Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Page 6
(Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the directive, and with the product standards EN 60255-6 and EN 60255-27 for the directive.
Section 1 1MAC302441-MB A Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation...
Section 1 1MAC302441-MB A Introduction Product documentation 1.3.1 Product documentation set Application manual Engineering manual Installation manual Operation manual Technical manual Communication Protocol manual Protocol Points List manual Figure 1: The intended use of manuals in different lifecycles The engineering manual contains instructions on how to engineer the IED using the different tools in PCM600.
1.3.2 Document revision history Document revision/date Product version History A/11/23/2010 First release Download the latest documents from the ABB web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-101/104 Communication Protocol Manual 1MAC306892-MB Symbols and conventions 1.4.1...
Section 1 1MAC302441-MB A Introduction 1.4.2 Manual conventions Conventions used in IED manuals. A particular convention may not be used in this manual. • Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. •...
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Section 2 IEC 60870-5-101/104 data mappings Overview This document describes the IEC 60870-5-101/104 data points and structures available in RER620 Ver. 1.0. The point tables show all the available IEC 60870-5-101/104 data points in this IED. The points are grouped into four tables: Analog Values, Binary Controls, Indications, and Integrated Totals and Regulating Step Positions.
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Point list for RER620 Ver. 1.0 Table 2: Analog values No events 61850 Path Disabled Description Multiplier Interrogation CMMXU1.A.phsA.cVal.mag.f 8000 "IA,IB,IC:phase A amplitude" CMMXU1.A.phsA.instCVal.ang.f 8001 "IA,IB,IC:phase A angle" CMMXU1.A.phsB.cVal.mag.f 8003 "IA,IB,IC:phase B amplitude" CMMXU1.A.phsB.instCVal.ang.f 8004 "IA,IB,IC:phase B angle"...
Page 19
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation VMMXU1.PPV.phsCA.cVal.mag.f 8058 "VA,VB,VC:phase CA amplitude" VMMXU1.PPV.phsCA.instCVal.ang.f 8059 "VA,VB,VC:phase CA angle" VMMXU2.PhV.phsA.cVal.ang.f 8061 "VA,VB,VC(2):phase A angle" VMMXU2.PhV.phsA.cVal.mag.f 8062 "VA,VB,VC(2):phase A amplitude" VMMXU2.PhV.phsB.cVal.ang.f 8063 "VA,VB,VC(2):phase B angle" VMMXU2.PhV.phsB.cVal.mag.f 8064 "VA,VB,VC(2):phase B amplitude"...
Page 20
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation RDRE1.MemUsed.stVal 10112 DFR:MemUsed status SDARREC1.AutoRecSt.stVal 10113 79:AutoRecSt status SDARREC1.ShotPntr.stVal 10114 79:ShotPntr status SPHPTOV1.StrDur.mag.f 10115 59-1:StrDur magnitude SPHPTOV2.StrDur.mag.f 10116 59-2:StrDur magnitude SPHPTOV3.StrDur.mag.f 10117 59-3:StrDur magnitude SPHPTUV1.StrDur.mag.f 10118 27-1:StrDur magnitude...
Page 22
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 3: Binary controls No events 61850 Path Disabled Description Multiplier Interrogation LLN0.LEDRs1.Oper.ctlVal 20000 LLN0:LEDRs1 control LLN0.LEDRs2.Oper.ctlVal 20001 LLN0:LEDRs2 control RDRE1.RcdTrg.Oper.ctlVal 20007 DFR:RcdTrg control RDRE1.MemClr.Oper.ctlVal 20008 DFR:MemClr control CMSTA1.RecRs.Oper.ctlVal 20009 CMSTA1:RecRs control LPHD1.RsDev.Oper.ctlVal 20013 LPHD1:RsDev control...
Page 23
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPCGGIO2.SPCSO1.Oper.ctlVal 21130 SPCGGIO2:SPCSO1 control SPCGGIO2.SPCSO10.Oper.ctlVal 21131 SPCGGIO2:SPCSO10 control SPCGGIO2.SPCSO11.Oper.ctlVal 21132 SPCGGIO2:SPCSO11 control SPCGGIO2.SPCSO12.Oper.ctlVal 21133 SPCGGIO2:SPCSO12 control SPCGGIO2.SPCSO13.Oper.ctlVal 21134 SPCGGIO2:SPCSO13 control SPCGGIO2.SPCSO14.Oper.ctlVal 21135 SPCGGIO2:SPCSO14 control SPCGGIO2.SPCSO15.Oper.ctlVal 21136 SPCGGIO2:SPCSO15 control...
Page 24
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SRGAPC2.Rs7.Oper.ctlVal 21171 SRGAPC2:Rs7 control SRGAPC2.Rs8.Oper.ctlVal 21172 SRGAPC2:Rs8 control XGGIO100.SPCSO1.Oper.ctlVal 21173 XGGIO100:SPCSO1 control XGGIO100.SPCSO2.Oper.ctlVal 21174 XGGIO100:SPCSO2 control XGGIO100.SPCSO3.Oper.ctlVal 21175 XGGIO100:SPCSO3 control XGGIO100.SPCSO4.Oper.ctlVal 21176 XGGIO100:SPCSO4 control XGGIO100.SPCSO5.Oper.ctlVal 21177 XGGIO100:SPCSO5 control...
Page 25
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 4: Indications No events 61850 Path Disabled Description Multiplier Interrogation LLN0.Loc.stVal LLN0:Loc status RDRE1.RcdMade.stVal DFR:RcdMade status LLN0.SetSeld.stVal LLN0:SetSeld status LLN0.SetChg.stVal LLN0:SetChg status GSEGGIO1.Alm.stVal GSEGGIO1:Alm status LPHD1.PhyHealth1.stVal Self-supervision / Warning LPHD1.PhyHealth2.stVal Self-supervision / Error LEDPTRC1.Str.general LEDPTRC1:general pickup LEDPTRC1.Str.phsA...
Page 26
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation FKEYGGIO1.Ind9.stVal FKEYGGIO1:Ind9 status FKEYGGIO1.Ind10.stVal FKEYGGIO1:Ind10 status FKEYGGIO1.Ind11.stVal FKEYGGIO1:Ind11 status FKEYGGIO1.Ind12.stVal FKEYGGIO1:Ind12 status FKEYGGIO1.Ind13.stVal FKEYGGIO1:Ind13 status FKEYGGIO1.Ind14.stVal FKEYGGIO1:Ind14 status FKEYGGIO1.Ind15.stVal FKEYGGIO1:Ind15 status FKEYGGIO1.Ind16.stVal FKEYGGIO1:Ind16 status DRFLO1.FltLoop.stVal FLO:FltLoop status PTGAPC1.In1.stVal...
Page 27
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TOFGAPC1.In1.stVal TOFGAPC1:In1 status TOFGAPC1.In2.stVal TOFGAPC1:In2 status TOFGAPC1.In3.stVal TOFGAPC1:In3 status TOFGAPC1.In4.stVal TOFGAPC1:In4 status TOFGAPC1.In5.stVal TOFGAPC1:In5 status TOFGAPC1.In6.stVal TOFGAPC1:In6 status TOFGAPC1.In7.stVal TOFGAPC1:In7 status TOFGAPC1.In8.stVal TOFGAPC1:In8 status TOFGAPC1.Q1.stVal TOFGAPC1:Q1 status TOFGAPC1.Q2.stVal...
Page 28
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation ZBAT1.SwConnSt.stVal UPS:SwConnSt status ZBAT1.UpsAlmStat.stVal UPS:UpsAlmStat status ZBAT1.UpsTimeDay.stVal UPS:UpsTimeDay status ZBAT1.UpsTimeHr.stVal UPS:UpsTimeHr status ZBAT1.UpsTimeMin.stVal UPS:UpsTimeMin status ZBAT1.UpsTimeSec.stVal UPS:UpsTimeSec status MVGAPC1.Q1.stVal MVGAPC1:Open MVGAPC1.Q2.stVal MVGAPC1:Closed MVGAPC1.Q3.stVal MVGAPC1:Phase A Open MVGAPC1.Q4.stVal MVGAPC1:Phase A Closed MVGAPC1.Q5.stVal...
Page 29
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SRGAPC2.Q4.stVal SRGAPC2:Q4 status SRGAPC2.Q5.stVal SRGAPC2:Q5 status SRGAPC2.Q6.stVal SRGAPC2:Q6 status SRGAPC2.Q7.stVal SRGAPC2:Q7 status SRGAPC2.Q8.stVal SRGAPC2:Q8 status SRGAPC2.Set1.stVal SRGAPC2:Set1 status SRGAPC2.Set2.stVal SRGAPC2:Set2 status SRGAPC2.Set3.stVal SRGAPC2:Set3 status SRGAPC2.Set4.stVal SRGAPC2:Set4 status SRGAPC2.Set5.stVal...
Page 30
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TONGAPC2.Q6.stVal TONGAPC2:Q6 status TONGAPC2.Q7.stVal TONGAPC2:Q7 status TONGAPC2.Q8.stVal TONGAPC2:Q8 status DLCM1.BrkSt.stVal LCM:BrkSt status DLCM1.LCMClose.general LCM:Close general DLCM1.LCMTrip.general LCM:Trip general DLCM1.RstIn.stVal LCM:RstIn status DLCM1.RstOut.stVal LCM:RstOut status DLCM1.S1Status.stVal LCM:S1Status status DLCM1.S2Status.stVal...
Page 43
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 5: Integrated totals and regulating step positions No events 61850 Path Disabled Description Multiplier Interrogation PEMMTR1.SupWh.actVal 14000 Reverse active energy Wh PEMMTR1.SupVArh.actVal 14001 Reverse reactive energy VArh PEMMTR1.DmdWh.actVal 14002 Forward active energy Wh PEMMTR1.DmdVArh.actVal 14003 Forward reactive energy VArh...
Page 44
Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings RER620 Point List Manual...
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Section 3 IEC 60870-5-101/104 protocol implementation This section describes the specific implementation of the IEC 60870-5-101 protocol within the RER620. The RER620 uses the Triangle MicroWorks, Inc. IEC 60870-5-101 Slave Source Code Library Version 3. This section and the documents listed below provide complete information on how to communicate with a RER620 via the IEC 60870-5-101 protocol.
Page 46
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation The possible selection (blank, X, R, or B) is specified for each specific Clause or parameter. NOTE: In addition, the full specification of a system may require individual selection of certain parameters for certain parts of the system, such as the individual selection of scaling factors for individually addressable measured values.
Page 48
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation A special assignment of ASDUs to class 2 messages is used as follows: Type Identification Cause of Transmission Note: In response to a class 2 poll, a controlled station may respond with class 1 data when there is no class 2 data available.
Page 49
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Selection of standard ASDUs Process information in monitor direction (station-specific parameter, mark each type ID with an “X” if it is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) <1>...
Page 50
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Process information in control direction (station-specific parameter, mark each type ID with an “X” if it is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) <45>...
Page 51
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Type identification and cause of transmission assignments (station-specific parameters) Shaded boxes are not required. Blank = function or ASDU is not used. Mark type identification/cause of transmission combinations: “X” if used only in the standard direction; “R”...
Page 53
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation 8.6 Basic Application Functions Station initialization (station-specific parameter, mark “X” if function is used) Remote initialization Cyclic data transmission (station-specific parameter, mark “X” if function is only used in the standard direction, “R”...
Page 54
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Station interrogation (station-specific parameter, mark “X” if function is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) global group 1 group 7 group 13 group 2...
Page 55
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Transmission of Integrated totals (station-specific parameter, mark “X” if function is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) Mode A: Local freeze with spontaneous Mode B: Local freeze with counter Mode C Freeze and transmit by counter interrogation...
Page 56
Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation File transfer (station-specific parameter, mark “X” if function is used) File transfer in monitor direction Transparent file Transmission of disturbance data of protection Transmission of sequences of events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan...
Section 4 1MAC302441-MB A Glossary Section 4 Glossary Analog input module ANSI American National Standards Institute Autoreclosing Binary input and output Circuit breaker Cycle building block CBFP Circuit-breaker failure protection CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day.