Page 1
AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G09LTCB AS G12LTCB AS G14LTCB OUTDOOR AO G09LTCN AO G12LTCN AO G14LTCN...
FEATURES MODEL ASG09LTCB / AOG09LTCN ASG12LTCB / AOG12LTCN ASG14LTCB / AOG14LTCN AO G09LTCN AO G12LTCN AO G14LTCN FEATURES Energy effi ciency class MODEL AS G09LTCB AS G12LTCB AS G14LTCB Cooling A+++ A+++...
Page 5
Powerful heating at low outdoor temperature Keeping the high heating capacity at low outdoor temperature. NEW model Current model * : ASYA09LEC (09 Class) ASYA12LEC (12 Class) 14%up Heating capacity 13%up (kW) 15%up 09 Class -15°C -7°C 2°C Outdoor temperature 12%up 23%up 38%up...
Page 6
High energy saving High COP is realized by using Large heat exchanger, DC rotary compressor, and inverter technology. 14%up! 7%up! 4.85 4.40 4.27 4.12 3.91 LT series LE series Class Class Class Energy saving control Human sensor catches movements of people in a room, and operates with lower capacity when the room is empty.
WIRELESS REMOTE CONTROLLER FEATURES 3 mode timer setup available (Weekly / Program / Sleep). Easy operation. Easy to change signal code (max. 4 units) by button operation. Simple function setting Setting of the air conditioner selection function is performed by remote controller. Built-in timers ...
Page 8
FUNCTIONS SENSOR button Signal Transmitter MODE button FAN button 10 °C HEAT button ECONOMY button SWING button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button START/STOP ON/OFF button button SEND button SLEEP button SELECT button RESET button...
FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Fan speed : High MODEL : ASG09LTCB Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right &...
Page 17
Note: Fan speed : High MODEL : ASG12LTCB Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right & Left Unit : m/s SIDE VIEW Vertical flap : Up...
Page 18
Note: Fan speed : High MODEL : ASG14LTCB Operation mode : FAN Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Center Unit : m/s TOP VIEW Vertical flap : Up Horizontal flap : Right & Left Unit : m/s SIDE VIEW Vertical flap : Up...
7-2. AIRFLOW MODEL : ASG09LTCB Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH 1300 1080 QUIET Heating Number of Fan speed rotations Airflow (r.p.m.) HIGH 1300 1120 QUIET - (01 - 16) -...
Page 20
MODEL : ASG12LTCB Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH 1370 1120 QUIET Heating Number of Fan speed rotations Airflow (r.p.m.) HIGH 1370 1180 QUIET - (01 - 17) -...
Page 21
MODEL : ASG14LTCB Cooling Number of Fan speed rotations Airflow (r.p.m.) HIGH 1370 1220 QUIET Heating Number of Fan speed rotations Airflow (r.p.m.) HIGH 1510 1220 1030 QUIET - (01 - 18) -...
ELECTRIC CHARACTERISTICS Model name ASG09LTCB ASG12LTCB ASG14LTCB Voltage 230~ Power supply Frequency Max. operating current Connection cable *1)Wiring Spec. Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) - (01 - 22) -...
SAFETY DEVICES Model Protection form ASG09LTCB ASG12LTCB ASG14LTCB Circuit protection Current fuse (PCB) 250V 3.15A Terminal protection Current (thermal) fuse 250V 3A OFF: 160±25°C Fan motor protection Thermal protector program ON: 110±25°C - (01 - 23) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CNA01 Control input See external CNB01 Operation status output input/output settings for details. CNB02 Error status output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
Page 28
When function setting is in "Forced stop" mode Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Parts (Optional) Parts name Model name External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF * For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply...
Page 30
ERROR STATUS OUTPUT An air conditioner error status signal can be output. Circuit diagram example Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *10 m Signal Optional parts Field supply * Make the distance from the PC board to the connected unit within 10m.
FUNCTION SETTINGS 12-1. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. •...
Page 32
FUNCTION DETAILS Compact wall Functions mounted 1) Filter sign 2) Cooler room temperature correction 3) Heater room temperature correction 4) Auto restart 5) Indoor room temperature sensor switching function 6) Remote controller signal code 7) External input control 8) Indoor unit fan control for energy saving 1) Filter sign The indoor unit has a sign to inform the user that it is time to clean the filter.
Page 33
4) Auto restart Enable or disable automatic system restart after a power outage. ( ... Factory setting) Setting description Function number Setting value * Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate using the remote controller, or external input device.
Page 34
REMOTE CONTROLLER SIGNAL CODE SETTING Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) (1) Press the START/STOP ( / ) button until only the clock is displayed on the remote controller display.
OPTIONAL PARTS 13-1. CONTROLLER Exterior Parts name Model No. Summary Large and full-dot liquid crystal screen, wide and large keys Wired remote easy to press, user-intuitive UTY-RVN M controller arrow key. *Optional communication kit is necessary for installation. The room temperature can be controlled by detecting the Wired remote temperature accurately with...
Page 36
2. OUTDOOR UNIT SINGLE TYPE : AOG09LTCN AOG12LTCN AOG14LTCN DTR_AO092E_02 2013.01.10...
SPECIFICATIONS Type INVERTER HEAT PUMP Model name AOG09LTCN AOG12LTCN AOG14LTCN Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current Cooling 1,700 2,050 Airflow rate Heating 1,700 2,000 Type×Q'ty Propeller fan×1 Motor output Cooling Sound pressure level dB(A) Heating Cooling...
DIMENSIONS MODEL : AOG09LTCN (Unit : mm) Top view Front view Side view Air flow 17.5 hole (10) (10) (10) hole (6x20=120) (6x20=120) ø20 hole 4-ø11.3mm hole Bottom view INSTALLATION PLACE CAUTION In areas with heavy snowfall, if the intake and outlet of the outdoor unit is blocked with snow, it may be dif- ficult to warm up and likely to cause breakdown.
Page 40
MODEL : AOG12LTCN, AOG14LTCN (Unit : mm) Top view Side view Front view Air flow 17.5 hole (10) (10) (10) hole (6x20=120) (6x20=120) ø20 hole 4-ø11.3mm hole Bottom view INSTALLATION PLACE CAUTION In areas with heavy snowfall, if the intake and outlet of the outdoor unit is blocked with snow, it may be diffi- cult to warm up and likely to cause breakdown.
ELECTRIC CHARACTERISTICS Model name AOG09LTCN AOG12LTCN AOG14LTCN Voltage 230 ~ Power supply Frequency *1) Max operating current 10.0 11.5 14.5 Starting Current Main Fuse (Circuit breaker) Current *2) Wiring Spec.: Power Cable 3.5-4.0 *3) Limited wiring length : *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring Spec.: Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
SAFETY DEVICES Model Protection form AOG09LTCN AOG12LTCN AOG14LTCN Current fuse 250V 20A ─ (Near the terminal) 250V 5A Circuit protection 250V 15A 250V 5A Current fuse (Main printed circuit board) 250V 3.15A 250V 3.15A Thermal protection OFF : 150±15°C OFF : 100±15°C Fan motor protection program ON : 120±15°C...