Custom Code Setting; Function Setting - Fujitsu Airstage ASUA4TLAV2 Installation Manual

Indoor unit (wall mounted type)
Hide thumbs Also See for Airstage ASUA4TLAV2:
Table of Contents

Advertisement

Table A
Address
Rotary Switch Setting
REF AD SW
Refrigerant circuit
× 10
× 1
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do no t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure .

6.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch
"SET3"
DIP switch

6.3. Function setting

Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "6.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
Code change
A
B
C
A
B
C
DIP switch "SET3"
ON
OFF
SW
SW
SW
SW
1
2
3
4
Custom code
A (Factory
SET3
B
C
setting)
SW1
OFF
ON
OFF
SW2
OFF
OFF
ON
WARNING
Function details
Function
Function
number
× 1
0
Filter indica-
1
11
tor interval
2
3
4
5
6
Filter indica-
7
13
tor action
8
9
0
1
(Forbidden)
20
2
.
.
(Forbidden)
23
.
(Forbidden)
24
3
(Forbidden)
26
Cool air
temperature
30
trigger
D
Heat air
temperature
31
trigger
D
Auto restart
40
(*1)
Cool Air
43
Prevention
External
D
46
control
ON
ON
Error report
47
target
Fan set-
ting when
cooling
49
thermostat
OFF
Switching
functions
for external
inputs and
60
external
outputs
terminals
(*2)
Setting number
Default
Adjust the filter cleaning interval
00 Standard
notification. If the notification
01 Longer
is too early, change to setting
01. If the notification is too late,
02 Shorter
change to setting 02.
00 Enable
01 Disable
Enable or disable the filter indi-
cator. Setting 02 is for use with a
Display only
on central
central remote controller.
02
remote
controller
00
00
00
31
Adjust the cool air trigger
00 Standard
temperature. To lower the trigger
01 Adjust (1)
temperature, use setting 01. To
raise the trigger temperature,
02 Adjust (2)
use setting 02.
Adjust the heat air trigger
00 Standard
temperature. To lower the trigger
01 Adjust (1)
temperature by 6 degrees C,
use setting 01. To lower the trig-
02 Adjust (2)
ger temperature by 4 degrees C,
use setting 02. To raise the trig-
03 Adjust (3)
ger temperature, use setting 03.
00 Enable
Enable or disable automatic
system restart after a power
01 Disable
outage.
00 Super low
Restrain the cold airflow with
making the airflow lower when
Follow the
starting heating operation. To
setting on
01
correspond to the ventilation,
the remote
set to 01.
controller
Allow an external controller to
00 Start/Stop
start or stop the system, or to
Emergency
perform an emergency stop.
01
stop
If an emergency stop is performed
from an external controller,
all refrigerant systems will be
disabled.
If forced stop is set, indoor unit
02 Forced Stop
stops by the input to the external
input terminals, and Start/
Stop by a remote controller is
restricted.
00 All
Change the target for reporting
Display only
errors. Errors can either be re-
on central
ported in all locations, or only on
01
remote
the central remote controller.
controller
Follow the
When set to 01, the fan stops
setting on
when the thermostat is OFF in
00
the remote
cooling operation. Connection
controller
of the wired remote controller
(2-wire type or 3-wire type)
and switching its thermistor are
01 Stop
necessary.
00 Mode 0
• Set this function when con-
01 Mode 1
necting the VRF system to a
ventilator, economizer, humidi-
02 Mode 2
fier, or other external device.
03 Mode 3
• The connection terminal
functions can be changed
04 Mode 4
depending on the type of ex-
05 Mode 5
ternal device. For details of the
06 Mode 6
connection terminal functions,
see the Design & Technical
07 Mode 7
Manual.
08 Mode 8
Details
En-10