1. Specifications Cassette Type Inverter heat pump Model name AUYG18LVLB AUYG24LVLA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V 5.20 6.80 Rated Btu/h 17,700 23,200 Cooling 0.90 - 5.90 0.90 - 8.00 Min.—Max. Btu/h 3,100 - 20,100...
Page 7
Model name AUYG18LVLB AUYG24LVLA Cooling Energy efficiency class Heating (Average) Cooling 5.2 (35°C) 6.8 (35°C) Pdesign Heating (Average) 5.2 (-10°C) 6.0 (-10°C) SEER Cooling 6.20 5.60 kWh/kWh SCOP Heating (Average) 4.20 3.90 Annual energy consumption kWh/a QHE (Average) 1,732 2,151...
2. Dimensions 2-1. Models: AUYG18LVLB and AUYG24LVLA Unit: mm • Cassette grille mounting state 530: Hanging bolt position op view Be sure to leave Service access service access for future service at the designated position. Min. 450 Drain port Drain port...
2-2. Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) Standard 2,700 High ceiling 3,000 3-way direction setting: Unit: mm 100 or more* NOTES: •...
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: AUYG18LVLB Indoor temperature °CDB °CWB °CDB...
5. Fan performance 5-1. Air velocity distributions ¢ Model: AUYG18LVLB Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: Upward 0.25...
Page 14
¢ Model: AUYG18LVLB Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s...
Page 15
¢ Model: AUYG24LVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Downward 0.25...
Page 16
¢ Model: AUYG24LVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit : m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit : m/s Side view Vertical airflow direction louver: Downward 0.25...
7. Safety devices Model Type of protection Protection form AUYG18LVLB,AUYG24LVLA Circuit protection Current fuse (PCB*) 250 V, 3.15 A 100 ± 10 °C Activate Fan motor stop Fan motor protection Thermal protection program 95 ± 10 °C Reset Fan motor restart...
8. External input and output Connector Input Output Remarks CN102 Control input (Operation/Stop) — See external input/output CN103 — Operation status output settings for details. — Fresh-air control output 8-1. External input • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
Page 23
Circuit diagram example • Contact capacity: DC 24 V or more, 10 mA or Indoor unit more. Connected unit control PCB • *: Make the distance from the PCB to the con- Connector Example: Switch nected unit within 10 m. •...
8-2. External output With using external output function, operating status of this product can be transmitted to the ex- ternal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. ...
8-3. Fresh-air control output Signal linked to the indoor unit fan on can be output. NOTE: In cold-air prevention control operation, the signal becomes off. Circuit diagram example Indoor unit Connected unit control PCB Example: Fan Example: 12 V Connector Relay unit Relay...
9. Remote controller 9-1. Overview a FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET). b START/STOP button Starts and stops operation. c SET button (vertical) Adjusts the vertical airflow direction. d SWING button Sets the automatic swing operation and selects swing mode (Up/down, Left/right, Up/down/left/right, and Stop swing).
10. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 10-1. Function settings on indoor unit By using some components on the PC board, you can change the function settings. Related components on the PC board and the applicable settings Component Setting content...
¢ DIP switch setting • Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch setting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00. Remote DIP switch number controller...
Page 31
1. Press the SET TEMP. ( ) buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to .) If the custom code does not need to be selected, press the MODE button, and proceed to STEP 2.
Page 32
STEP 2: Selecting the function number and setting value 1. Press the SET TEMP. ( ) buttons to select the function Function number number. To switch between the left and right digits, press the MODE button. 2. Press the FAN button to proceed the setting value. To return the function number selection, press the FAN button again.
Page 33
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign Ceiling height...
Page 34
4) Room temperature sensor control for cooling Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. Function number Setting value Setting description Factory setting Standard ♦...
Page 35
9) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode ♦ (Setting prohibited) Forced stop mode 10) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Page 36
¢ Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.
12. Optional parts 12-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal Wired remote screen, wide and large keys easy to UTY-RVNYM controller press, user-intuitive arrow key. Wire type: Polar 3-wire Room temperature can be controlled by detecting the temperature Wired remote UTY-RNNYM...
12-2. Cassette grille Exterior Part name Model name Summary The form of grille discharges wind Cassette grille UTG-UFYD-W away from the ceiling making it difficult to leave dirt marks. 12-3. Others Exterior Part name Model name Summary Use to connect with various External UTY-XWZX peripheral devices and air conditioner...
1. Specifications Type Inverter heat pump Model name AOYG18LBCB AOYG24LBCB Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 2,380 2,850 Airflow rate Heating 2,080 2,700 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level *1 dB (A)
2. Dimensions 2-1. Model: AOYG18LBCB Unit: mm Pitch of bolts for installation Top view Side view Front view Side view 2-2. Model: AOYG24LBCB Unit: mm Pitch of bolts for installation Top view Side view Front view Side view - 39 -...
3. Installation space 3-1. Models: AOYG18LBCB and AOYG24LBCB ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 45
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example “When an obstruction in the upper space:”.
Page 46
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOYG18LBCB NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Model: AOYG24LBCB NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — 0.963 0.961 0.959 — — 0.984 0.981 0.979 0.977 0.975 Indoor unit is higher than outdoor unit *1 —...
9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrat- ed above. - 52 -...
10. Electrical characteristics Model name AOYG18LBCB AOYG24LBCB Voltage 230 ~ Power supply Frequency Max operating current *1 13.5 15.7 Starting current Circuit breaker current Wiring Power cable spec. Cross-sectional area Connection cable *3 Limited wiring length *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Model Type of Protection form protection AOYG18LBCB AOYG24LBCB 250 V, 25 A 250 V, 25 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 250 V, 5 A 250 V, 3.15 A 250 V, 3.15 A 125±10 °C 125±10 °C Activate...