6.6.5
Relay Programming Options
The two on board relays of the control panel can be selected to activate for general alarm,
general supervisory, resettable auxiliary power or door holder power. Relay 1 is defaulted to
activate for general supervisory. Relay 2 is defaulted to activate for general alarm.
6.6.5.1 General System Relay Silence Option
This option defaults to silenceable. This option controls the silencing behavior for Relay 1,
Relay 2 and the general output relays at SLC addresses 141 through 148.
6.6.6
Dialer Phone Line Programming Options
The programming options below are available for each of the two phone lines.
6.6.6.1 Line Prefix
This option allows the insertion of digits, delays and special tone characters to be dialed
before the phone number stored in the account option is dialed. The default setting is to not
have any prefix.
6.6.6.2 Dial Tone Detection
The default configuration for this option is "Enabled". If set to "Disabled", the dialer will not
check for the presence of dial tone on the associated phone line prior to making a call.
6.6.6.3 Line Monitoring Enabled (Y/N)
This option is used to enable phone line voltage supervision. It defaults to No.
6.6.6.4 Dialing Option
The dialer can use touch tone or pulse dialing when calling the central station. The options for
dialing are touch tone only, dial pulse only or alternating touch tone/dial pulse when multiple
attempts are used to connect with the central station. The default setting is touch tone only.
6.6.6.5 Pulse Dialing Format
There are two duty cycle options for the pulse dialing. US format is 60/40. European format is
66/34. The default setting is the US format.
151450
Programming