SINGLE ZONE MEGA AND MEGA 115V WALL MOUNTED INSTALLATION MANUAL Single Zone Mega: LS090HEV2, LS120HEV2, LS180HEV2, LS240HEV2 Single Zone Mega 115V: LS090HXV, LS120HXV...
Refer to the figure at right for maximum length and elevation of piping. Indoor unit Outdoor unit Table 9: Single Zone Mega and Mega 115V Refrigerant Piping System Limitations. Model Numbers LS090HEV2, LS120HEV2 LS180HEV2, LS240HEV2 LS090HXV, LSU120HXV Vapor 3/8 inches 1/2 inches 3/8 inches Pipe Sizes...
Always follow local codes when selecting and installing copper pipe and piping system components. Approved piping for use with LG Single Zone products will be marked “R410 RATED” along the length of the pipe. Piping wall thickness must meet local code requirements and be approved for a maximum operating pressure of 551 psi. When bending piping, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed piping;...
COPPER EXPANSION AND CONTRACTION Copper Expansion and Contraction Under normal operating conditions, the vapor pipe temperature of 1. From Table 11 find the row corresponding with the actual length of a Duct Free System can vary as much as 280°F. With this large the straight pipe segment.
PIPING HANDLING Piping Materials and Handling Keep Pipes Capped While Storing. Pipes used for the refrigerant piping system must include the specified thickness, and the interior must be clean. While handling and storing, do not bend or damage the pipes, and take care not to contaminate the interior with dust, moisture, etc.
Failure to do so will cause significant performance degradation. Proper leak checks must be performed. Using isolation valves does not automatically void any LG product warranty, however, a limited warranty will be voided in whole or part if any field supplied accessory fail in any way that causes product failure.
Page 31
REFRIGERANT SYSTEM ENGINEERING Obstacles Figure 32: Installing Piping Above and Below an Obstacle. When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant pipe run, it is best practice to route the MINIMUM pipe over the obstacle.
Page 32
Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve.
FLARING AND BRAZING PROCEDURES Flaring and Brazing Procedures One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform both flared and brazed connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Refer to the table below and on the next two pages for error codes that are generated from the indoor and outdoor units. These codes are the most common. Your particular system might generate additional codes not listed here. Please contact LG Support if you see these types of errors and a simple power cycle has not corrected the issue.
Communication type RS-485–BUS type. LG-supplied cable was used; or 22-3 AWG, twisted, stranded, unshielded cable (minimum) was used between the indoor unit (Mega 115V) and its zone controller (if present for Mega 115V). No cables were spliced, and no wire caps are present.