1. Specifications Cassette Type Inverter heat pump Model name AUU9RLF AUU12RLF AUU18RLF Power supply 208/230 V ~ 60 Hz Available voltage range 187—253 V 2.64 3.52 5.28 Rated Btu/h 9,000 12,000 18,000 Cooling 0.90—3.60 0.90—4.00 0.90—5.90 Min.—Max. Btu/h 3,100—12,000 3,100—13,600 3,100—20,100...
Page 7
Cassette Type Inverter heat pump Model name AUU9RLF AUU12RLF AUU18RLF NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
2. Dimensions 2-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF Unit: in (mm) • Cassette grille mounting state 20-7/8 (530): Hanging bolt position 5-5/16 9-13/16 (250) (135) op view Be sure to leave Maintenance space maintenance space for future service at the designated position.
Page 9
• Standard type grille (UTG-CCGF) Side view 27-9/16 (700) Bottom view • Grid type grille (UTG-CCGFG) Side view 24-7/16 (620) Bottom view - 5 - 2-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF 2. Dimensions...
Page 10
• The ceiling height cannot be set in the 3-way outlet mode. Therefore, ceiling height setting change by function setting 20 is prohibited. For details, refer to "Contents of function setting" page 36. - 6 - 2-1. Models: AUU9RLF, AUU12RLF, and AUU18RLF 2. Dimensions...
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: AUU9RLF Indoor temperature °FDB °FWB °FDB...
7. Safety devices Model Type of protection Protection form AUU09-18RLF Circuit protection Current fuse (PCB*) 250 V, 3.15 A Activate: 212 ± 27 °F (100 ± 15 °C) Activate Fan motor stop Fan motor protection Thermal protection program Reset: 203 ± 18 °F Reset (95 ±...
8. External input and output Connector Input Output Remarks CN102 Control input (Operation/Stop) — See external input/output CN103 — Operation status output settings for details. — Fresh-air control output 8-1. External input • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. •...
Page 31
Circuit diagram example • Contact capacity: DC 24 V or more, 10 mA or Indoor unit more. Connected unit control PCB • *: Make the distance from the PCB to the con- Connector Example: Switch nected unit within 33 ft (10 m). •...
8-2. External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. ...
8-3. Fresh-air control output Signal linked to the indoor unit fan on can be output. NOTE: In cold-air prevention control operation, the signal becomes off. Circuit diagram example Indoor unit Connected unit control PCB Example: Fan Example: Relay unit 12 V Connector Relay...
9. Remote controller 9-1. Wired remote controller ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
Page 35
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: in (mm) 4-3/4 (120) 11/16 (18) Front view Side view Size (H × W × D) in (mm) 4-3/4 × 4-3/4 × 11/16 (120 × 120 × 18) Weight oz (g) 5.6 (160)
10. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 10-1. Function settings on indoor unit By using some components on the PC board, you can change the function settings. Related components on the PC board and the applicable settings Component Setting content...
Page 37
¢ DIP switch setting • Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00. Remote DIP switch number controller...
10-2. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment. ¢ Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller.
Page 39
Repeat steps 3 to 6 to perform additional settings. Press the SET TEMP. buttons ( ) and FAN button simultaneously again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1 minute if no opera- tion is performed.
Page 40
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign Ceiling height...
Page 41
4) Room temperature control for indoor unit sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00"...
Page 42
7) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 43
10) Room temperature control for wired remote controller sensor NOTE: Before performing this setting, refer to Function 95. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to "Both"...
10-3. Function settings on wired remote controller By using some components on the wired remote controller, you can change the function settings re- lated on the remote controller. ¢ Component location Components on the wired remote controller used for the function settings are located as shown in the following figure.
Page 45
• SW4: °F/°C switch Displayed unit for temperature can be switched between Fahrenheit (°F) and Celsius (°C). °F/°C switch Factory setting °C °F ♦ • SW6: Memory backup setting Set to ON to use the batteries for memory backup. If the batteries are not used, all of the set- tings stored in the memory will be deleted if there is power failure.
12. Optional parts 12-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal screen, Monitor Mo 10:00AM Mode Set temp. wide and large keys easy to press, Wired remote ° F user-intuitive arrow key. Cool High UTY-RVNUM Icon check: controller Menu...
12-2. Cassette grille Exterior Part name Model name Summary When using this cassette grille, the Cassette grille UTG-CCGF ceiling openings become smaller. This cassette grille can be installed Cassette grille UTG-CCGFG appropriately on the grid type ceiling common in the office. 12-3.
1. Specifications Type Inverter heat pump Model name AOU9RLFC AOU12RLFC AOU18RLFC Power supply 208/230 V ~ 60 Hz Available voltage range 187—253 V Starting current Cooling 795 (1,350) 1,207 (2,050) 1,457 (2,475) Airflow rate CFM (m Heating 989 (1,680) 1,083 (1,840) 1,386 (2,355) Type ×...
2-2. Installation space ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 53
Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 60 (1,500) or more 10 (250) 12 (300) or more or more When there are obstacles at the front and rear.
Page 54
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 79 (2,000) or more 119 (3,000) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 40 (1,000) or more 10 (250) or more...
5. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 5-1. Models: AOU9RLFC and AOU12RLFC NOTE: Values mentioned in the table are calculated based on the maximum capacity.
5-2. Model: AOU18RLFC NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length COOLING — — — 0.951 0.950 — — 0.979 0.967 0.966 Indoor unit is higher than outdoor unit *1 — 0.988 0.983 0.971 0.970 0.994...
6. Additional charge calculation 6-1. Models: AOU9RLFC and AOU12RLFC Refrigerant type R410A lb oz 2 lb 10 oz Refrigerant amount 1,200 ¢ Refrigerant charge 49 or less 66 (Max.) Total pipe length 0.22 oz/ft 15 or less 20 (Max.) (20 g/m) Additional charge 6-2.
9. Electrical characteristics Model name AOU9RLFC AOU12RLFC AOU18RLFC Voltage 208/230~ Power supply Frequency 13.4 17.3 MCA * Starting current MAX. CKT. BKR * Power cable Wiring Size spec. * Connection Limited wiring cable * ft (m) 60 (18) 75 (22) length *1: Minimum Circuit Ampacity (Calculation based on UL1995) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
10. Safety devices Model Type of Protection form protection AOU9RLFC AOU12RLFC AOU18RLFC 250 V, 20 A Current fuse (Near the terminal) 250 V, 25 A 250 V, 5 A Circuit protection 250 V, 15 A 250 V, 10 A Current fuse (Main PCB) 250 V, 3.15 A 212±27 °F (100±15 °C) Activate...