD) CAUTION The board contains components that can be destroyed by electrostatic discharge. These components can be easily destroyed if not handled properly. If you do have to use electronic boards, however, please observe the following: •...
Page 10
Safety information 1.3 Components that can be destroyed by electrostatic discharge (ESD) Terminal Module 150 (TM150) Operating Instructions, 03/2012, A5E03758735A...
General information The terminal module TM150 is a DRIVE-CLiQ component for temperature evaluation. The temperature is measured in a temperature range from -99 °C to +250 °C for the following temperature sensors: ● PT100 (with monitoring for wire breakage and short-circuit) ●...
Page 12
General information 2.1 Safety information Terminal Module 150 (TM150) Operating Instructions, 03/2012, A5E03758735A...
Mechanical installation Figure 3-1 Dimension drawing Terminal Module 150 (TM150) Note The TM150 is installed near the Power Module on a mounting rail, which must be provided by the customer. Terminal Module 150 (TM150) Operating Instructions, 03/2012, A5E03758735A...
Electrical installation 4.2 Interface description Interface description 4.2.1 X524 electronics power supply Table 4- 1 Terminal strip for the electronics power supply X524 Terminal Designation Technical data Electronic power supply Voltage: 24 V DC (20.4 V – 28.8 V) Current consumption: Max. 0.2 A Electronic power supply Max.
Electrical installation 4.2 Interface description 4.2.3 X531-X536 temperature sensor inputs Table 4- 3 X531-X536 temperature sensor inputs Terminal Function Function Technical data 1x2- / 2x2-wire 3 and 4-wire +Temp Temperature sensor connection for sensors with (channel x) (channel x) 1x2 wires Connection of the 2nd measurement cable for sensors with 4-wires -Temp...
Electrical installation 4.4 Protective conductor connection and shield support Protective conductor connection and shield support The following diagram shows a typical Weidmüller shield connection clamp for the shield supports. ① Protective conductor connection M4/1.8 Nm ② Shield connection terminal, Weidmüller company, type: KLBÜ CO1, order number: 1753311001 Figure 4-4 Shield support and protective conductor connection of the TM150...
Page 22
Electrical installation 4.4 Protective conductor connection and shield support Terminal Module 150 (TM150) Operating Instructions, 03/2012, A5E03758735A...
Technical specifications General technical data Table 5- 1 General technical data Product standard EN 61800-5-1 Technical data Table 5- 2 Technical data 6SL3055- 0AA0-3LA0 Unit Value Electronic power supply Voltage 24 V DC (20.4 – 28.8) Current (without DRIVE-CLiQ) 0.07 Power loss PE/ground connection On housing with M4/1.8 Nm screw...