Automation systems, controlling a physical axis (32 pages)
Summary of Contents for Siemens CP-8000
Page 1
Open Source Software Table of Contents General Information System Overview SICAM A8000 Series Function Packages Ambient Conditions CP-8000, CP-8021, CP-8022 System Components and Technical Data Installation and Circuitry User Manual Preparing the Engineering Engineering via SICAM TOOLBOX II Engineering via SICAM WEB...
Page 3
Technical system maintenance and service, module handling Within this manual there are hints how to obtain information or files by means of the website http://www.siemens.com/sicam. If you have no access please consult your project manager at Siemens. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 4
Symbolic names, program names and file name extensions are described in this font. Note Within this manual described functions for operation, diagnosis and test of CP-8000/CP-802x have been recorded by means of an industrial PC with operating system Microsoft Windows 7 Enterprise ® (Service Pack 1) [64 bit] and web browser Microsoft Internet Explorer ®...
Page 5
CAEx plus Online Help SICAM Device Manager Product Information D51-001 SICAM Device Manager User Manual D51-003 PC Products Reference List D95-003-1 available in the engineering system SICAM TOOLBOX II SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 7
2. Ensure that electricity cannot be switched on again! 3. Double check that no electrical current is flowing! 4. Discharge, ground, short circuit! 5. Cover or otherwise isolate components that are still electrically active! SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 8
· Disposal ─ For the disposal of the device it is necessary to observe the local and national direc- tives. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 9
Insofar as the applicable Open Source Software License Conditions provide for it you can or- der the source code of the Open Source Software from your Siemens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years since purchase of the Product.
Page 20
Commissioning and Test ................. 307 8.2.3.1 Loading Program Code............... 307 8.2.3.2 Test Functions ..................307 8.2.3.2.1 Simulating Function Diagram Offline ..........307 8.2.3.2.2 Testing Function Diagram Online ........... 308 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 21
Selection of the Transmission Facility ..........342 9.1.7.4 Settings of the Messages..............343 9.1.7.5 Data Management and Priority Control ..........344 9.1.8 Configuration of the Decentralized Archive..........345 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 22
Table of Contents 9.1.9 Configuration of the Process Data Archive ..........347 9.1.10 Configuration of the Local Process Data Display (only CP-8000) ..... 348 9.1.11 Configuration of Peripheral and Internal Signals........349 9.1.11.1 Defining Signals ................. 349 9.1.11.1.1 Duplicate and Delete Rows ............352 9.1.11.1.2...
Page 23
11.1 Operation and Display Elements ..............472 11.1.1 Description of the LED Display ..............473 11.1.2 Description of the LCD Display (only CP-8000) ........475 11.1.2.1 Navigation ..................476 11.1.2.2 Device Information ................476 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 24
11.4.1.1 Internal Modules ................. 515 11.4.1.2 SD Card ..................... 515 11.4.2 Replacement of a Module ................ 516 11.4.3 Adapt New Equipped I/O Modules in the Parameterization....... 517 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 25
Transfer an Input to a Signalling Output and to a Command Output ....544 Combine two Inputs with AND ..............545 Linear Adaptation with Value Selection ............546 Operating Hours Counter ................547 Bounce Suppression ..................549 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 26
GPRS Communication without IPSec VPN ..........600 E.7.2 GPRS Communication with 1 IPSec VPN Tunnel ........601 E.7.3 GPRS Communication with 2 IPSec VPN Tunnel ........602 Glossary ..........................605 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Evidently all applications can be combined with each other. CP-8000/CP-802x can be deployed universally and is suitable for electrical distribution substa- tions, gas distribution substations, hydropower plants, pipelines, railway power supplies, as well as in building protection or for alarm signaling.
General Information 1.1.2 Different Fields of Application Due to their node functionality, CP-8000/CP-802x can be used in a variety of ways: · Classical small telecontrol unit · Remote terminal unit with manifold communication to the central station · Automation and supervision of local network stations ·...
1.1.4 Local Operation with CP-8000 In addition to status LEDs, CP-8000 provides function keys and a display on the front of the housing in order to enable a variety of . SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
If the scope of signals of a substation should ever be insufficient, additional I/O Modules can be equipped or further CP-8000/CP-802x can be connected via the communication interfaces. Freely programmable user programs for local control or regulating functions round out the versatile attributes of the system.
The configuration is transferred directly to the replacement device (plug and play). 1.1.8 Compatibility CP-8000/CP-802x is in the range of IEC 60870-5-101/103/104, when using standard proto- cols, compatible with the hitherto existing SICAM RTUs system family (SICAM AK, SICAM TM, SICAM EMIC, SICAM MIC, SICAM BC).
IP address configurable (2 MAC addresses reserved, see type label of the de- vice) 1x RS-232 and 1x RS-485 1x selectable RS-232 or RS-485 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
System Architecture 1.3.1 CP-8000 CP-8000 consists of a power supply, a Master Module, up to 4 protocol elements, and 2 internal I/O Modules. Additionally, up to 6 external I/O Modules can be attached via a coupling module. Higher-level automation unit...
2.1.1.1 CP-8000 With CP-8000 the supply is carried out via an internal power supply module. This provides the operating voltage for the internal modules (Master Module and I/O Modules) and for selected transmission facilities with multi-point traffic and dial-up traffic, as well as for the external I/O Modules.
Page 39
Power supply DC 110 to 220 V, 12 W PS-8640 Power supply DC 24 to 60 V, 45 W PS-8642 Power supply DC 100 to 240 V, AC 100 to 240 V, 45 W SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Initialization tool for the detection of devices and IP address allocation tartup SD card Memory card for parameters and firmware Note In a system of the SICAM A8000 series only 1 Master Module may be used. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
ST1ST0 Siemens SINAUT-ST1 Slave RS-232, RS-485 TG8ST0 L&G Telegyr 800 Slave RS-232, RS-485 Additional information on interfacing to third-party systems and further protocols is available on request. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Features · Support of I/O Modules ─ CP-8000: 2 internal and up to 6 external I/O Modules (maximal 116 I/Os) ─ CP-802x: up to 8 external I/O Modules (maximal 128 I/Os) · Acquisition and preprocessing of process data according to IEC 60870-5-101/104 with and without time tag ─...
6 connectable via coupling module CM-8811 connectable via coupling module CM-6811 2.1.5.1 Internal I/O Modules Internal I/O Modules are available only with CP-8000. They are fixed integrated. Product Overview Type Designation DI-8100 Binary input 12x DC 24 to 60 V, 1 ms...
The external SICAM I/O Modules can be used with all products of the SICAM A8000 series: · With CP-8000, up to 6 external SICAM I/O Modules can be used · With CP-8021 and CP-8022, up to 8 external SICAM I/O Modules can be used Note With CP-8000 the coupling module CM-8811 is required.
2.1.5.3 External SICAM TM I/O Modules The external SICAM TM I/O Modules can be used only with CP-8000. Up to 6 external SICAM TM I/O Modules can be used. Thereby, also a 2-line arrangement is possible with TM I/O Modules extension cable CM-6810.
For further details refer to section 9.1.11.5.5, Command Output. Option “Checked Command Output” (applies for CP-8000 with SICAM TM I/O Modules) · Only 1 command output basic module may be connected, alternatively ─ DO-6220, command output according to IC1 ─...
System Overview Communication 2.2.1 Interfaces For a multitude of communication possibilities CP-8000/CP-802x provides the following inter- faces: · 2 Ethernet TCP/IP interfaces LAN/WAN (X1 and X4) both Ethernet interfaces have optionally one common IP address or two independent IP addresses (2 separate MAC addresses ·...
Page 48
Server Ed. 1 is required, else is ET85 to be used GPRS communication possible via X1, X4 and external GPRS modem X3 in RS-422 mode Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
IEC 60870-5-104, Ethernet (10/100 Mbps) Interface to remote devices: GPRS Further SICAM A8000 or any other local IED possible Interface to local devices: IEC 60870-5-103, Modbus (RS-485) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
5 V via RS-232 interface (in case of CP-8022 as of production level CC) provides RS-232 and RS-485 interface transmission of SMS possible without IPsec VPN tunnel Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
System Overview Firmware Structure and Data Flow The basis for CP-8000/CP-802x is a modular, open, and thus non-technology-dependent sys- tem architecture for processing, communication, and peripherals (single-processor system, firmware). The adaptation to the specific needs of the application is accomplished by relying on an indi- vidual hardware configuration and by loading standard firmware and parameters.
System Overview Engineering Engineering, diagnosis and test of CP-8000/CP-802x takes place alternatively via · SICAM TOOLBOX II (as of Version 6.01) · SICAM WEB · SICAM Device Manager 2.4.1 SICAM TOOLBOX II The integrated engineering system SICAM TOOLBOX II comprises all stages of plant configu- ration and maintenance, this means data collection, configuring, parameter setting, expand- ing, changing, testing, system diagnosis, and documentation.
SICAM WEB for Simple Applications A top priority was also a simplified engineering possibility. For the configuration, diagnosis and testing, CP-8000/CP-802x provides an integrated web server that is operated with a standard web browser (Microsoft Internet Explorer® as of Ver- sion 9).
With restrictions ü Sum diagnosis information Via instruction list Via SNMP traps Extras Program Sicam_first_startup (find all CP-8000/CP-802x devices in a network and preset IP ad- dresses) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
CP-8000/CP-802x supports one IPSec VPN tunnel. Thus, it is e.g. possible, to completely secure the IEC 60870-104 communication between CP-8000/CP-802x and a higher-level control center, even if the connection is running over a public network. CP-8000/CP-802x uses the IKE protocol (Internet Key Exchange) and the PSK authentification process (Pre-Shared Key).
Function Packages 3.1.3 Communication with the Engineering System (SICAM TOOLBOX II) For the communication between the SICAM TOOLBOX II and CP-8000/CP-802x exist differ- ent variants: · Physical connection ─ Locally by means of a direct cable (RS-232 interface) ─ Remotely −...
Messages with process information have a 5-stage message address. Message addresses must be parameterized at the sources (I/O Modules, open-/closed-loop control function). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
64000 automation units. 3.1.6.2 Addressing of Process Information Addressing and the structure of the process information to be passed on by CP-8000/CP-802x are consistent with the IEC 60870-5-101/104 standard. Therefore, the information is in turn compatible and interoperable with many other vendors.
Monitoring of communication · Functionality (periodical call messages with monitoring function, monitoring of transmis- sion quality) · Data integrity (secured transmission, identification through failure of data concerned) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
3.1.10 Failure Management The failure management system concept implemented in CP-8000/CP-802x ensures the indi- vidual identification of data of failing system components and the correct system and process behavior in disturbance events. For this purpose, the failure management function includes ·...
This system concept ensures that, if central parts succumb to a failure, as much of the func- tionality as possible will remain intact. CP-8000/CP-802x is capable of functioning autono- mously – this means, it will continue carrying out its defined local function even where the en- tire communication is disturbed.
Messages with system information are either processed directly (example: station interroga- tion) or distributed further based on their destination address (CASDU) (example: mes- sages for remote maintenance) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
· Process information in monitor direction priority MEDIUM with class 2 data · Process information in monitor direction priority LOW with class 2 data · Transparent information Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Protocol element return information ─ Cost control of telephone charges ─ Cost-efficient utilization of the telephone line (for instance command initiation only if a connection has already been established) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Spontaneous for binary information items and integrated totals ─ Definable cycle for measured values ─ Non-volatile on flash card · Reading of the archive via SICAM WEB by means of file download possible Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· Spontaneous reception of messages with process information from the communication · Postprocessing and forwarding of the process data for the output via I/O Modules SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Bitstring of 32 bit The data transfer of the spontaneous information objects to the open-/closed-loop control func- tion for further processing is dependent on the result of the checks. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The time tag corresponds either cycle- synchronous with the current time (resolution corresponds with the cycle time) or the time in- formation from an assigned spontaneous information object. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Within the cycle time, the application programs must process the input handling and the output handling · The cycle time can be set in the application program Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ The value of a variable can change again at any time after setting, due to the function of the program (“CAEx plus Online Test”) ─ The value of a variable remains maintained until the test mode is active (SICAM WEB) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 72
Compiler errors During the course of the interrogation, the current run time and the number of time-outs can be optionally reset (does not apply for SICAM WEB). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ Derived information items ─ Processing results ─ Operations-relevant error information (for instance “command output fault”) · Postprocessing and forwarding of the process data for the output via I/O Modules SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note The following data applies for CP-8000/CP-802x without external SICAM TM I/O Modules. If CP-8000/CP-802x is expanded with external SICAM TM I/O Modules, the corresponding data of the SICAM TM system apply. Refer to SICAM TM System Datasheet, MC6-007-2. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Cl.S3 and IEC 60255-21-3 Cl.1. The values apply in operation and for storage. The permitted mechanical stresses during transport depend on the transport packaging. The device packaging is not a transport packaging. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note CP-8000: With cold temperatures the display becomes more sluggish and the legibility may be restricted (at –25°C the reaction time is 5 s). Unrestricted SICAM A8000 / CP-8000 •...
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
2.5 kVp IEEE C37.90.1 1 MHz common AO-8380: tested with 4.0 kVp AI-8310: tested with 10…1 V AI-8310: tested with 10 V AI-8310: tested with 100 V SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The immunity and the galvanic insulation is as- sumed by the external data communications equipment. You can find the electrical ambient conditions of data transmission equipment in the related data sheets. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
IEEE C37.90.1 1 MHz common CP-8000: tested with 2.0 kVp The listed values are valid for shielded cat.5 cables with a length of up to 100 m. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
+10°C and +35°C, in order to prevent premature ageing of the electrolytic capacitors used. For a longer storage period Siemens also recommends connecting the device to the supply voltage once a year for 1 to 2 days, in order to form the electrolytic capacitors used. You should proceed likewise before a planned use of the device.
Master Module. With the power supply modules (with CP-8000 internal), it must be considered that due to the efficiency factor (typical 80%; sub-zero temperature 77%) the power consumption values of the external consumers must be corrected.
SICAM TM I/O coupling module Communication via SMA connector GPRS interface can be used optionally for RS-232 or RS-485 communication ext. GPRS modem/router with Ethernet/LAN interface SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
DC 60 V max. switching capacity: < 40 A ohmic resistance: < 5 Ω permanent floating current after activation of the fuse: < 1.3 A Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
124 x 30 x 132 mm (measure without DIN rail) Weight Approx. 240 g (incl. bus module 12 g) as of production level CC for the generation of the auxiliary voltage for specific transmission facilities SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
124 x 30 x 132 mm (measure without DIN rail) Weight Approx. 400 g (inkl. bus module 12 g) for the generation of the auxiliary voltage for specific transmission facilities applies only for PS-8642 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
100 files of 25 records each (= 2500 records) 200 files of 50 records each (= 10000 records) 200 files of 25 records each (= 5000 records) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 94
RJ45 socket connector 8-pole (IEC 603.7) Dimension (LxWxH) 124 x 128 x 123 mm (measure without DIN rail) Weight Approx. 800 g only for specific transmission facilities Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
100 files of 25 records each (= 2500 records) 200 files of 50 records each (= 10000 records) 200 files of 25 records each (= 5000 records) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 97
Approx. 210 g (CP-8021), ca. 260 g (CP-8022) only CP-8022 for CP-8022 with production level BB applies class 4 only for specific transmission facilities as of production level CC SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Acquisition of transmission delay (primary station) used for correction of clock syn- chronization (with request status of link = proprietary) · Command transmission ─ Demand ─ Set control location ─ Check control location Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 99
─ Day of week (DOW) = 0 for all messages in transmit direction (day of week time tag) ─ Originator address = 0 for all messages in transmit direction · Transparent Mode (Tunneling) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 100
− I bit handling for time ON/OFF ─ Protocol element return information − Status DTR (1 = state line active) − Status DSR (1 = state line active) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
CP-8022 (switchable mode via parameter) Note Details about realization of various operation modes are given in the manual SICAM SICAM RTUs Plat- forms – Configuration Automation Units and Automation Networks. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Functions for supporting redundant communication routes Note The previously mentioned functions are described in detail in the document SICAM SICAM RTUs • Ax 1703 Common Functions Protocol Elements, section "Dial-Up Traffic (DIA)". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Check control location · Transmission of integrated totals · File transfer ─ Disturbance records to SICAM DISTO ─ Disturbance records to control center systems according to IEC 60870-5-101/104 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 106
The previously mentioned functions are described in detail in the document SICAM SICAM RTUs • Ax 1703 Common Functions Protocol Elements, section "Interfaces of Protective Devices (103)". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
− Set control location − Data filter in transmit direction “ON/OFF“ − Data filter in receive direction “ON/OFF” − Activate/Deactivate interface − Activate/Deactivate interface + protocol functions Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
CP-8022 (switchable mode via parameter) Note Details about realization of various operation modes are given in the manual SICAM RTUs Platforms - Configuration Automation Units and Automation Networks. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Preset control location Protocol element return information ─ PRE return information 0 “Status DATA TRANSFER (Master Module)” ─ PRE return information 1 “Status DATA TRANSFER (104)” SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 112
10 connections Note The previously mentioned functions are described in detail in the document SICAM RTUs • Ax 1703 Common Functions Protocol Elements, section "LAN Communication (104)". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ Check control location ─ Command interlocking ─ Direct control with normal security ─ Direct control with enhanced security ─ SBO control with enhanced security · Setting groups Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 115
(for details see SICAM RTUs • Ax 1703 Common Functions Protocol Elements, chapter “LAN Communication (61850)”, section Basic Data Types” and “Conversion IEC 60870-5-101/104 ↔ IEC 61850“) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 116
SICAM TOOLBOX II connection over LAN/WAN ("remote connection") ─ Remote connection based on HTTP/HTTPS ─ Authentication in SICAM RTUs using connection password (optional) ─ Warning “Remote Connection” Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
TXD+, TXD-, RXD+, RXD- (twisted pair) Note Details about realization of various operation modes are given in the manual SICAM RTUs Platforms - Configuration Automation Units and Automation Networks. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
ATTENTION: check power consumption of external modem! · Standby transmission line over the public telephone network (PSTN) · Data transmission using time slot radio · Co-ordination of several masters SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
CP-8022 (switchable mode via parameter) Note Details about realization of various operation modes are given in the manual SICAM SICAM RTUs Plat- forms – Configuration Automation Units and Automation Networks. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
CP-802x/CPC80 Remote Station (Counter Device) System System element Protocol element Remarks Third-party system – – acc. to IEC 62056-21 (IEC 61107) mode C with EDIS/OBIS data coding SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ 5 V power supply for external modem ATTENTION: check power consumption of external modem! · Protocol element control and return information ─ Protocol element return information ─ Station status ─ Station failure Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 123
─ Predefined optimized parameters for selected transmission facilities ─ Free definable parameters for transmission facility ─ 5 V power supply for external modem ATTENTION: check power consumption of external modem! SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
CP-8022 (switchable mode via parameter) Note Details about realization of various operation modes are given in the manual SICAM RTUs Platforms - Configuration Automation Units and Automation Networks. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ Access to the web server with standard web browser via HTTP (Hyper Text Transfer Protocol) · Special functions Note The previously mentioned functions are described in detail in the document SICAM RTUs ▪ Ax 1703 Common Functions DNP3. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
5.5.11.1 Functions Communication of a central station with one or more substations. · Unbalanced multi-point traffic according to Siemens SINAUT ST1 (TIM 11) ST1ST0 is substation ─ Data acquisition by polling (station interrogation) ─ Acquisition of events (transmission of data ready to be sent) ─...
Note The previously mentioned functions are described in detail in the document SICAM RTUs • Ax 1703 Common Functions SK 1703 Multi-Point Traffic GV-U. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
CP-8022 (switchable mode via parameter) Note Details about realization of various operation modes are given in the manual SICAM RTUs Platforms - Configuration Automation Units and Automation Networks. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
System Components and Technical Data Integrated Protocol SNMP 5.6.1 Overview CP-8000/CP-802x provides the protocol SNMP. This protocols is integrated in the firmware of the Master Module. CP-8000/CP-802x is SNMP Agent. SNMP Manager · SNMP variables retrievable via: ─ Standard SNMP network management software ─...
Calculation the function affects process information which is used as input for the calculation of calculated (derived) values Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ Settable output of the categories DO_EX and DO_DX − Mixed output of binary information items and commands on 1 DO module possible − Output of persisting commands SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Groups that are loaded with > 2 A should not be next to another; example: 3 A-3 A-1 A-1 A-3 A-3 A-1 A-1 A instead of 3 A-3 A-3 A-3 A-1 A-1 A1 A-1 A Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
System Components and Technical Data 5.7.2 External SICAM I/O Modules Note The technical data of the SICAM I/O Modules are described in the document SICAM I/O Modules. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ If outputs of the module are used for binary information output, no outputs of the same module can be used for pulse commands ─ Usage of outputs as Watchdog SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The previously mentioned functions are described in detail in the document SICAM RTUs Common Func- tions Peripheral Elements according to IEC 60870-5-101/104, chapter “Measurement in Three-Phase Systems – I/O Module”. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The previously mentioned functions are described in detail in the document SICAM RTUs Common Func- tions Peripheral Elements according to IEC 60870-5-101/104, chapter “Measurement in Three-Phase Systems – I/O Module”. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
External SICAM TM I/O Modules (only with CP-8000) Note The technical data of the SICAM TM I/O Modules are described in the document SICAM TM I/O Modules. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ The autonomous operable functions of the module are operated buffered, thus count- ing function and counts remain correct also over a voltage failure from up to 72 hours ─ Spontaneous transmission SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Settable assignment for messages and pulse commands, which are acquired or output on the I/O Master Module ─ Predefined assignment for messages and pulse commands, which are acquired or output on the I/O Master Module Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
─ Settable assignment for messages and pulse commands, which are acquired or output on the I/O Master Module ─ Predefined assignment for messages and pulse commands, which are acquired or output on the I/O Master Module SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
─ Settable assignment for messages and pulse commands, which are acquired or output on the I/O Master Module ─ Predefined assignment for messages and pulse commands, which are acquired or output on the I/O Master Module Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
System Components and Technical Data MTBF Values of the SICAM A8000 Modules The MTBF values shown in this section have been calculated according to Siemens standard SN29500. All electrical and electromechanical components have been considered. Not included are mechanical components (screws, housing, adhesive labels, etc.).
Interfaces ..................... 207 6.11 Installation of External Communication Connections ........212 This chapter describes the mechanical design of CP-8000/CP-802x and how the installation and wirings are to be accomplished. This chapter shows further how the various communication methods can be realized by means of the standard modems and special cables.
Ethernet interface. On the right side of the housing is the bus connector for the I/O coupling module. It is covered with a label. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Locking Hook The device is locked onto the DIN rail and also removed again using the locking hook. Details see section 6.4.2, Mounting of the Master Module. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
X4: 00-E0-A8-B2-51-64 6MF21011AB100AA0FF BF1208154985 Humboldtstr. 59, 90459 Nuremberg, Germany www.siemens.com/sicam Made in India Symbol Meaning CE conformity Protection class II / protective insulation The documentation must be observed Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Locking Hook The device is locked onto the DIN rail and also removed again using the locking hook. Details see section 6.4.2, Mounting of the Master Module. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
6MF28021AA00 BB GF1611016515 Humboldtstr. 59, 90459 Nuremberg, Germany www.siemens.com/sicam Made in India Symbol Meaning CE conformity Protection class II / protective insulation The documentation must be observed Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Installation and Circuitry 6.2.3 CP-802x Front and Side View 18 mm 124 mm 30 mm 18 mm 124 mm 30 mm Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
6.3.1 DIN Rail (TS35 Rail) For the installation of CP-8000/CP-802x a DIN rail is to be used, which conforms to the Euro- pean Standard IEC 60715. The orientation and position in which the DIN rail is to be installed must be determined locally.
When using a cable duct with 100 mm depth below the device, it is necessary to keep a 50 mm minimum distance between device and cable duct to operate the locking hook. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
**) when using a cable duct with 100 mm depth below the device, it is necessary to keep a 50 mm min- imum distance between device and cable duct to operate the locking hook SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
O H 2 R T X 2 R S - 4 8 5 O H 3 R T X 3 E T H L K 4 P K 4 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
If the device is extended by external SICAM TM I/O Modules (max. 6 are permitted), then you must consider the width of the coupling module, the I/O Modules, the bus protection cap and the end clamp. Example: CP-8000 + 6 ext. SICAM TM I/O Modules Thermical space ............. 30 CP-8000..............128 CM-6811 coupling module ........
Installation and Circuitry 6.4.2 Mounting of the Master Module CP-8000 can be installed on the DIN rail by hand, without any tools. Hang the inclined device in the top edge of the DIN rail. Swing the device until the locking hook has contact with the bottom edge of the DIN rail.
Lift the device upwards out of the rail. Note If external I/O Modules are coupled to your device, then you can only remove the device after separating the external I/O Modules. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Installation and Circuitry 6.4.4 Coupling of external SICAM I/O Modules CP-8000 can be expanded by up to 6 external SICAM I/O Modules. Thereto the following steps are essential: · Mounting of the coupling module for SICAM I/O Modules · Mounting of the bus connector for SICAM I/O Modules ·...
The tongue and groove system integrated in the modules facilitates the correct combination. The module is only connected correctly when the locking hook is snapped onto the DIN rail. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 182
Installation and Circuitry Caution To increase the stability it is necessary to mount an end clamp flush left from the CP-8000 housing and flush right after the last SICAM I/O Module. SICAM C MIC SICAM A8000 CP-8000 P OK E TH...
Installation and Circuitry 6.4.5 Coupling of External SICAM TM I/O Modules CP-8000 can be expanded with up to 6 external SICAM TM I/O Modules. Thereto the follow- ing steps are essential: · Mounting of the coupling module for SICAM TM I/O Modules ·...
Mounting of the SICAM TM I/O Modules After CP-8000 and coupling module are mounted on the DIN rail you can start to mount the SICAM TM I/O Modules. Lead the first I/O Module as shown in the following picture into the guides on the SICAM TM I/O coupling module and lock it on the DIN rail.
Page 185
Installation and Circuitry Caution To increase the stability it is necessary to mount an end clamp flush left from the CP-8000 housing and flush right after the last SICAM TM I/O Module. SICAM A8000 SIC AM CMIC CP-8000 E TH...
Installation and Circuitry 6.4.6 Separating of Master Module and I/O Coupling Module If you need to separate a CP-8000 from the I/O coupling module (e.g. spare part replace- ment), proceed as follows: Separate the external I/O Modules from the Master Module.
LK 4 PK 4 OH 2 RS- 232 RTX2 O H3 RTX3 for thermal reasons, a minimum distance of 30 mm must be maintained around the device SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
R S - 2 3 2 R T X 2 L K 7 P K 7 R T X 3 O H 3 R T X 6 O H 6 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
DIN rail. Note You also can open and lock the locking hooks on the module, before you mount the module. They must be closed manually after assembly. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note If external I/O Modules are coupled to your device, then you can only remove the device after separating the external I/O Modules. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The tongue and groove system integrated in the modules facilitates the correct combination. The module is only connected correctly when the locking hook is snapped onto the DIN rail. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
. Both elements must be aligned seamlessly. O H2 RS-2 3 2 RTX2 RTX3 RTX6 Afterwards you can attach the bus connectors of further SICAM I/O Modules in the same way. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
You can take information on the SICAM I/O Modules out of the following document: Document name Item number SICAM I/O Modules User Manual DC8-012-2 Please consider the notes in the section 2.1.5.4, Configuration Rules for I/O Modules. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Installation and Circuitry Memory Cards 6.6.1 SD Card CP-8000/CP-802x uses an SD card (Secure Digital) for the storage of firmware, application and diagnosis data. The Master Modules are supplied with an SD card inserted. You find further information in section 7.5.1, Card.
Disconnect the device from the supply voltage and wait for at least 30 s. Push the SIM card carefully until it is disengaged and springs out of the slot. The SIM card can now be removed. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
(see example for process peripherals). 6.7.1 Power Supply CP-8000 has an integrated power supply module (see 5.3.1, CP-8000 (integrated)). · The supply can be performed via a station battery or series power units. ·...
6.7.5 Protective Earth/Ground When installing CP-8000/CP-802x, it is to be ensured that the cabinet or rack used has proper protective earth and ground. That means, that all electrical conducting parts must be connected large-surface and as short as possible with the existing grounding system.
Before switching the device on it must be connected to the designated power supply. Switching on takes place by connecting the voltage at the corresponding connector (X12/CP-8000, X1/PS-862x, X1/PS-864x), commonly by switching on a miniature circuit breaker (Details see 6.7.1, Power Supply).
Installation and Circuitry 6.9.1.4 Digital Input DI-8100 The following circuitry variants are examples, and do not relate exclusively to the depicted inputs/outputs. DI-8100 Controller reinforced insulation PS-8630 AUX V0+/- SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Further information see section 11.2.3, Behavior of the Process Outputs upon Startup and Failure. 6.9.1.5.1 1 and 2-pole Circuitry DO-8203 Controller 1-pole with pole with 2-pole switched plus switched m inus Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Installation and Circuitry 6.9.1.5.2 1½-pole Circuitry DO-8203 Controller 1,5-pole *) no galvanical insulation between the relay common and COM OUT D06 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Installation and Circuitry 6.9.2 CP-802x 6.9.2.1 Power Supply Modules PS-8620 and PS-8622 PS-862x 5 V 28 V galvanical insulation PS-8620: DC 24...60 V PS-8622: DC 110...220 V Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
5 V 28 V reinforced insulation - (N/-) + (L/+) contact wetting/ modem supply PS-8640: DC 24...60 V PS-8642: DC 100...240 V only PS-8642 AC 100... 240 V SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
CP-8022 (SIM Card is not scope of supply) Note X1 and X4 are alternatively 1 Ethernet interface (duplicated via an internal switch) or 2 independent Ether- net interfaces. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
6.10 Interfaces 6.10.1 CP-8000 6.10.1.1 Position of the Interfaces on the Housing The communication and process interfaces are positioned on the CP-8000 Master Module ac- cording to their use. Interfaces on the Interfaces on the front of the housing top of the housing...
DIN rail Note The assignment of X3 is independent whether a termination is existing or not (termination = resistance that is connected through parameter in the firmware). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 209
OUT D00 to D07…………… make contact outputs 0 to 7 COM OUT D00 to D07…….. common (root) outputs 0 to 7 BAT+/-………………………… input voltage AUX V0+/-……………………. voltage distribution SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
6.11 Installation of External Communication Connections Via the communication interfaces of CP-8000/CP-802x selected transmission facilities can be connected. Depending on the kind of the selected communication type, different connection cables are required for the connection of a data transmission facility.
RS-485 CP-8000 Note CM-0847 replaces CM-0827 which is used only in existing plants. A maximum of 6 star couplers CM-0822 may be attached next to each other. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 216
X2:9 n.c. Shield Shield Connection CTS–GND: see note at page 212. Wiring for Connection CP-8000 – CM-0827 Fiberoptic Interface (Existing Plants) Recommended D-Sub/RJ45 Adapter RS Pro MHDA9-SMJ8-M-K (see appendix A.8.1, Recommended Third-Party Products). This adapter provides a wired RJ45 socket and an unwired D-sub plug (female).
Page 223
SIPROTEC 5 Note No protective device slaves may be connected to the T1/R1 connector of the Siemens 7XV5450 star coupler. T1/R1 is used for connection with the central station or to other star couplers in a star or ring structure.
Page 224
1 L- L+ SIPROTEC 5 Note A maximum of 30 Siemens 7XV5450 star couplers may be used in a star or ring structure. No protective device slaves may be connected to the T1/R1 connector of the Siemens 7XV5450 star coupler.
Page 225
1 L- L+ SIPROTEC 5 Note A maximum of 30 Siemens 7XV5450 star couplers may be used in a star or ring structure. No protective device slaves may be connected to the T1/R1 connector of the Siemens 7XV5450 star coupler.
Page 226
This configuration with converters is given when, for example, the customer provides the complete infra- structure for the communication. Alternatively, a CM-0847 can be used in the substations instead of the optical converter RS232-FO 7XV56529. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 237
This chapter describes with which methods CP-8000/CP-802x can be parameterized and pro- grammed, and which prerequisites must be fulfilled thereto. Note Grafics and screenshots shown in this chapter relate to the engineering of CP-8000. They apply analo- gously for CP-8021 and CP-8022. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
(diagnosis, process display) can be used in this case. Note CP-8000/CP-802x is delivered ex factory with an equipped SD card and a default web parameterization. At the moment that you load SICAM TOOLBOX II parameters, the access via SICAM WEB is only reading (role guest).
The toolsets are also available as “Light” version. With this version, the engineering is limited to maximal 100 system elements and 2000 data points. The toolsets are available individually. You find information and updates for the individual toolsets, as well as numerous licences, on the website http://www.siemens.com/sicam. Document Item number...
Information thereto reside within a permanently updated List of PC preference types. Should that be not at your disposal, please consult your contact person at Siemens. For the installation of the SICAM TOOLBOX II the following preconditions are required: ·...
Microsoft Windows Server 2008 R2 ® 64 Bit PC, Notebook Microsoft Windows Server 2012 R2 ® 64 Bit PC, Notebook DirectX version depends on the used operating system SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
For the performing of the respective function, a special firmware is provided for each system element. The functionality of each system element is adjustable by means of parameters. As a partner of Siemens, you are able to download all the code revisions for your system as loadable binary files via the website http://www.siemens.com/sicam.
Preparing the Engineering Integrated Protocol SNMP CP-8000/CP-802x supports the protocol SNMP Agent (version 2 and version 3). For the engi- neering of the SNMP protocol you need to get MIB files and a MIB browser. 7.4.1 Download of the MIB-Files MIB-files can be downloaded from the website http://www.siemens.com/sicam:...
Memory Cards 7.5.1 SD Card For the storage of engineering data CP-8000/CP-802x needs an SD card. This resides in the slot at the housing front (CP-8000) or housing back (CP-802x), refer to section 6.6.1, Card. With delivery of CP-8000/CP-802x, all required files for the correct operation are stored in folders on the SD card: ·...
Preparing the Engineering Interfaces for the Communication CP-8000/CP-802x provides the following interfaces for engineering and maintenance: Interface Type Engineering tool Ethernet TCP/IP SICAM TOOLBOX II or SICAM WEB Serial RS-232 SICAM TOOLBOX II or SICAM WEB Ethernet TCP/IP SICAM TOOLBOX II or SICAM WEB...
Connecting Engineering PC with the Target Device 7.7.1 SICAM TOOLBOX II Before parameters can be loaded via the SICAM TOOLBOX II into CP-8000/CP-802x, the fol- lowing steps must be performed: · Insert a suitable SD card into the target device (if not present) ·...
Preparing the Engineering 7.7.1.1 Physical Connection 7.7.1.1.1 Serial Point-to-Point Connection Engineering PC and CP-8000 are connected with a direct cable via the serial interface (X2). SICAM TOOLBOX II CP-8000 TOOLBOX II Revision : Licen se Pak: PO K Versio n 5 | Siemen s AG...
Page 252
Standard patch cable CP-802x max. 1.8 m TOOLBOX II Revision : License Pak: Version 5 | Siemen s AG D-sub/RJ45 adaptor Wiring for Connection CP-8000 – PC (patch cable + D-sub/RJ45 adapter) 9-pole D-sub Engineering female X2:1 X2:2 X2:3 X2:4 X2:5...
Preparing the Engineering 7.7.1.1.2 Serial Connection via Telecommunication Facilities Engineering PC and CP-8000 are connected via the serial interface (X2) via modems and al- ternatively via a dedicated line, the public fixed network, or wireless radio. serial serial Modem Modem Line, PSTN, GSM, ...
Preparing the Engineering 7.7.1.1.3 LAN/WAN Connection via Ethernet Interface Engineering PC and CP-8000 are connected via one of the Ethernet interfaces (X1 or X4) via a network by means of standard patch cables. Ethernet TCP/IP IEC 60870-5-104 Standard patch cable...
Preparing the Engineering 7.7.1.1.4 LAN/WAN Connection via Serial Interface and Terminalserver Engineering PC and CP-8000 are connected via the serial interface (X2) via a network and a terminal server. Ethernet TCP/IP Terminal Server Standard patch cable Direct cable SICAM TOOLBOX II...
Preparing the Engineering 7.7.2 SICAM WEB Before CP-8000/CP-802x can be parameterized via SICAM WEB, the following steps must be performed: · Insert a suitable SD card with the current firmware codes into the target device (if not pre- sent) ·...
Preparing the Engineering 7.7.2.1 Physical Connection 7.7.2.1.1 Point-to-Point Connection via Serial Interface Engineering PC and CP-8000 are connected via the serial interface (X2) with a direct cable. Web browser CP-8000 RS-232 OH 2 RS-485 OH 3 Direct cable connection 2x D-sub Wiring for Connection CP-8000 –...
Page 259
With CP-802x, a standard patch cable and a D-sub/RJ45 adapter must be used. Web browser Standard patch cable CP-802x max. 1.8 m D-sub/RJ45 adaptor Wiring for Connection CP-8000 – PC (patch cable + D-sub/RJ45 adapter) 9-pole D-sub Engineering female X2:1 X2:2 X2:3...
The parameterization via point-to-point is suitable if the engineering PC and the target device are not operated in a network. Engineering PC and CP-8000 are connected with a cross connected patch cable via one of the Ethernet interfaces (X1 or X4).
The parameterization via LAN/WAN is suitable if the engineering PC and (several) CP-8000/CP-802x are operated in a network. Engineering PC and CP-8000 are connected with a cross connected patch cable via one of the Ethernet interfaces (X1 or X4). Ethernet TCP/IP IEC 60870-5-104...
The establishing of a communication connection between engineering PC and the target device takes place via adjustable IP addresses. For the initial parameter setting of CP-8000/CP-802x, default IP addresses are available. These are specific for the respective physical connection. With local engineering, fixed IP addresses are used since they are required only temporarily for the parameterization of the target device.
Connection setup via SICAM WEB Configure IP Address for Engineering PC For the parameter setting the IP addresses predefined in CP-8000/CP-802x are used. There- by the web server of the target device assignes automatically the IP address 172.16.0.2 to the engineering PC, if this is configured for the automatic acceptance of an IP address.
WEB. Note According to the parameterization in CP-8000/CP-802x you have to enter a http or https address in the browser to establish the connection. During the first time connetion establishment via https there is a check if the corresponding security certifi- cate is installed.
Configure IP Address with Sicam_first_startup With operation in a network, an unambiguous IP address must be assigned to each connected CP-8000/CP-802x. The assignment of the IP address is dependent on the subnet mask used in the network. The identification for the assignment of the IP address happens solely via the MAC address of the target device.
Page 266
With the firmware CPC80 as of revision 09 the setting of an IP address by means of Sicam_first_startup is supported only as long as the default IP address (172.16.0.3) exists in the target device. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 267
. After the startup, the respective target device can be addressed by the webbrowser. Note The writing of the IP address with Sicam_first_startup is also possible locally via the serial interface. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 268
WEB. Note According to the parameterization in CP-8000/CP-802x you have to enter a http or https address in the browser to establish the connection. During the first time connetion establishment via https there is a check if the corresponding security certifi- cate is installed.
Interaction with the Engineering Tool 7.8.1 SICAM TOOLBOX II For the engineering of CP-8000/CP-802x serves the SICAM TOOLBOX II installed on the en- gineering PC. Before you start with the engineering, the predefined configuration parameters of the SICAM TOOLBOX II must be checked and changed, if necessary (see section 8.1.1, Presets).
7.8.2 SICAM WEB For the engineering of CP-8000/CP-802x serves the web browser installed on the engineering PC. The web browser shows HTML sites provided by the integrated web server of CP-8000/CP-802x. The parameterization is performed online in the target device.
Page 271
By clicking on this button you are able to return to the Dashboard from each website in SICAM WEB. Navigation By clicking on this button you are able to select the desired area from a drop-down list from each website in SICAM WEB. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Thus, you can see at a glance whether there is a modification of parameters (button enabled) or not (button disabled). For the user name guest the button is always disabled. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 273
You have the possibility to specifically search for certain information: ─ In the field Filter enter the word (or a part of it) to search for ─ Click the cross to reset the filter SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
In the table, click on a value of a parameter · For showing/hiding the description of the selected parameter, click on the yellow bar locat- ed to the right of the work area Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 275
Press ESC key if you want to restore the previous valid value In case of table parameters, there is the possibility to define new rows with parameters. The procedure for that is described subsequently. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 276
This is how to fill an amount of table parameters automatically: Example 1: · Select the desired column · Enter the start value and the increment, then click on Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 277
Example 2: · Select the desired column · Enter the start value and the increment, then click on The selected column is now filled according to the input: SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
HOW ALL PARAMETERS The state of the checkbox is maintained during the current session. When logging on again, the state of the checkbox is deactivated. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The language of the GUI corresponds to the language settings of your browser. If the browser language is not supported, English will be used as the standard language. Additionally, you have the option of installing language packs, see 9.3.9, Install Language Package. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
If you leave the page, the web browser is closed, the session is automatically terminated, and unsaved data is lost · If you stay on the page, you can continue workoing with the latest entered values Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Logon If you open a new browser window or a new browser tab: You are already logged on at CP-8000/CP-802x (successful logon). The logon dialog will appear after opening a new browser window or a new browser tab, after entering the IP address of the device and after a successful connection establishment.
Test of the application program Offline simulation of the application program is not possible. A simplified online test (state display, forcing of a selectable signal) is available. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
SICAM TOOLBOX II in the SICAM TOOLBOX II Online Help and in the CAEx plus Online Help. Note Screenshots shown in this chapter relate to the engineering of CP-8000. They apply analogously for CP-8021 and CP-8022. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You find the details thereto in the SICAM TOOLBOX II Online Help, chapter “TOOLBOX II Presets”, section “User/Role Administration”. Note All operation and test functions of CP-8000/CP-802x described in this manual are generally applicable for the admin role available in the SICAM TOOLBOX II. Note From SICAM TOOLBOX II V5.11 it is possible to create domain users.
If all tools are quit without logout, the user will remain logged in unless a logout from the Toolbox PC or Toolbox Server takes place. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
TOOLBOX II with the tool “Master Data Update”. You find further information in section 11.5.1.2, Importing Master Data into the SICAM TOOLBOX You find information on firmware files in section 7.3, Loadable Firmwares. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
“OPM II”. The description of the system-technical and process-technical settings can be found in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter “Telecontrol”. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
I/O Module (system technique). Note With CP-8000, the slots for the internal I/O Modules are predefined in the parameter-setting: IOM0: DO-8203, IOM1: DI-8100. For external I/O Modules, the slots IOM2 … IOM7 are available. With CP-802x, the slots IOM0…IOM7 are available for external I/O Modules.
By means of the context menu of a hardware pin or software data point, selection Edit image , you get directly to the process-technical settings of the respective signal. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
A type is defined respectively for objects, that have the same features (examples: feeder, cir- cuit breaker, disconnector). You find the instruction to define the different types in the SICAM TOOLBOX II Online Help, chapter “OPM II”, section “Types”. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The generation of the file takes place via selection of the menu Destination systems | SICAM 1703… | SICAM 1703 Transformer. You find the details thereto in the SICAM TOOLBOX II Online Help, chapter “OPM II”, section “Elcad”. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You can select an automation unit and start the comparison via the menu Parameter | Comparison AUs <-> Toolbox ). For each selected automation unit appears the indication whether the parameters are current or not current. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
"Service Programs“, section "Data Flow Test". You find further information in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "System Services", section "Data Flow Test". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
You find the instruction for this test function in the SICAM TOOLBOX II Online Help, chapter "Service Programs“, section "Topology Test". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You can save the displayed records of DEAR in a file (Format .csv) on the engineering PC. You find the information thereto in the SICAM TOOLBOX II Online Help, chapter “OPM II”, section “System Technique”, “General”, “SICAM RTUs”, “Decentral Archive Display”. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
AU OPM II ONLINE simulation (test of function chart test function select AU logic in the target chart CAEx plus system) Online Test SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Optionally to the creation of a function diagram, an instruction list (IL) with ASCII format can be imported in “CAEx plus” (tool “OPM II”, context menu of the CPU, Instruction list | Import from file ). Function Diagram (Example) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· Signals from the signal list From the signal list only signal types supported by CP-8000/CP-802x can be used in the type instance (for instance the message with TI 38 – “protection event” is not allowed). The check is performed via the data type of the signal. Also the system data point from the signal list can not be used in the type instance.
You can start the code generation via the following ways: · CAEx plus Transformer · CAEx plus, via the context menu of the Master Module (<firmware>) Start of the Program Code Generation Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 305
“CAEx plus”. You find the details thereto in the SICAM TOOLBOX II Online Help, chapter “OPM II”, section “Transform and Load”, “CAEx plus”. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Further extensive possibilities for the documentation are provided by the optional function Document Management (additional product for “CAEx plus”). You find the details thereto in the CAEx plus Online Help, chapter “Additional Products”, sec- tion “Documents Management (optional)”. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Data). Caution During a loading operation, the switching off of CP-8000/CP-802x is to be absolutely avoided, since the data on the SD card could be destroyed as a result. You find the technical description thereto in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter “Automation”, section “Open-/Closed-Loop Con-...
With user program running, the simulated value of a variable is statically overwritten. In contrast to this, inputs/outputs are not statically overwritten, rather only with a change to their process image (edge- triggered). With user program stopped, simulated values are retained. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Note Screenshots shown in this chapter relate to the engineering of CP-8000. They apply analogously for CP-8021 and CP-8022. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 310
SD card is installed in the target device · Target device is switched on · Physical connection to the target device is established · IP addresses for target device and/or engineering PC are configured Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
20 seconds. The session with the web server of the target device has started. As user name administrator you can begin now with the parameter-setting. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Display I/O status ü Force outputs ü ü Diagnosis Note No more than 1 administrator and 2 guest can be logged in to the device at the same time. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The basic settings are necessary to logon to the target device and security · Authentication procedure · Change web server password · Set IP addresses · Enable optional “Autoconfiguration” SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
SICAM WEB uses the respective role information: · Authentication via locally stored credentials ─ Usernames, passwords, profiles defined by CP-8000/CP-802x will be used · Authentication via external service (RADIUS server) ─ Usernames, passwords, profiles defined by the RADIUS server will be used ─...
Structure of the response from the configured RADIUS server: User role Administrator User role Guest Service-Type = Login-User Service-Type = Login-User Cisco-AVPair = “priv-lvl=15“ Cisco-AVPair = “priv-lvl=0“ SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
A secure password must contain at least one digit, one uppercase letter, one lowercase letter and one special character Note In case of problems with passwords please contact the Siemens Support Center. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual...
This applies for all protocols using a password for authentication, such as HTTP, HTTPS, SNMP. Note For secure password storage/https in CP-8000 a hardware revision >= ***CC is required. With the parameter you can select between non-secure or se- Secure password storage cure password storage.
Page 318
Example: You must enter the same password in both input fields (new password and verify new pass- word). Each entered character is shown as a bullet. Example: Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 319
Switching Between Secure and Non-Secure Password Secure passwords and non-secure passwords are stored separately in CP-8000/CP-802x. If you enter a non-secure password in the target device, and you activate the secure pass- word storage afterwards, you must enter a new secure password.
X1, for instance · X1: process LAN · X2: office LAN The server services of CP-8000/CP-802x are accessible on both interfaces. The further possibilities resulting thereout are described in Appendix E, Cases. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual...
CP-8022 6MF28022AA00 BB CP-8022 6MF28022AA00 CC The MAC addresses reside on the type plate sideways at the module housing (see 6.1.1.2, Type Plate and 6.1.2.2, Type Plate). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You will find more information in section 9.1.7.2, Physical Interface for the Communication. You will find further information in appendix E.6, Usage with IPSec VPN. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
APNs. PPP authentication If authentication is needed, then have to be entered. PPP user name PPP password SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You will find more information in section 9.1.7.2, Physical Interface for the Communication. You will find further information in appendix E.7, Usage of the Internal GPRS Modem (CP-8022). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Engineering via SICAM WEB 9.1.2.7 Autoconfiguration CP-8000/CP-802x provides the option of being configured automatically by means of a com- plete autoconfiguration file via DHCP service. The autoconfiguration file is a previously gener- ated CP-8000/CP-802x backup (see 9.3.2, Download Device Settings).
Page 326
It is designed for simpliest data transfer based on the client-server principle. The proto- col supports only the reading and writing of files and is suitable for applications that do not re- quire the complex procedures of FTP. The TFTP server must provide the configuration file of the respective CP-8000/CP-802x target device. Note TFTP does not provide authentication or encryption.
Page 327
If the same file name is given, the target device keeps its settings. If another name is given, the file is downloaded again and the settings are accepted. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
SICAM A8000 CP-80xx | Master module | AU common settings | common address of ASDU (CASDU). (least significant octet) and (most significant octet) result automatically in the CASDU1 CASDU2 CASDU upon storing. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
You find further information thereto in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "System Services", section "Operating States", "Firm- ware Shut Down". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Hardware (integrated on the Master Module) + loadable firmware ─ internal I/O Modules (only CP-8000) are detected automatically ─ external I/O Modules are detected automatically The protocol elements and I/O Modules supported by CP-8000/CP-802x are listed in chapter 2.1.3, Protocol Elements and 2.1.5,...
Page 331
Restart device. During startup, the settings are stored on the SD card and the configuration pages for the se- lected system elements are built in SICAM WEB. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You find more detailed information on the protocols in the manual SICAM RTUs Ÿ Ax 1703 Common Functions Protocol Elements. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
9.1.4.3 I/O Master Module In CP-8000/CP-802x you can equip 1 I/O Master Module. The hardware for the I/O Master Module as well as 2 internal I/O Modules are integrated on the Master Module. With use of external I/O Modules, these must be connected (mechanically) to the target de- vice before the engineering in SICAM WEB.
Page 334
I/O Modules. With deviation the target device notifies an error. If the once detected configuration is changed, pay attention to section 11.4.3, Adapt New Equipped I/O Modules in the Parameterization. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
9.1.5 Configuration of the Time Management · Menu Home | Settings 9.1.5.1 Time Synchronization The internal clock of CP-8000/CP-802x serves for the time tagging of generated data · from the periphery · from the optional Open/closed-loop control function · for the records in the diagnosis The resolution of the time tag is 1 ms.
Engineering via SICAM WEB 9.1.5.1.1 Time Synchronization with Multi-Point Traffic The time is sent from a central station (time master) to CP-8000/CP-802x. The time master must synchronize at least each 60 s, in order that the minimum resolution of 10 ms is achieved.
You can enable the daylight saving time and select the format for the setting of the daylight saving time rule. In the subdirectory Daylight saving time rule you can adjust the exact da- ta for the daylight saving time/normal time switchover. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Edit the fields D and T as you wish IME ZONE · Click on the button in order to load the defined time into the target device Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
For the transparent information, there is a channel for all remote stations. This is where the warning is set or reset if the filling level of the channel reaches the parameterized thresholds. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
9.1.7.2 Physical Interface for the Communication CP-8000/CP-802x can communicate simultaneously via multiple physical interfaces. For each configured protocol element an interface must be assigned exclusively. The assignment of the interface for each protocol element resides in the directory tree under...
In case of enabled IP Security always must be selected with parameter Network settings | IP address |Network connection X1 (Network connection X2), even if IP Security is used via GPRS. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
"Optimized Parameters for selected Transmission Facili- ties". After saving the settings a restart request appears. · Click , if you want to change further parameters · Click to perform a restart Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· Monitoring ACTCON Transmission with/without time tag The information objects supported by CP-8000/CP-802x can be transmitted to the control cen- ter either with time tag or without time tag. The definition happens selectively for each type identification. You find the parameters thereto in the subdirectory Transmission with/without time tag.
You find the information thereto in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "Telecontrol", section "Communication with other Automation Units", section "Data Storage", "Behavior during a Communication Failure" and section "Priori- ty Control". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
SD card. You may select this parameter referring to your field of application. The smaller the bandwidth of your communication line is the smaller the separated files should be. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
Page 346
The addresses that are calculated automatically are not shown in the web browser. If such an address is set in the parameterization of the telecontrol function, an error message occurs on attempt to apply. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Recording Grid for Measured Values This parameter defines the recording grid (the cycle time) for measured values. It can be set from 1 to 60 minutes. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Engineering via SICAM WEB 9.1.10 Configuration of the Local Process Data Display (only CP-8000) The definition of the groups happens in the · Menu Home | Settings The local process data display (cockpit) enables the visualization of the status of process sig- nals on the LCD.
The firmware of the I/O Master Module provides the functions for the technological preparation of the inputs/outputs (signal preprocessing, signal postprocessing). CP-8000/CP-802x supports 2 internal and up to 6 external I/O Modules. The following types can be used: ·...
Page 350
Enter the desired number of rows (each row corresponds to 1 signal) · Cick on the button In the following example 2 new signals have been created: Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 351
"Data Flow Control". Type Identification The description of the different type identifications (TI) resides in the manual SICAM RTUs Common Functions System and Basic System Elements, Appendix "Message Formats". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Define Name, IEC address and type identification for the new signals This is how you can delete lines: · Mark the relevant row · Click on the button Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Enter the value 1 in the input field STEP · Click on the button ILL SELECTED Result: The IOA1 of all subsequent signals is consecutively increased by the value 1. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The assigned signals are now listed in a table under the tab Assignment. Note You can enlarge the work area by clicking on the bars right and/or left beside the work area. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 355
All signals of the selected category (on the selected system element) are displayed listed in the table. Thereby, the signal name, the message address and the type identification are tak- en over from the work area for the signal generation. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
9.1.11.2.1 Configurable Logging and Display of Signal States Process signals assigned to the Master Module can be configured for the logging (alarm, event, archive) and for the display on the LCD (cockpit – only CP-8000). The following categories and signal types are designated for that:...
Page 357
When position 2 is not used, at this place an empty line will be displayed on the LCD (see 11.1.2.4.5, Cockpit). Description of the parameters see Process data message. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 358
Enter the measuring range for the value adaptation · Enter the number of decimal places for the display Description of the parameters see Process data measured value. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 359
This is how you get to the logging of signal states on the LCD: · Menu Monitoring | Events (further information see 11.1.2.4.2, Events | DEF Events) · Menu Monitoring | Alarms (further information see 11.1.2.4.4, Alarms) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Bit number (0…15; all bits) Error message sum diag- Error_location/BSE Error location/basic system element nostics table Error_location/SSE Error location /supplementary system ele- ment Error type Error class in the diagnosis Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 361
SID-ST Source identification station number if mul- tipoint traffic mode 0…99 if R-SID 0…254; if automatic, the SID will be learned SID-SSE Source identification supplementary system element SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 362
The state faulty position for double point information is displayed with this name (max. 6 characters) State_TextInt_(MSG) The state intermediate position for double point information is displayed with this name (max. 6 characters) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 363
· Key switch · Listening mode-control · A/P-control with failed SCA-RS · Switch-over disabled · Terminate binary information Failure_behavior_(RED) · Maintain status BSE_(RED) Basic system element SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 364
New address of the datapoint. The complete address consists of new CASDU1, CASDU2, IOA1, IOA2 and IOA3. New CASDU1 and CASDU2 = 255 means no address- conversion. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 365
· OR conjunction, rising edge time delayed Inversion NO/YES Fail_behav_status Conjunction type Time_delay Time delay n•100 ms · 0 0 no delay · 1 = 100 ms · 255 = 25.5 s SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Mark on the right side the signals to be assigned · Click on the button (Assign) The assigned signals are now listed in a table under the tab Assignment. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 367
In the dropdown list only those datapoints are offered that are compatible with the processing type and that are not yet in use. are irrelevant here and therefore not editable. PINS SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 368
Activate the checkbox S if you want to edit expert parameters HOW ALL PARAMETERS · Save your changes from time to time, refer to Apply Further steps: Restart device. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
0…99 if R-SID 0…254; if automatic, the SID will be learned SID-SSE Source identification supplementary system element ACTCON_yes_no Sending of ACTCON and ACTTERM SW_CO_EA – command – error acknowledgement SW_DO_TE-6460 – SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Mark on the right side the signals to be assigned · Click on the button (Assign) The assigned signals are now listed in a table under the tab Assignment. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 371
The HW pin is automatically assigned, as soon as you have defined processing type and datapoint of the signal. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 372
Activate the checkbox S if you want to edit expert parameters HOW ALL PARAMETERS · Save your changes from time to time, refer to Apply Further steps: Restart device. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Standard PM (PM inputs per modules) or input IN D17 of one BI-module as PM input for all modules Attention: Selected module must be a DI module. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 374
The belonging time is to configure here. Inversion Inversion (S) NO/YES block Blocking (= not used) (S) NO/YES Type Conditioned value type (S) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 375
SID-ST Source identification station number if mul- tipoint traffic mode 0…99 if R-SID 0…254; if automatic, the SID will be learned SID-SSE Source identification supplementary system element SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
0.1 to 25.5 RS_outp_same_state_1 Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t ≠ 0 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 377
· YES: ON is I/O with lower I/O number OFF is I/O with higher I/O number Regulating_command Use as regulating command (S) NO/YES RS_Image Parameter works only with ACP 1703 platform SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 378
0.1 to 25.5 RS_outp_same_state_1 Selection of command output and command confirmation, if return state is already end position before output. Attention: only active if RS_mon_t is ≠ 0. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 379
Command retry suppression time in seconds. command output 2-pole Within this time a command with same ad- dress is discarded without error information (s) 0.1 to 6553.5 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 380
Within this time (in sec) the enabling over the syncronisation input must occur on the com- mand. 0 = no syncronisation over syncronisation input. Attention: Function only active if sync_t = 0 0.1 to 6553.5 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 381
SID-ST Source identification station number if mul- tipoint traffic mode 0…99 if R-SID 0…254; if automatic, the SID will be learned SID-SSE Source identification supplementary system element SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 382
0 to 6553.5 RS_react_t_1 Information reaction time (S) Pulse command: 0 .. time appropriate to output time Persistent command: 0 .. time appropriate to termination time 0 to 6553.5 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 383
SID-BSE Source identification basic system element SID-ST Source identification station number if mul- tipoint traffic mode 0…99 if R-SID 0…254; if automatic, the SID will be learned SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 384
Source of state information for state infor- mation monitoring · Peripherals · Open-/closed loop control function · Both (logical OR) Sw_Seq_command_seq Switching sequence: output additional com- mand before or after the command Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 385
Within this time (in sec) the 1 out of n enabling must occur on the command. 0 = no 1 out of n enabling necessary. Attention: Function only active if sync_t = 0. 0.1 to 25.5 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 386
0 to 255 RS_Image_CASDU2 Address of corresponding return state infor- mation (S) 0 to 255 RS_Image_IOA1 Address of corresponding return state infor- mation (S) 0 to 255 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
% of temperature range 0 to 1000.0 thresh_uncond Change threshold in % of X_100% (S) AI_T: % of temperature range 0 to 103.00 block Blocking (=not used) (S) NO/YES SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 388
Zero range suppression (and check of the plausibility limits) (S) NO/YES thresh_additive Change threshold in % of X_100% (S) AI_T: % of temperature range 0 to 1000.0 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 389
Change threshold in % of X_100% (S) AI_T: power factor % of temperature range 0 to 1000.0 thresh_uncond Change threshold in % of X_100% (S) AI_T: % of temperature range 0 to 103.00 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 390
Change threshold in % of X_100% (S) AI_T: % of temperature range 0 to 1000.0 thresh_uncond Change threshold in % of X_100% (S) AI_T: % of temperature range 0 to 103.00 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 391
· 8510: 230 V - 8511: 3.25 V/SQRT3 · 8510: 400 V/SQRT3 - 8511: 3.25 V/SQRT3 transformer_Y_100% Nominal range of transformer: primary in kV or 230 V or in Ampere 1.0 to 36.0 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Source identification supplementary system element AO_U – analog output fail_subst value Substitute value, if behavior of failure is voltage parametrized on ouput substitute value (S) -1000000000000000.000 to Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 393
SID-ST Source identification station number if mul- tipoint traffic mode 0…99 if R-SID 0…254; if automatic, the SID will be learned SID-SSE Source identification supplementary system element SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
1 analog output Signal type and wiring are dependent on the respective I/O Module. Note Please consider the indications in section 2.1.5.4, Configuration Rules for I/O Modules. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
I/O Module for the entire automation unit. Thereby the desired I/O Module is selected. Note With a mixture of 1 ms and 10 ms input modules, the power monitoring should be set on an input module with 1 ms accuracy. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
If with AI-8510 the parameter transformer_X_100% is set to 100 V/√3, then the parameter transform- er_Y_100% may have a value from 1 to 36 only. The parameter transformer_Y_100% may be 230 V only if parameter transformer_X_100% is set to 230 V. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
(mean value creation and transient suppression). With the temperature acquisition (i.e. Pt20) via a resistance acquisition, the mean value crea- tion and transient monitoring must be replicated in the open-/closed-loop control function. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
If the equipped sequence of I/O Modules is suitable, an information is assigned automati- cally to a command. Otherwise no assignment takes place. You find the exact assignment in the following table. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 399
SI IOM x – IN D01 ... command IOM y – CA01/CB01 DI-610x with DO-6230 SI IOM x – IN D07 ... command IOM y – CA07/CB07 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 400
DI IOM x – IN D06/D07 ... command IOM y – CA06..CB07 x = 0..7, y = x+1, z = x+2 Note In each case the module DO-62xx must be equipped directly after the module DI-610x. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 401
DM IOM x – IN D10/D11 ... command IOM z – OUT D00/D01 DM IOM x – IN D12/D13 ... command IOM z – OUT D02/D03 DM IOM x – IN D14/D15 ... command IOM z – OUT D04/D05 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 402
─ 8 pulse commands with 2-pole wiring Note A mixed wiring (1-, 1.5- and 2-pole) on one module DO-6230 is not permissible. For varied wirings addi- tional DO-6230 must be used. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Master Module. You find further information thereto in the manual SICAM RTUs Common Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Binary Information Output", section "Deactivation or Retention on Failure". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The file type . csv must be kept. Note During the generation procedure the menu must not be left. The selection of another webpage may lead to the occurrence of undefined states. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The file is checked upon validity. If the data is valid, it is written on the SD card of the target device. Otherwise an error indication is displayed. After successful import, the following dialog appears: · Click on the button Further steps: Assigning (Master, Master, I/Os), Apply. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Engineering via SICAM WEB 9.1.12 Usage of CP-8000/CP-802x as SICAM PAS I/O The devices CP-8000/CP-802x can be used as non-licensed SICAM PAS substations. The differentiation between normal operation and operation as SICAM PAS I/O is done via a pa- rameter.
Thereto the configuration can be downloaded as XML file via a menu item in SICAM WEB. You will find further details in section 9.3.5, Download SICAM PAS I/O Configu- ration. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
By means of clicking on the side bar rightmost, the control area for the changing of process values can be opened (if the test page is opened for the first time in a session, the control ar- ea is closed). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Only if you select another I/O Module, the column width will be reset. Example: Digital input – single-point information Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 411
The updated process value of the requested group is now displayed. Note The counter group and action correspond to the identifiers FRZ and RQT in the message to the I/O Master Module. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 412
Engineering via SICAM WEB Example: Digital output – binary information state Example: Digital output – command state Example: Analog input – measured value, floating point Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The values are converted depending on the type identification (TI). Analog values are dis- played as conditioned values. The data format of the displayed inputs corresponds to the setting of the respective data point on the I/O Module (signal list). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note Errors that the target device recognizes upon forcing outputs (for instance by means of internal interlocks, application parameters, etc.) are recorded in the diagnosis (menu History). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 415
According to IEC 60870-5-101/104, chapter "Pulse Commands", section "Functions Inde- pendent of the Hardware of the Systemelement", sections "Select and Execute Command", "Set Control Location", "Command Output Time". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 416
You find further details in the manual SICAM RTUs Common Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Setpoint Values by means of Currents and Volt- ages", section "Select and Execute Command". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The event buffer contains up to 4096 records and is managed as ring buffer. This means, if the event buffer has been fully written, the respective oldest record is overwritten by the most current. The event buffer is stored non-volatile. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 419
If the event page is reopened again, all events since leaving the event page are automatically loaded. If during the leaving of the event page a ring buffer overflow occurred, only the last 4000 events can be loaded. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
A dialog for the selection of the saving path is opened. The default file name can be changed, if needed. Follow the instructions of your web browser. · You can abort the procedure by clicking on Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
By means of clicking the green button the current alarms are displayed in the table. By means of clicking the general button the alarm list is reloaded. With activated halt function, this is thereby not canceled. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 422
When selecting another menu within the session (e.g. settings, signals), the content of the table remains, but the polling for new alarms is stopped. If the alarm page is reopened again, all current alarms are au- tomatically loaded. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
A dialog for the selection of the saving path is opened. The default file name can be changed, if needed. Follow the instructions of your web browser. · You can abort the procedure by clicking on SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The signals from the periphery are distributed based on the settings in the Topology (data flow direction, data flow routing). Therefore, a system variable for the data flow routing must not be used in the instruc- tion list. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· Cycle (PLC_START) The cycle part is run through cyclically (CP-8000/CP-802x provides 1 task). The cycle time is definable by means of a system variable. You will find some selected program examples in appendix B, Examples for Instruction Lists (IL).
M_DINT_RESULT. After the call of a function (CAL) all inputs of the respective function are set to the default val- ues again. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Respectively the first result of the function block is written in the accumulator. If a function block has more than one result, then this can be accessed as with the parameter transfer. Example: CTU_TEST.CU CTU_TEST.R CTU_TEST.PV CTU_TEST CTU_TEST.CV (*access to 2nd result*) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
In the program part PLC_START Time-scale is set during running operation and can be changed by means of the applica- tion program. Example: PLC_RESET: PLC_CYCLETIME (*set cycle time 20 ms*) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Status change of a data point from the periphery · Status change of a data point from the communication The spontaneous program execution is enabled in the IL by setting the variable PLC_SINGLE (single run). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 431
1, then only spontaneous program passes take place. You find further details in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "Automation", section "Restricted Open-/Closed-Loop Control Function", "Internal Signal Processing". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
2 cycle passes are required). Note The corresponding typ identification can be generated by means of Verwendung of utilization of the com- mand "with/without time" (for instance TI 45/TI 58). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
This is how to upload an IL to the target device: · Click on the button , if an IL is available in ASCII format You have the possibility to abort the procedure. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 436
The result of the syntax check is displayed in the bottom toolbar. In case of error you will find further details in the status log. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Note For the transmission via Ethernet, it is recommended to deactivate the settings for HTTP 1.1 of your PC (Control Panel, Internet Options, tab "Advanced"). Otherwise the possibility exists that CP-8000/CP-802x can not interprete the transmitted ASCII file. 9.2.2.1.2 Load Application Programm Offline...
· Syntax, logic, addressirng · Limits for program size, cycle time, memory In case of error you find further information in the status log: Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Used program memory on the SD card of maximum number of bytes (application program size) <Number> / 4096 bytes Used variables of maximum number of bytes Test mode off / on Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
If you select a binary variable, T is displayed for TRUE and F for FALSE: Example: Analog value If you select a numeric variable, the number is displayed as follows: SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
With execution of one of the functions, the test mode is switched on: · Halt of the application program (immediately) · Cold start of the application program (per request) · Warm start of the application program (per request) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 443
When clicking the button , the application program is processed cyclically again and the test mode remains switched on. This status changes as follows: The buttons are enabled/blocked as follows: SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 444
· in the State: running, the program part PLC_START is processed cyclically again · in the State: halt, the program processing is halted Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
IL and paste it into an input field. If the variable name is invalid or empty, the type is displayed as unknown and the button is disabled. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 446
You also can regard simultaneously the status of up to 10 variables from the IL. If you click on the button , the test mode is terminated. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 447
, the new value is written on the signal and is displayed right beside the data type: If you click on the button , the test mode will be terminated. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Confirm the procedure with If settings still have not been saved, the following dialog will appear: You have the possibility to abort the procedure in order to save the changes. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 449
With the initial commissioning, the startup may last up to 15 minutes, since at this the files on the SD card will be unpacked and the system folders on the SD card are created. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
The progress is thereby displayed by the web server. This procedure can take a few minutes. Note During generation procedures the website must not be left. The selection of another website may lead to the occurrence of undefined states. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
With this procedure, all telecontrol parameters, instruction list and firmware codes are stored jointly on the SD card in the Master Module. Select thereto the submenu Restore device settings . You have the possibility to abort the procedure. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 452
With different results, the file is deleted and no changes are carried out; an error infor- mation is displayed After successful upload the target device will be restarted: · Click on the button in order to close the dialog Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The context menu of Sicam_first_startup is opened: · Change the language if needed and open the context menu again · After that click on Write flash card from A8000 parameter file SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 454
Note With operation in a network first a valid IP address must be assigned by means of the program Sicam_first_startup. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
(SCL) as representation format. Depending on the purpose of the SCL file, it is classified into various file types. CP-8000/CP-802x devices support the file types ICD and IID. The corresponding files can be uploaded only to IEC 61850 protocol elements.
Page 456
During loading procedures the website must not be left. The selection of another website may lead to the occurrence of undefined states. With startup the uploaded file will be stored on the SD card under \ETx5\5_<BSE>_<ZSE>.icd. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
9.3.5 Download SICAM PAS I/O Configuration For the usage of CP-8000/CP-802x as SICAM PAS I/O the configuration of the data points can be synchronized with a superior device SICAM PAS. The configuration of the data points can be downloaded as XML file and be stored on the en- gineering PC.
Page 458
Follow the instructions of your web browser. The file name is put together of PASIO_CFG<date>_<time>.xml. · After successful generation click on in order to close the dialog Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 459
In order to read the XML file you must remove the SD card from the target device and put it in- to a card reader installed on your engineering PC. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
Page 460
TI 48 (0 = direct) select_execute_t SETPOINT_SCALED_SEL_BEFORE_EXE for TI 49 (0 = direct) select_execute_t SETPOINT_FLOAT_SEL_BEFORE_EXE for TI 50 (0 = direct) select_execute_t SEND_CMD_END_TERMINATION for TI 48…TI 50 (0 = terminat- Termination_t Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
(see 9.1.11.2.1, Configu- rable Logging and Display of Signal States). Select thereto the submenu Download process data archive . The following dialog will appear: SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 462
You have to abort the procedure and try again. If the error is persistent, check the communi- cation and/or – if possible – trigger a startup of the target device. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 463
The download can be aborted at any time by means of: · Cancel function via web browser · Closing the web browser Example for an Archive File SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Subsequently the file is checked upon validity. If the data is valid, it is written on the SD card of the target device. Otherwise, an error information is displayed. After successful upload the following dialog appears: · Click on the button Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Subsequently the file is checked upon validity. If the data is valid, it is written on the SD card of the target device. Otherwise, an error information is displayed. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Click Select a file in order to open the selection dialog · Select the source directory and the source file (the file type must be *. nls) · Click on the button Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 467
The newly installed language is available in the dropdown list of the Logon dialog. Note Apart from the standard languages English and German, presently no language packages are defined. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 468
Engineering via SICAM WEB Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Multiply devices · Online connection to devices via SICAM WEB You will find the instructions for this tool in the document SICAM Device Manager User Manu- al (D51-003). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
11.6 Remote Maintenance ................... 523 This chapter describes the internal checks and displays of the devices CP-8000/CP-802x, which diagnosis options are available, what is to be considered with the exchange of the sys- tem or external modules, and how functional updates can be loaded into the system.
Service 11.1 Operation and Display Elements The operation and display elements of CP-8000/CP-802x are located on the front of the re- spective housing. CP-8000 provides an LED status display and an integrated LCD text display. Display RS-232 Status and Function LEDs...
· 0.1 s interval: Loading of firmware into the Flash PROM · Sum error (voltage failure, power supply defective, ™ at least one of the monitored voltages smaller than setpoint value) · Startup SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 474
1 s: registered to mobile network 2 s: error (SIM, registration, IPsec, …) · Connection not established ™ · Startup ž Yellow Package X7 Data exchange with GPRS modem ™ Startup Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· Open list EDIT Edit value Accept 11.1.2.2 Device Information The menu itemt Device information is devided in the submenus · Device · Language · Display · Startup page Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
With the function keys ▲ and ▼ you can select a language. Press the function key OK to activate the selected language. Submenu Submenu Display/settings Meaning/range – Deutsch Language English SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
For changing press the function key + or – and accept with OK. Submenu Submenu Display/settings Meaning/range – Contrast 1…9 Display Backlight level 1…3 Backlight dimmed 0…2 Time until dimmed 0…99 ¨◄►þ Invert display Display test Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Cockpit Cockpit Note If the selected page is not existing, then the superior menu will be displayed. Example: selection of an I/O Module that is not equipped. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Menu with external SICAM I/O Modules (exam- Menu with external SICAM TM ple) I/O Modules (example) With the function keys ▲ and ▼ you can select an I/O Module. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 481
AO: output value 2.1.4 IOM3: 2.1.5 IOM4: 2.1.6 IOM5: 2.1.7 IOM6: 2.1.8 IOM7: dependent on the respective module percentage of the measuring range of the respective module SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
No connection established <Firmware> PRE2: ™ Connection not established ™? 2.2.4 No detailed information avail- <Firmware> PRE3: able for this protocol No interface is assigned to this protocol Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 483
Meaning of the status symbols: ˜ Connection is established ™ Connection is not established This information is displayed if there are no details available for this protocol. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The submenu Cockpit displays up to 32 configurable groups with up to 255 signals each. The submenu I/O Modules displays the signal states at the inputs and outputs of the equipped I/O Modules. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
11.1.2.4.1 Events | ALL Events The submenu Events is devided in the sub- menus · All Events · DEF Events (process events) · DIA Events (diagnosis events) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 486
Date of the selected event Time stamp Timestamp of the selected event Time quality bit !: invalid (optional) Indication of daylight-saving S: daylight-saving time (op- time tional) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Date Date of the selected event Time stamp Timestamp of the selected event Time quality bit !: invalid (optional) Indication of daylight-saving S: daylight-saving time time (optional) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Date Date of the selected event Time stamp Timestamp of the selected event Time quality bit !: invalid (optional) Indication of daylight-saving S: daylight-saving time time (optional) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Example: measured values In this example, 2 measured values are as- signed to the group positions 1 and 5. Positions 2, 3 and 4 are not assigned. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
(only with equipped I/O Master Module). The image besides shows the standard sub- menu. The menu structure and the display corresponds with the submenu Configuration | I/O Modules (see section 11.1.2.3.1, Modules). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
· successional modules are not operational ™ ˜ Check of the configuration for pulse Configuration error · Pulse command output is locked for all command output modules Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 493
By means of the lighted display this state can not be identified clearly. This state can now only be ended with a Power up or Reset. The reset can be initiated by the SICAM TOOLBOX II as well as with SICAM WEB. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
· Operation tution value is output Communication failure Substitution value is output Master Module Failure Master Module Substitution value is output SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
You find the error indications recorded in the online diagnosis in the SICAM TOOLBOX II Online Help, chapter "Parameter Documentation and Diagnosis Info", section "Diagnosis In- formation", under the respective firmware. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
SICAM TOOLBOX II 11.3.2.1 Connection Possibilities for the Diagnosis For the access to the diagnosis data of CP-8000/CP-802x, an online connection of the engi- neering PC to the target device is required. Reading access is at the same time possible local- ly and from the distance.
Page 498
Remote connection via further automation units Ethernet TCP/IP TOOLBOX II R evisio n: License Pak: Ver sion 5 | Sie me ns A G CM-1820 Toolbox cable (EIA-232) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Service 11.3.2.2 Diagnosis Overview CP-8000/CP-802x contains extensive diagnosis functions for monitoring the system. Since the firmware executes the appropriate error monitoring routines automatically, no settings by the user are necessary thereto. With the tool "Diagnostic" (TOOLBOX II | Service Programs | Diagnostic), system states and error information items can be read, and printed out if required.
Page 500
You find the d description of the diagnosis functions in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "System Services", section "Diagno- sis". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Bus runtime You find further information in the manual SICAM RTUs Common Functions System and Basic System Elements, chapter "Automation", section "Open-/Closed-loop Control Function", section "Display Status Information". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 502
· of the "openPLC" You find the exact details in the CAEx plus Online Help, chapter "Target System Connection", section "Program Messages for Target System Connection". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
SICAM WEB 11.3.3.1 Connection Possibilities for the Diagnosis For the access to the diagnosis data of CP-8000/CP-802x, an online connection of the engi- neering PC to the target device is required. Reading access is also possible if the target de- vice was engineered via the SICAM TOOLBOX II.
Service Connection via Ethernet Ethernet TCP/IP 11.3.3.2 Diagnosis Overview CP-8000/CP-802x provides an automatic diagnosis system. This recognizes ocurring errors, and generates corresponding indications. The system diagnosis can be read out in different menus: · Device information · Diagnosis indications ─ Diagnosis status ─...
Prerequisite is that the web server has been activated (in the directory tree under SICAM A8000 CP-80xx | Master module | PRE <0…3>: Ethernet Interface IEC61850 Ed.2 | HTTP web server = enabled). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 506
You find further information for that in the manual SICAM RTUs Common Functions Protocol Elements, chapter "LAN Communication (61850)", section "Web Server". Example for CP-8022 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The diagnosis shows all current errors in the target device. The display takes place in plain text in chronological order. The content of each column (exception: Detail info) can be sorted descending or ascending. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 508
The existing table will be deleted and all detail information will be read out completely from the device and will be listed in a table. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Error text Short description Error state Raising or cleared error Detail info Detailed description Error class Board failure Communication Intern Startup Warning Event Error ID Failure ID SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 510
The existing table will be deleted and only those entries which have been created by the de- vice since the last reading procedure will be read out from the device and will be listed in a ta- ble. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
A dialog for the selection of the saving path is opened. The default file name can be changed, if needed. Follow the instructions of your web browser. · You can abort the procedure by clicking on SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Time stamp of the security-relevant information System address Address of the corresponding hardware Information Region number Component Master Module address Supplementary Module address Class Notice Warning Alert Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
A dialog for the selection of the saving path is opened. The default file name can be changed, if needed. Follow the instructions of your web browser. · You can abort the procedure by clicking on SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The check result is displayed in the bottom tool bar. In case of error the details are displayed in the status log. · Click on the global button , if you want to read the status log Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
If a hardware error exists, a replacement of the system or of the external I/O Module is re- quired. 11.4.1.2 SD Card CP-8000/CP-802x accesses with each startup the SD card and checks it. The following cases lead to errors with the SD card: ·...
(see section 11.5, Firmware Update). After the replacement of a system, this is operational after a startup. Note With CP-8000, internal modules cannot be exchanged. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
With startup the parameterization of the learnt I/Os is built up newly with the default values. 11.4.3.1 Adding I/O Modules Additionally equipped I/O Modules are recognized by CP-8000/CP-802x and "learnt“ upon startup, without notifying an error thereby. With parameterization via SICAM WEB, new mod- ules are added automatically in the directory tree.
Removing or inserting the SIM card is allowed only in the de-energized device! Subsequently, the access data must be adapted in the parameterization, see 9.1.2.6, Settings for Internal GPRS Modem (CP-8022). Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Service 11.5 Firmware Update In CP-8000/CP-802x, a new system element or the functionality of a system element can be updated in need. For each system element, an individual loadable firmware is provided. You find information thereto in section 7.3, Loadable Firmwares.
The latest firmware revision available in the SICAM TOOLBOX II is loaded You find the instructions thereto in the SICAM TOOLBOX II Online Help, chapter "Service Programs", section "Load Firmware". Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
For the loading via SICAM WEB an already running firmware CPC80 and SWEB00 must exist in the target device. This is already loaded on the SD card equipped in the target device ex works. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
RY-LED and the red ER-LED do not light up. An access with the SICAM TOOLBOX II is no longer possi- ble in this case. In this case please consult our Customer Support Center. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
On the clients is no installation required, the access to the web server takes place via the Mi- crosoft Internet Explorer ® (as of version 5.0). You find a detailed description of the configuration in the SICAM TOOLBOX II Online Help, chapter "web.engineering". SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note: Only for CP-802x! Spare Part Designation Article number CM-8812 Bus Connector SICAM I/O C53207-A5812-D481 10 pcs. (This bus connector is included with all PS-862x and PS-864x modules) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
DI-8112 Digital Input 6MF2811-2AA00 2x8, DC 110 V DI-8113 Digital Input 6MF2811-3AA00 2x8, DC 220 V DO-8212 Digital Output Relay 6MF2821-2AA00 8x DC 24 to 220 V/AC 230 V Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 529
AI-8511 Analog Input 6MF2851-1AA00 3x U (LoPo), 3x I (LoPo) AO-8380 Analog Output 6MF2838-0AA00 4x ±20 mA/±10 V CM-8820 CT Adapter for AI-8510 6MF2882-0AA00 3xI 1 A_5 A/225 mV SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
(This bus connector is included with all PS-862x and PS-864x modules) A.3.1 Accessory Designation Article number CM-8811 Coupling Module for 6MF2881-1AA00 SICAM I/O Modules Note: Only for SICAM I/O Modules at CP-8000! Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
6MF1113-0GB02-0AA0 2x8, DC 24 to 60 V 1 ms DI-6103 Digital Input 6MF1113-0GB03-0AA0 2x8, DC 110/220 V 1 ms DI-6104 Digital Input 6MF1113-0GB04-0AA0 2x8, DC 220 V SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Note: Only for SICAM TM I/O Modules at CP-8000! Bus termination for TM housing 6MF1313-0GA50-0AA0 Note: The bus termination for TM housing (TC6-050) is part of this item Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Order Information A.10 Engineering Tools A.10.1 SICAM TOOLBOX II Note Please note that CP-8000/CP-802x is supported by the SICAM TOOLBOX II as of version 6.01. Designation Item number SICAM TOOLBOX II V6 License D30-017-6 Catalog, License Ordering SICAM TOOLBOX II S38-100 The SICAM TOOLBOX II is supplied on an USB stick.
(*store at input 0 for AND function*) I_030_003_000_000.VALUE (*read input IN01*) AND.IN1 (*store at input 1 for AND function*) (*call function*) M_BOOL_TESTFLAG (*store in a flag*) O_030_008_000_000.VALUE (*store as single command output*) SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
(*sum of operating hours = minutes*) (*divided by 60*) To reset the counter score it is necessary to reset the counter (CTU_COUNTER.R) as well as the flag with the retained value (M_DINT_MINUTESOLD). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 548
(*besides reset of the time the*) CTU_COUNTER.R (*counter input R is set to "0"*) M_BOOL_RESET (*if the flag is set to "1"*) CALC ResetCounter (*call the subroutine ResetCounter*) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
CU input of the counter causes an increment. Therefore the ap- plication program handles the R input before the CU input of the counter. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
Page 550
(*Module 9 - the output is reset during the input is detected as bounc- ing*) M_BOOL_INPUT00 AND.IN0 M_BOOL_BOUNCING00 STN AND.IN1 CAL AND (*call module 9 – if bouncing, then "0"*) O_030_002_000_000.VALUE (*output of input information*) Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
· During the transmission a device · Otherwise detach the SD card from connection fault may have the target device and overwrite it been occurred again with valid parameters offline Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 555
(e.g. menu figuration page correctly when the indication was quitted prematurely) appears, PLOAD SUCCESSFUL with hyperlink to the target device SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Settings in Microsoft Windows 8 ..............558 Settings in Microsoft Windows 7 ..............568 Settings in Microsoft Windows Vista ............. 577 Restore Settings for the Internet Use ............586 SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The Hardware Wizard starts, which guides you comfortably through the installation. Place a and click Next>. tick in the box D ’ T DETECT MY MODEM W ILL SELECT IT FROM A LIST Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 559
TANDARD ODEM In this window mark the wanted port and confirm the input with Next>. Complete the modem installation in the next window with the button Finish. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The modem installation is now complete! D.1.2 Network Configuration To establish a new data-communication connection, select via the Start menu the item Control Panel. Double-click on the symbol Network and Sharing Center. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 561
ET UP A NEW CONNECTION OR NETW ORK In the following window, as Network Connections Type select the item C ONNECT TO THE . Then go to Next>. NTERNET SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 562
ET UP A , and continue. NEW CONNECTION ANYW AY As next step you have to select . Please click on D CONNECT ION MANUALLY UP CONNECTION and continue. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 563
A window appears with the connection test, that you can abort. Then select S ET UP THE CONNECTION ANYW AY Click now on the network icon in the notification area of the Taskbar. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 564
Now a view of all available networks opens. Select hereby the new dial-up connection and click on Connect. Click in the window “Connect …” on the button Properties. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 565
Mark the line Internet Protocol Version 4 (TCP/IPv4) and then click on Properties. In this window the items O and O BTAIN AN ADDRESS AUTOMAT ICALLY BTAIN SERVER must be selected. Continue with Advanced…. ADDRESS AUTOMAT ICALLY SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 566
Click now on the network icon in the notification area of the Taskbar. Now a view of all available networks opens. Select hereby the new dial-up connection and click on Connect. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 567
Set Up Dial-Up Connection on Engineering PC Click in the window „Connect …“ on the button Dial. The installation and configuration is thereby complete! SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
W ILL SELECT IT FROM A LIST Under M : select (Standard Modem Types)and under M : select a ANUFACTURERS ODELS , then click Next>. 33600 TANDARD ODEM Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 569
115200, as shown in the lower window. If this setting shows another value, please PEED correct it and confirm with OK. The modem installation is now complete! SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
To establish a new data-communication connection, select via the Start menu the item Control Panel. Double-click on the symbol Network and Sharing Center. Click on S ET UP A NEW CONNECTION OR NETW ORK Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 571
In the following window, as Network Connections Type select the item C ONNECT TO THE . Then go to Next>. NTERNET As next step you have to select CONNECT ION MANUALLY Click on D and continue. UP CONNECTION SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 572
Pay attention to the ticks in the boxes. Finally, click on Connect. A window appears with the connection test, that you can abort. Then select S ET UP THE CONNECTION ANYW AY Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 573
For advanced settings and to check the new dial-up connection, click in the “Network and Sharing Center” on C . Click with the right mouse button on ONNECT TO A NETW ORK SIE and select Properties. ONNECTION TO SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 574
Mark the line Internet Protocol Version 4 (TCP/IPv4) and then click on Properties. In this window the items O and O BTAIN AN ADDRESS AUTOMAT ICALLY BTAIN SERVER must be selected. Continue with Advanced…. ADDRESS AUTOMAT ICALLY Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 575
In order to set up a connection, select via the Start menu the item Control Panel. Click on C in the Network Sharing Center. Select the connection and ONNECT TO A NETW ORK click on the button Connect. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 576
Set Up Dial-Up Connection on Engineering PC Click in the window "Connect …" on the button Dial. The installation and configuration is thereby complete! Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The Hardware Wizard starts, which guides you comfortably through the installation. Place a and click on Next>. tick in the box D ’ T DETECT MY MODEM W ILL SELECT IT FROM A LIST SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 578
Standard 33600 bps Modem, then click Next>. In this window mark the wanted port and confirm the input with Next>. Complete the modem installation in the next window with the button Finish. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The modem installation is now complete. D.3.2 Network Configuration To set up a new data-communication connection, select via the Start menu the item Control Panel. Double-click on the symbol Network Connections. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 580
Go to C REATE A NEW CONNECT ION In the following window select the item C as network connection ONNECT TO THE NTERNET type. Then continue with Next>. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 581
D . Furthermore, enter a and a UP PHONE NUMBER USER NAME PASSW ORD Pay attention to the ticks in the boxes. Finally, click on Connect. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 582
Set Up Dial-Up Connection on Engineering PC Then a window appears with the connection test, that you can abort. Then select S ET UP THE CONNECTION ANYW AY To finish click on Cancel. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 583
For advanced settings and to check the new dial-up connection click with the right mouse but- and select the menu item Properties. ton on D SIE D ONNECTION UP CONNECTION Check the settings and if necessary correct them. Then confirm with OK. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 584
GATEW AY ON REMOTE NETW ORK In order to set up a connection, select via the Start menu the item Connect to and select Di- al-up Connection SIE. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 585
Or you can set up the connection via this window, if it is still open, by clicking the button Connect. Click in the window "Connect …"on the button Dial. The installation and configuration is thereby complete. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
In order to set up a connection to SICAM MIC now, you must start at first the new dial up connection manually, and afterwards you can connect with the respective target device. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 587
Usage with IPSec VPN ................. 595 Usage of the Internal GPRS Modem (CP-8022) ..........599 This chapter shows the network structure of typical applications of CP-8000/CP-802x. Note The IP-addresses and subnet maks shown in these examples are exemplary and serve only for better understanding.
(in this case both Ethernet interfaces use the MAC address of X1) In this configuration CP-8000, CP-8021 or CP-8022 can be reached with the set IP ad- dress via both Ethernet interfaces (X1 or X4). The unused port is not deactivated.
(Ethernet-Interface, X1 or X4, can be set by parameter) · Communication with the external system via IEC 60870-5-104 (Ethernet interface, X1 or X4, can be set by parameter) · CP-8000, CP-8021 or CP-8022 is used as switch between control system and external system · 1 IP address ·...
(Ethernet interface, X1 or X4, can be set by parameter) · CP-8000, CP-8021 or CP-8022 serves as switch between control system and SICAM TOOLBOX II By means of SICAM TOOLBOX II, which is connected via the integrated switch, it is pos- sible to reach the local SICAM A8000 and further SICAM RTUs components via the “Con-...
The data packages are sent via that interface (X1 or X4) to which the respective source IP address (Own IP address X0 X1) is assigned. Own IP address Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 593
Use Cases Example A This example shows the usage of 2 static routes from CP-8000, CP-8021 or CP-8022 via 2 gateways to control center in different IP networks. Control Center Zone 1 Control Center Zone 2 Control Center A Control Center B...
Page 594
Source IP address - Static route 0 192.168.94.1 Own IP address X1 255.255.255.0 Subnet Mask X1 Source IP address - Static route 1 10.9.16.1 Own IP address X4 255.255.255.0 Subnet Mask X4 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
IPSec tunnel supervision by ping 1 | Ping peer IP address if NO: Encryption algorithm Authentication algorithm Diffie Hellman group Note CP-8000, CP-8021, CP-8022 and the remote station must be configured in different networks when IPSec VPN is used. The parameters Remote site <x> |Subnet IP address Remote site <x>...
E S C Note The default gateway under must be the external visible Local site | VPN client default gateway IP address of the router, in this example 192.168.1.151. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
The default gateway under must be the external visible Local site | VPN client default gateway IP address (=2 IP address) of the GPRS router, in this example 192.168.1.2. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
The default gateway under must be the external visible Local site | VPN client default gateway IP address (=2 IP address) of the GPRS router, in this example 192.168.1.2. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
In Google Chrome ® the cache must be deleted before the logon with SICAM WEB via https. For routing in 2 tunnels it is necessary to define both remote stations (remote site 1 and remote site 2). SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
IP address) Process Note Siemens recommends with this configuration the parameterization of an IP address for the local LAN interfaces X1/X4 as a precaution. Thereby you can prevent a “lockout” due to an erroneous GPRS config- uration. When GPRS is activated, the local LAN interfaces X1 and X4 are operated in switch mode.
255.255.255.0 Process Note Siemens recommends with this configuration the parameterization of an IP address for the local LAN interfaces X1/X4 as a precaution. Thereby you can prevent a “lockout” due to an erroneous GPRS config- uration. When GPRS is activated, the local LAN interfaces X1 and X4 are operated in switch mode.
Subnet mask GPRS VPN1 Process Note Siemens recommends with this configuration the parameterization of an IP address for the local LAN interfaces X1/X4 as a precaution. Thereby you can prevent a “lockout” due to an erroneous GPRS config- uration. When GPRS is activated, the local LAN interfaces X1 and X4 are operated in switch mode.
An automation unit consists of at least 1 mounting rack or 1 DIN rail (depending on system), 1 power sup- ply and 1 Master Module, as well as optional I/O Master Modules and optional protocol elements. SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted...
Page 606
With dial-up traffic, the connection setup and the data transmission takes place only upon interrogation by the central station. Command direction Transmission facility from the central station to a substation Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 607
Comprises 16 diagnostic bits (of a system diagnostic class) that commonly belong logically together Detailed diagnostic table Contains all diagnostic bits recognized by the system elements ž Digital input SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 608
Firmware Program that is not changeable by the user, that adds a predefined and parameter-settable functionality to the hardware Floating Point Unit ž Function diagram Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 609
(dependent on load or priority) Local parameter Parameter that is managed on the own module (firmware) and is used only there SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 610
The periodical control circuit check detects if the command circuits are ready to function correctly, without activating the actuator.Control circuits are checked one by one, by activating all its relays, one by one, thus closing the control circuit with high restistance. Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 611
Network device for connecting two independent network segments as internet and LAN RS-232 Standard for serial data transmission RS-485 Standard for serial data transmission Request to Send (switch on transmit device), control line of an RS-232 interface SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted DC8-037-2.02, Edition 10.2017...
Page 612
Serves for the exchange of a process signal or a derived information (inclusive status) between the I/O Master Module and the own automation unit, another automation unit or a control center system ž Supplementary system element Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...
Page 613
Glossary Tool for the administration of SICAM TOOLBOX II data (Siemens Stammdaten Manager); reserved for developer of Siemens AG. Supplementary system element Supplementary system elements are situated hierarchically below the Master Module; there are I/O Master Modules, and protocol elements...
Page 614
Glossary Web services Web standard for function calls between independent devices Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual DC8-037-2.02, Edition 10.2017...