When installing a HS-NCM (High-Speed Network Communications Module) on high-speed networks and workstations, adhere to the following to
avoid permanent damage:
•
Do not attempt to upgrade HS-NCM to software v30.x (or higher) on a network that utilizes v20 HS-NCMs using v20.4 (or lower) software. This
will result in permanent damage to all v20 HS-NCMs on the network
•
Attempting to individually upgrade any v20 HS-NCM with software V30.x (or higher) will result in permanent damage
•
When using v30 HS-NCM, VeriFire Tools v8.20 (or higher) is required for all HS-NCM software upgrades
•
When using an Ethernet cable (RJ45) to bridge a VDSL network with a BoradR-Reach network use VeriFire Tools version 10.80 (or higher)
•
When a HS-NCM-W-2, HS-NCM-WMF-2 or HS-NCM-WSF-2 is used in a network use VeriFire Tools version 10.80 (or higher)
1
Product Overview
NOTE:
References to V20 HS-NCM indicate hardware assembly HS-NCM-PCA.
References to V30.x and V31.x (or higher) HS-NCM indicate hardware assembly HS-NCM-PCB.
References to V31.x (or higher) indicate hardware assembly HS-NCM-W-2, HS-NCM-WMF-2, HS-NCM-WSF-2 (HS-NCM-PCC)
The High-Speed Network Communications Module (HS-NCM) provides a means for connecting specific Notifier fire alarm control products to High-
Speed NOTI•FIRE•NET™. There are six types of HS-NCMs available: HS-NCM-W/W-2 for connecting nodes with twisted-pair wire; HS-NCM-MF
and HS-NCM-SF are used for connecting nodes with fiber-optic cable; HS-NCM-WMF/WMF-2 and HS-NCM-WSF/WSF-2 are used for connecting
nodes with fiber-optic cables to nodes with twisted-pair wire; HS-NCM-MFSF for connecting nodes with multi-mode fiber cable to nodes with single-
mode fiber cable. The following equipment may be used with the HS-NCM:
* Power for the HS-NCM for use with 10th Edition panels is provided via the NUP connection on the FACP itself or an external UL/ULC listed power
supply.
† Power for the HS-NCM for use with UL 8th Edition panels must be provided by a 24 VDC UL/ULC listed power supply.
*
The following revisions
of the UL 10th edition panels require a 24 VDC UL/ULC listed power source to power the HS-NCM and cannot be pow-
ered via the panel's NUP port
* The revision and assembly name can be found on the fire panel's circuit board.
† NUP Port connections are still required for communication between the HS-NCM and the fire panel. TX, RX, and GND connections must be used for
NUP connections.
‡ If TB1 is utilized to power the HS-NCM, a UL Listed, Regulated, Power Limited 24VDC power source is required
WARNING
Adhere to the following To Avoid Permanent Damage:
UL 10th Edition
• NFS2-3030
• NFS2-640
• NFS-320
• NCA-2
• DVC-EM
• ONYXWorks
• NCD
• N16E/N16X
†
:
• NFS-320
• NFS2-640
• NFS2-3030
• N16E/N16X
• DVC-EM
• DVC
• NCA-2
High-Speed Network Communications Module
Product Installation Document
PN 54014:C1 12/15/2020 ECN: 151329
*
UL 8th Edition
• NFS-3030
• NFS-640
• NCA
CPU2-640PCB Revision E or older
CPU2-640PCB Revision E or older
CPU2-3030PCC Revision I or older
‡
Core/PMB PCB
DVC-EMPCB Revision F or older
DVC-PCA All Revisions
NCA-2PCC Revision I or older
†