01
Installation Preparations
1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only qualified professionals or trained personnel are allowed to install, commission, and maintain the UPS.
Otherwise, personal injury or equipment damage may occur, and the caused UPS damage is not covered under any
warranty or service agreement.
4. This document describes the operation procedure for a single UPS. For details about how to operate a parallel
system, see the user manual.
Model
Weight
UPS5000-H-400K-FT
< 750 kg
UPS5000-H-500K-FT
< 805 kg
UPS5000-H-600K-FT
< 860 kg
Recommended Power Cables
Item
400 kVA
Mains input current (A)
743
Mains input
Recommended cross-
L1/L2/L3/N
2 x (4 x 240) 3 x (4 x 185) 4 x (4 x 185)
sectional area (mm
2
)
PE
240
Bypass input current (A)
608
Bypass input
Recommended cross-
L1/L2/L3/N
2 x (4 x 240) 3 x (4 x 185) 4 x (4 x 185)
sectional area (mm
2
)
PE
240
Output current (A)
608
Output
Recommended cross-
U/V/W/N
2 x (4 x 240) 3 x (4 x 185) 4 x (4 x 185)
sectional area (mm
2
)
PE
240
Nominal battery discharge current (A) 877
Battery input
Maximum battery discharge current (A) 1062
(lead-acid
Recommended cross-
+/-
2 x (2 x 240) 3 x (2 x 185) 3 x (2 x 240)
battery)
sectional area (mm
2
)
PE
240
Nominal battery discharge current (A) 831
Battery input
Maximum battery discharge current (A) 1043
(SmartLi)
Recommended cross-sectional area
For details, see the IEC-60364-5-52
(mm
)
specifications and SmartLi User Manual.
2
Equipotential
Recommended cross-sectional area
16
ground point
(mm
2
)
Cabinet Description
UPS5000-H-400K
Bypass input switch
Mains input switch
Monitor display unit
Surge protection
boxes (optional)
Switch handle
Control module
Intelligent
detection card
Bypass module
Power modules
UPS5000-H-(400 kVA-600 kVA)-FT Quick Guide (100 kVA Power Modules)
Dimensions (H x W x D)
2000 mm x 800 mm x 1000 mm
500 kVA
600 kVA
Remarks
929
1115
760
912
Connection method:
Crimped DT terminal
Bolt Specifications:
L1/L2/L3/U/V/W/+/-:
760
912
M16 x 55 mm (120 N· m)
PE: M12 x 30 mm (47 N· m)
Equipotential ground point:
1108
1330
M6 x 20 mm (4.5 N· m)
1327
1593
NOTE:
The currents listed in the
1039
1247
table are measured at a
1304
1564
rated voltage of 380 V.
UPS5000-H-600K
Bypass input switch
Mains input switch
Maintenance
bypass switch
Monitor display unit
Output switch
Five power modules are
configured for the 500
kVA model, and six power
modules for the 600 kVA
model. The figure uses
the 600 kVA model as an
example.
Space Planning
Surge protection
boxes (optional)
Switch handle
Control module
Intelligent
detection card
Bypass module
Power modules
1
Issue: 04
Date: 2022-12-29
02
Installing Cabinets
Unpacking
Securing the Cabinet
unit: mm
A: mounting holes
on the channel steel
B: mounting holes
on the floor
Maintenance
bypass switch
Output switch
Copyright © Huawei Digital Power Technologies Co., Ltd. 2022. All rights reserved.