FEATURES MODELS AUG45LRLA / AOG45LETL AUG54LRLA / AOG54LETL FEATURES Energy saving • All DC design • Heat exchange efficiency increased and larger air flow by adoption of new type turbo fan Advancement in comfort •...
Page 5
Economy operation The power consumption can be reduced. Improvement of installation & maintenance • Adjustment of hanger position is possible after installation Mounting position of body can be fine adjusted after mounting the cassette grille. Detachable grille corner Adjustment can be done by just taking off the corner part High lift drain pump...
WIRED REMOTE CONTROLLER FEATURES Various timer setup available (ON / OFF / WEEKLY). Equipped with weekly timer as standard function. (Start/Stop function is twice per day for a week) When setting up the timer, operation mode and temperature ...
Page 7
FUNCTIONS START/STOP button Pressed to start and stop operation. SET TEMP button Selects the setting temperature. MODE button Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). FAN button Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). ECONOMY button Turns the economy efficient mode on and off.
SPECIFICATIONS CASSETTE MODEL Type INVERTER HEATPUMP Model name G45LRLA G54LRLA Power source 230 V ~ 50 Hz Available voltage range 198 - 264 V 12.5 13.3 Rated Btu/h 42700 45400 Cooling 4.0-14.0 4.5-14.5 Min.-Max. Btu/h 13700-47800 15400-49500 Capacity 14.0 16.0 Rated...
DIMENSIONS MODELS : AU G45LRLA, AUG54LRLA Ceiling opening and hanging bolt pitch (Unit : mm) 950 (Panel frame) 860 - 910 (Ceiling opening) 840 (Body frame) 795 (Hanging bolt pitch) Refrigerant piping and drain piping positions Drain pipe (Connect the attached drain hose) Airflow split-flow duct and fresh air inlet positions...
Page 10
INSTALLATION PLACE (Unit : mm) Strong and durable ceiling 298 or more 1,500 3,000 or more or more Ceiling mode “Low” : 2.7 m Ceiling mode “Standard” : 3.2 m Obstruction Ceiling mode “High” : 4.2 m Floor 3-way directions setting ...
FAN PERFORMANCE 7-1. AIR VELOCITY DISTRIBUTION Note: Condition 7-1-1. STANDARD MODE Fan speed : High Operation mode : FAN MODEL : AUG45LRLA Ceiling mode : Standard 4-way air outlet Unit : m/s 0.25 Top view 0.25 Vertical airflow direction louver: Up Unit : m/s Side view...
Page 15
Note: Condition Fan speed : High Operation mode : FAN Ceiling mode : Standard 3-way air outlet Unit : m/s 0.25 0.25 0.25 Top view Vertical airflow direction louver: Up Unit : m/s Side view 0.25 0.25 Vertical airflow direction louver: Up Unit : m/s Side view...
Page 16
Note: Condition Fan speed : High Operation mode : FAN MODEL : AUG54LRLA Ceiling mode : Standard 4-way air outlet Unit : m/s Top view Vertical airflow direction louver: Up Unit : m/s Side view Vertical airflow direction louver: Up Unit : m/s Side view...
Page 17
Note: Condition Fan speed : High Operation mode : FAN Ceiling mode : Standard 3-way air outlet Unit : m/s Top view Vertical airflow direction louver: Up Unit : m/s Side view Vertical airflow direction louver: Up Unit : m/s Side view Vertical airflow direction louver: Down...
Note: Condition 7-1-2. SPECIAL UPWARD MODE Fan speed : High Operation mode : FAN MODEL : AUG45LRLA Ceiling mode : Standard 4-way air outlet Unit : m/s Side view Vertical airflow direction 0.25 louver: Special upward MODEL : AUG54LRLA ...
7-2. AIRFLOW 7-2-1. 4-WAY OUTLET MODEL : AUG45LRLA Cooling / Heating Number of Fan speed rotations Airflow (r.p.m.) 1900 HIGH 1118 1640 1460 1250 QUIET MODEL : AUG54LRLA Cooling / Heating Number of Fan speed rotations Airflow (r.p.m.)
7-2-2. 3-WAY OUTLET MODEL : AUG45LRLA Cooling / Heating Number of Fan speed rotations Airflow (r.p.m.) 1690 HIGH 1490 1340 1140 QUIET MODEL : AUG54LRLA Cooling / Heating Number of Fan speed rotations Airflow (r.p.m.) 1740 HIGH...
7-3. FRESH AIR MODELS : AU G45LRLA, AUG54LRLA Airflow volume - Static pressure of Fresh air intake characteristic Duct (Inside Dia. ø70mm) Duct Fan Static pressure required to take in fresh air Airflow (m Installation 70 mm 2.5 mm screw 62 mm 250 mm...
7-4. DUCT CONNECTION MODELS : AU G45LRLA, AUG54LRLA Outlet air AUG45LRLA Duct (Inside size. 350mm×100mm) Fan Speed High 1-way Fan Speed High 2-way Fan Speed Quiet 1-way L=10m Fan Speed L=5m Quiet 2-way L=1m Airflow (m /min) AUG54LRLA Fan Speed High 1-way...
Page 23
PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT zConnect the air outlet duct to maximum two locations among the four duct connection locations. (Do not connect ducts to three or more locations.) zBlow-off pattern when a branch duct is installed ...
ELECTRIC CHARACTERISTICS AUG45LRLA Model name AUG54LRLA Voltage 230 ~ Power supply Frequency Max. operating current (Indoor unit) Connection cable 1.5 (Min.) *1) Wiring spec. (Indoor unit to outdoor unit) *2) Limited wiring length *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0005) *2) Limited wiring length : Limit voltage drop to less than 2%.
SAFETY DEVICES Model Protection form AUG45LRLA AUG54LRLA Circuit protection Current fuse (PCB) 250V 3.15A °C OFF Thermal protection Fan motor protection program °C ON - (01 - 24) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CN102 Control input — See external CN103 — Operation status output input/output settings for details. — Fresh air control output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor unit Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
Page 30
FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor unit Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V...
FUNCTION SETTINGS 12-1. INDOOR UNIT INDOOR UNIT DIP SW Remote controller address setting Jumper Wire Setting prohibited SWITCH POSITION MAIN PCB Indoor unit Printed circuit board DIP-SW SETTING Remote controller address setting A number of indoor units can be operated at the same time using a wired remote controller. Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board.
12-2. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. • After the power is turned on, perform the Function Setting according to the installation conditions using the remote controller.
Page 33
(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops flashing. If the setting value display changes or if “- -” is displayed when the flashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.) (6) Repeat steps 2 to 5 to perform additional settings.
Page 34
CONTENTS OF FUNCTION SETTING • Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control. •...
Page 35
3) Outlet directions Select the appropriate number of outlet directions according to the installation conditions. ( . . .Factory setting) Setting Description Function Number Setting Value 4-way 3-way 4) Vertical airflow direction range control To prevent draft, change the setting to "Upward" (01). Note that the airflow in certain usage conditions may leave the ceiling dirty.
Page 36
8) Room temperature sensor switching (Only for wired remote controller) When using the Wired remote controller temperature sensor, change the setting to "Both" (01). ( . . .Factory setting) Setting Description Function Number Setting Value Indoor unit Both 00: Sensor on the indoor unit is active.
OPTIONAL PARTS 13-1. CONTROLLER Exterior Parts name Model No. Summary Large and full-dot liquid Wired remote crystal screen, wide and UTY-RVN M large keys easy to press, controller user-intuitive arrow key. The room temperature can Wired remote be controlled by detecting UTY-RNN ...
13-3. OTHERS Exterior Parts name Model No. Summary Air outlet shutter plate is Air outlet installed at the air outlet UTR-YDZC shutter plate when 3-way direction is performed. Wide panel hides the gap Wide panel UTG-AGYA-W between the ceiling hole and the Cassette grille.
Page 40
2. OUTDOOR UNIT SINGLE TYPE : AOG45LETL AOG54LETL DTR_AO136E_03 2014.05.16...
Page 41
CONTENTS 2. OUTDOOR UNIT FEATURE ······························································································ 02 - 01 2. SPECIFICATIONS ·············································································· 02 - 03 DIMENSIONS ······················································································· 02 - 04 4. INSTALLATION PLACE ··································································· 02 - 05 4-1. SINGLE OUTDOOR UNIT INSTALLATION ········································· 02 - 05 4-2. MULTIPLE OUTDOOR UNIT INSTALLATION ·····································...
FEATURE FEATURES Peak cut operation Peak cut mode Suppresses maximum capacity to perform energy-saving operation, preventing breaker tripping. This function operates by setting a peak current value and reducing the power consumption. * Performance drops by reducing the power consumption preferentially. Level 1 ...
Page 43
Space saving Compact size High performance has been realized with a compact outdoor unit. Due to the compact size, the space required for installation has been reduced, allowing a wider selection of installation locations. 4-direction piping connection Rear Piping is connectable in any of the four directions.
SPECIFICATIONS Model name AOG45LETL AOG54LETL Power source 1Ø 230 V~ 50 Hz Available voltage range 198 - 264 V Starting current 18.9 20.9 Cooling 6,750 6,750 Airflow rate Heating 6,200 6,850 Type × Q'ty Propeller × 2 Motor output Cooling Sound pressure level dB(A) Heating...
INSTALLATION PLACE 4-1. SINGLE OUTDOOR UNIT INSTALLATION WHEN THE UPWARD AREA IS OPEN (Unit : mm) Obstacles at front and Obstacles at rear Obstacles at rear and Obstacles at front only sides only only rear only 1000 or more 1000 or more WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA ...
4-2. MULTIPLE OUTDOOR UNIT INSTALLATION WHEN THE UPWARD AREA IS OPEN (Unit : mm) Obstacles at rear only Obstacles at front only Obstacles at front and rear only 1500 or more 1500 or more WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA ...
AIR FLOW MODELS: AO G45LETL, AOG54LETL Cooling Number of MODEL rotations Air flow (r.p.m.) 6750 Upper fan AO G45LETL 1875 Lower fan 3974 6750 Upper fan AO G54LETL 1875 Lower fan 3974 Heating Number of MODEL rotations Air flow...
ELECTRIC CHARACTERISTICS Model name AO G45LETL AO G54LETL Voltage 230 ~ Power supply Frequency *1) Max. operating current 22.5 23.5 Circuit breaker current *2) Wiring spec. Power cable *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring spec.
SAFETY DEVICES Model Protection form AO G45LETL AO G54LETL Current fuse 250V 30A, 250V 10A x2, 250V 3.15A (Filter printed circuit board) Circuit protection Current fuse 250V 3.15A (Main printed circuit board) OFF : 150±15°C Fan motor protector Thermal protector ON : 120±15°C Thermal protection program...
EXTERNAL INPUT & OUTPUT Input Output Connector Remarks Low noise mode ― CN10 Peak cut mode ― CN11 See external input/output settings ― Error status CN12 for details. ― Compressor status CN13 13-1. EXTERNAL INPUT ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specified by external signal.
Page 59
PEAK CUT MODE • Operation that suppressed the current value can be performed by means of the following on- site work. The air conditioner is set to the Peak cut mode when closing the contact input of a commercial ON/OFF switch to a connector on the outdoor control PC board.
13-2. EXTERNAL OUTPUT ERROR STATUS OUTPUT • An air conditioner error status signal is produced when a malfunction occurs. Circuit diagram example Outdoor unit Connected unit control PC board Connector Power supply 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load Load ●...
Page 61
COMPRESSOR STATUS OUTPUT • Compressor operation status signal is produced when the compressor is running. Circuit diagram example Outdoor unit Connected unit control PC board Connector Power supply 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load Load ●...
FUNCTION SETTINGS Caution Discharge the static electricity from your body before setting up the push buttons. Never touch the terminals or the patterns on the parts that are mounted on the board. 14-1. FIELD SETTING SWITCHES The positions of the switches on the outdoor unit control board are shown in the figure below. LED lamps Push buttons...
14-2. SETTING METHOD Stop the operation of air conditioner before this setting. 14-2-1. LOW NOISE MODE LED lamp part (1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more. (2) Confirm that the (POWER / MODE) blinks 9 times, then press [ENTER] button (SW3). PUMP POWER LOW NOISE...
14-2-2. PEAK CUT MODE LED lamp part (1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more. (2) Confirm that the (POWER / MODE) blinks 9 times, then press [ENTER] button (SW3). PUMP POWER LOW NOISE PEAK CUT DOWN...
OPTIONAL PARTS Exterior Parts name Model No. Summary Use to operate the External input External connect UTY-XWZXZ3 and output function of Outdoor unit. - (02 - 24) -...