1. Specifications Duct Type Inverter, Heat pump Model name ARU18RGLX ARU24RGLX ARU30RGLX Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V 5.28 7.03 8.79 Rated Btu/h 18,000 24,000 30,000 Cooling 1.58—6.30 1.58—8.50 2.81—10.26 Min.—Max.
Page 7
Duct Type Inverter, Heat pump Model name ARU18RGLX ARU24RGLX ARU30RGLX NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB/67°FWB (26.67°CDB/19.44°CWB), and outdoor temperature of 95°FDB/75°FWB (35°CDB/23.9°CWB). – Heating: Indoor temperature of 70°FDB/60°FWB (21.11°CDB/15.56°CWB), and outdoor temperature of 47°FDB/43°FWB (8.33°CDB/6.11°CWB).
Page 8
Duct Type Inverter, Heat pump Model name ARU36RGLX Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V 10.55 Rated Btu/h 36,000 Cooling 2.81—11.43 Min.—Max. Btu/h 9,600—39,000 10.55 Rated 47°FDB Btu/h 36,000 (Outdoor temp.) 2.70—14.07 Capacity Min.—Max.
Page 9
Duct Type Inverter, Heat pump Model name ARU36RGLX NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB/67°FWB (26.67°CDB/19.44°CWB), and outdoor temperature of 95°FDB/75°FWB (35°CDB/23.9°CWB). – Heating: Indoor temperature of 70°FDB/60°FWB (21.11°CDB/15.56°CWB), and outdoor temperature of 47°FDB/43°FWB (8.33°CDB/6.11°CWB). –...
2-3. Installation space requirement Provide sufficient installation space for product safety. NOTE: The detailed component shape depends on the model. ¢ Models: ARU18RGLX, ARU24RGLX, ARU30RGLX, and ARU36RGLX Unit: in (mm) 1 (20) or more 6 (150) 12 (300) or more...
NOTES: • Do not place any wiring or illumination in the maintenance space, as they will impede service. • The detailed component shape depends on the model. ¢ Models: ARU18RGLX, ARU24RGLX, ARU30RGLX, and ARU36RGLX Unit: in (mm) • Provide a maintenance access for maintenance purposes.
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ARU18RGLX Indoor temperature °FDB °FWB °FDB...
5. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 5-1. Fan performance curve ¢ Model: ARU18RGLX (inWG) (Pa) Fan performance curve_1 1.20 1.12 1.04 0.96 0.88 Hi (SP mode20) 0.80...
Page 24
NOTES: • Setting of the external static pressure is switchable into modes by using the remote controller. • According to the resistance of the connecting duct, perform the setting of the external static pressure with referring “Fan performance curve_2” above. •...
Page 25
Characteristics of air volume and capacity • Cooling (CFM) 1,177 1,000 1,500 2,000 Airflow • Heating (CFM) 1,177 1,000 1,500 2,000 Airflow - 21 - 5-1. Fan performance curve 5. Fan performance...
Page 26
¢ Model: ARU24RGLX (inWG) (Pa) Fan performance curve_1 1.20 1.12 1.04 0.96 0.88 Hi (SP mode20) 0.80 0.72 0.64 SP mode20 upper limit 0.56 0.48 0.40 0.32 0.24 Normal SP upper limit Hi (Normal SP) Qu (SP mode20) 0.16 Normal SP 0.80 lower limit Qu (Normal SP)
Page 27
Characteristics of air volume and capacity • Cooling (CFM) 1,177 1,000 1,500 2,000 Airflow • Heating (CFM) 1,177 1,472 1,000 1,500 2,000 2,500 Airflow - 23 - 5-1. Fan performance curve 5. Fan performance...
Page 28
¢ Model: ARU30RGLX (inWG) (Pa) Fan performance curve_1 1.20 1.12 1.04 0.96 0.88 Hi (SP mode20) 0.80 0.72 0.64 SP mode20 upper limit 0.56 0.48 SP mode20 0.40 lower limit 0.32 Qu(SP mode20) 0.24 Hi (Normal SP) Normal SP upper limit 0.16 0.80 Normal SP...
Page 29
Characteristics of air volume and capacity • Cooling (CFM) 1,177 1,472 1,000 1,500 2,000 2,500 Airflow • Heating (CFM) 1,177 1,472 1,000 1,500 2,000 2,500 Airflow - 25 - 5-1. Fan performance curve 5. Fan performance...
Page 30
¢ Model: ARU36RGLX Fan performance curve_1 (inWG) (Pa) 1.20 1.12 1.04 0.96 0.88 Hi (SP mode20) 0.80 0.72 SP mode20 0.64 upper limit 0.56 0.48 SP mode20 0.40 lower limit 0.32 Normal SP Hi (Normal SP) upper limit 0.24 Qu(SP mode20) 0.16 Normal SP 0.80...
Page 31
Characteristics of air volume and capacity • Cooling (CFM) 1,177 1,472 1,766 1,000 1,500 2,000 2,500 3,000 Airflow • Heating (CFM) 1,177 1,472 1,766 1,000 1,500 2,000 2,500 3,000 Airflow ¢ Automatic airflow adjustment procedures 1. To start the auto setting, use setting value 32 in function number 26. 2.
6-2. Sound level check point 79 in (2 m) 40 in (1 m) Product Measuring duct Measuring duct (Set the static pressure as rating in this area) Microphone Microphone Front view Side view - 34 - 6-2. Sound level check point 6.
7. Safety devices Model Type of protection Protection form ARU18RGLX ARU24RGLX Circuit protection Current fuse (PCB*) 250 V, 5 A 239 ±59°F (115 ±15°C) Activate Fan motor stop Thermal protection program Fan motor protection 158°F (70°C) Reset Fan motor restart Current protection Activate 2.13 A...
Page 41
¢ External input and output PCB The indoor unit Operation/Stop can be set by using the input terminal on the PCB. Input select Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.) •...
8-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m). •...
8-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
Page 44
External output External input Function and output Indoor unit Mode External input and output PCB setting PCB (Rotary Output CN47 Output 1 Output 2 Output 3 Indoor unit fan 60-00 Operation/Stop Operation/Stop Error status operation status Indoor unit fan External heater 60-00 Operation/Stop Error status...
Page 45
¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
8-4. Details of function ¢ Control input function When function setting is "Operation/Stop" mode 1 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal...
Page 47
When function setting is "Forced stop" mode • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
Page 48
When function setting is "Operation/Stop" mode 2 • In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Stop Input of indoor unit Terminal (Remote On →...
Page 49
¢ Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 60-02 / 4 60-05 / 7 Off → On Thermostat off 60-06 / 8 External input and output Input 1 60-08 / A 60-09 / B...
Page 50
¢ Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal 60-00 / 2 Off → On Error 60-01 / 3 60-02 / 4...
Page 51
¢ Indoor unit fan operation status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Fan run 60-10 / C Output of indoor unit CN47 High → Low Fan stop 60-00 / 2 Off →...
Page 52
¢ External heater output Function setting Indoor unit Wired R. C. Control Primary heater Auxiliary heater Control switching external heaters Sensor activation* No. 61 Auxiliary heater Heat pump 61-00 — External device* control 1 Auxiliary heater Heat pump External device 61-01 —...
Page 53
Return air • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 49 - 8-4.
Page 54
Auxiliary equipment control by room temperature Auxiliary equipment control is switchable by room temperature. Auxiliary equipment switching is per- formed for each room temperature divided to following 3 zones. Zone A Ts +0.9°F (0.5 °C) Ts: Setting temperature Ts -0.9°F (0.5 °C) Tr: Room temperature Zone B Zone C...
Page 55
Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
Page 56
Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. DIP-SW101-3 • Heater is off as shown in following diagram of heating temperature.
Page 57
Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater is on as shown in following diagram of heating Heater on temperature.
Page 58
• Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump Combination zone prohibition only zone Outdoor temperature zone* zone Comp. On/Off 12 V Heater DIP-SW101-3: On DIP-SW101-3: Off *: The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 59
Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
Page 60
• Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Combination zone Outdoor temperature zone * prohibition zone Comp. On/Off 12 V Heater DIP-SW101-3 On DIP-SW101-3 Off * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 61
Auxiliary heater control by outdoor temperature 3 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
Page 62
• Operation status Heat pump only zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater DIP-SW101-3 On DIP-SW101-3 Off *: The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 63
Auxiliary heat pump control • External heater output Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. DIP-SW101-3 • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Indoor unit fan •...
Page 64
Auxiliary heat pump control by outdoor temperature 1 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. DIP-SW101-3 • Heater is off as shown in following diagram of heating temperature.
Page 65
• Outdoor temperature zone Outdoor temp. Combination zone ( Heat pump + Heater) A + 3.6°F ( 2°C): -0.4°F (-18°C) *A: -4°F (-20°C) Heater only zone *: Adjustable by function setting 67 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting)
Page 66
Auxiliary heat pump control by outdoor temperature 2 • External heater output Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. DIP-SW101-3 • Heater is off as shown in following diagram of heating temperature.
Page 67
• Outdoor temperature zone Outdoor temp. Heater only zone B + 3.6°F (2°C): 46.4°F (8°C) *B: 42.8°F (6°C) Combination zone (Heat pump + Heater) *: Adjustable by function setting 67 • Operation status Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C)
Page 68
Auxiliary heat pump control by outdoor temperature 3 • External heater output Operation Condition Heater is on as shown in following diagram of heating Heater on temperature. DIP-SW101-3 • Heater is off as shown in following diagram of heating temperature.
Page 69
• Outdoor temperature zone Outdoor temp. Heater only zone B + 3.6°F (2°C): 46.4°F (8°C) B: 42.8°F (6°C)* Combination zone (Heat pump + Heater) A + 3.6°F (2°C): -0.4°F (-18°C) A: -4°F (-20°C)* Heater only zone ...
Page 70
¢ Heating thermostat on for humidifier Indoor unit Function External output setting Situation Mode Rotary SW Heating Indoor unit fan Heating thermostat on operation thermostat on no. 60 status 60-05 CN47 Example of 60-06 Output3 individual Not used 60-07 Output2 connection 60-08 Output1...
NOTE: Incorrect settings can cause a product malfunction. 9-1. Function settings on indoor unit ¢ Models: ARU18RGLX, ARU24RGLX, ARU30RGLX, and ARU36RGLX By using some components on the PCB, you can change the function settings. Related components on the PCB and the applicable settings...
Page 72
DIP switch setting • Remote controller address setting (SW100) When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00. Remote DIP switch number controller...
9-2. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment. ¢ Setting procedure by using remote controller Remote controller is not attached for this product.
Page 74
2) Static pressure Select the appropriate static pressure according to the installation conditions. Function number Setting value Setting description Factory setting 0.12 inWG (30 Pa) 0.16 inWG (40 Pa) 0.20 inWG (50 Pa) 0.24 inWG (60 Pa) 0.28 inWG (70 Pa) 0.32 inWG (80 Pa) 0.36 inWG (90 Pa) 0.40 inWG (100 Pa)
Page 75
3) Room temperature control for indoor unit sensor NOTE: If the remote sensor unit option is selected, perform this setting. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
Page 76
4) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to “Both“ (01). Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 77
7) Cold air prevention This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the setting on the remote controller. (Excluding defrost mode) Function number Setting value Setting description Factory setting Enable ♦...
Page 78
11) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable Enable Remote controller...
Page 79
14) Operating temperature switching of external heaters Sets the temperature conditions when the external heater is ON. For details, refer to “External heater output” in Chapter 8-4. "Details of function" on page 42. Setting description Setting value of function 61: Function Setting Factory...
Page 80
16) Outdoor temperature zone boundary temperature B Setting required if changing of the outdoor temperature setting for heat pump only zone is required when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details, refer to “External heater output” in Chapter 8-4. "Details of function"...
Page 81
19) Fan delay time Sets the fan delay time when the heater is turned off. Function number Setting value Setting description Factory setting 1 minute ♦ 50 seconds 40 seconds 30 seconds 20) External heater use in defrosting Enables or disables external heater use in defrosting. NOTE: Inappropriate heater selection may cause cold air in defrosting.
10. Accessories Part name Exterior Part name Exterior Operation manual Cable tie (large) Installation manual Cable tie (medium) (indoor unit) Special nut A (large Cable tie (small) flange) Special nut B (small Drain hose insulation flange) Washer Drain hose Coupler heat insulation Hose band (large) Coupler heat insulation...
11. Optional parts 11-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD Office Fri 10:00AM Mode Set Temp. Wired Remote panel. Backlit LCD enables easy Cool 80°F Custom Auto Auto Heat 74°F UTY-RNRUZ* Cool 84°F Room Temp.
FGL sales company. For connection between indoor unit Modbus UTY-VMSX with UART interface and a Modbus Converter open network. This converter can control Fujitsu Thermostat UTY-TTRX General products using a third-party Converter thermostat controller. - 80 - 11-2. Others...
Page 85
Exterior Part name Model name Summary This converter is required when Network UTY-VTGX connecting single split system to VRF Converter network system. Network This converter is required when Converter UTY-VTGXV connecting single split system to VRF (AC power network system. supply) NOTE: Combined use of following optional parts and WLAN Adapter (UTY-TFSXZ2) is not allowed.
1. Specifications Type Inverter, Heat pump Model name AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current 11.5 16.1 Cooling 1,177 (2,000) 2,119 (3,600) 2,237 (3,800) Airflow rate CFM (m Heating 1,489 (2,530)
3. Installation space 3-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX ¢ Space requirement Provide sufficient installation space for product safety. Single outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Page 91
• When there is an obstruction in the upper space: Unit: in (mm) When there are obstacles at the rear When there are obstacles at the rear, sides, and and above. above. Max. 19 Max. 19 (500) (500) 40 (1,000) or more 24 (600) or more...
Page 92
Multiple outdoor unit installation • When the upper space is open: Unit: in (mm) When there are obstacles at the rear only. When there are obstacles at the front only. 60 (1,500) or more 10 (250) 12 (300) or more or more When there are obstacles at the front and rear.
Page 93
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 79 (2,000) or more 119 (3,000) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 40 (1,000) or more 10 (250) or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX NOTE: Values mentioned in the table are calculated based on the maximum capacity.
9-2. Sound level check point Rear Microphone Microphone Airflow 40 in (1 m) Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 99 - 9-2. Sound level check point 9.
11. Safety devices Model Type of protection Protection form AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX Current fuse (Filter PCB) 250 V, 5 A × 2 Circuit protection Current fuse (Main PCB) 250 V, 3.15 A × 2 °F (150 °C) Activate Fan motor stop Fan motor protection Thermal protection °F (120 °C)
12. Accessories 12-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX Part name Exterior Part name Exterior Installation manual Drain cap Drain pipe - 102 - 12-1. Models: AOU18RGLX, AOU24RGLX, AOU30RGLX, and AOU36RGLX 12. Accessories...