INSTALLATION MANUAL OUTDOOR UNIT For authorized service personnel only. INSTALLATIONSANLEITUNG AUSSENGERÄT Nur für autorisiertes Fachpersonal. MANUEL D'INSTALLATION UNITÉ EXTÉRIEURE Pour le personnel de service agrée uniquement. MANUAL DE INSTALACIÓN UNIDAD EXTERIOR Únicamente para personal de servicio autorizado. AJ*072LELAH AJ*090LELAH MANUALE D'INSTALLAZIONE AJ*108LELAH UNITÀ...
INSTALLATION MANUAL 1. SAFETY PRECAUTIONS VRF system outdoor unit • Be sure to read this Installation manual thoroughly before installation. PART No. 9380545293-04 • The warnings and precautions indicated in this Installation manual contain important information pertaining to your safety. Be sure to observe them. Contents •...
This mark indicates procedures which, if improperly per- 2. ABOUT THIS PRODUCT CAUTION formed, might possibly result in personal harm to the user, or damage to property. 2.1. Precautions for using R410A refrigerant This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids.
2.4. Combinations 3.2. Drain processing The number of CAUTION Outdoor unit cooling Maximum connect- Model indoor units that can capacity [kW] able indoor units Perform drain work in accordance with this Manual, and ensure that the drain water is be connected are as properly drained.
3.3.1 Single outdoor unit installation 3.3.3 Outdoor units installation in multi row When the upward area is open Unit: mm * The following settings are not recommended in case of cooling by a low outside tem- perature. Unit: mm (1) Obstacles at rear only (2) Obstacles at rear and sides only (1) Single parallel unit arrangement (2) Multiple parallel unit arrangement...
3.5. Installing the unit 4. SYSTEM CONFIGURATION • Please install the outdoor unit without slant. (within 0.3 degrees ) For detailed information, refer to the Design and Technical Manual. • Install 4 anchor bolts at the locations indicated with arrows in the figure. 4.1.
Table. B (Diameter of piping used between outdoor unit and first separation 5. PIPE INSTALLATION tube or header) For the following installation conditions, it is necessary to increase the piping size. 5.1. Brazing • Condition 1: Total indoor unit capacity ratio ˃ 110% •...
5.4.2 Removing the pinch pipe 5.3. Opening the knockout hole WARNING CAUTION Remove the pinch pipe only when the internal gas is completely drained as shown on the below instructions. Be careful not to deform or scratch the panel while opening the knockout holes. If gas still remains inside, the piping may crack if you melt the brazing filler metal of the To protect the piping insulation after opening a knockout hole, remove any burrs from junction area with a burner.
6. ELECTRICAL WIRING 6.2. Knockout hole CAUTION 6.1. The precautions of electrical wiring Be careful not to deform or scratch the panel while opening the knockout holes. WARNING After opening the knockout holes, remove burr on the edges, and attach the one-touch bush (accessory), grommet or conduit etc.
6.4.3 Enabling/Disabling automatic address setting 6.4. Transmission line You can enable/disable automatic address setting for the indoor unit and the signal ampli- fier. CAUTION To enable automatic address setting for the indoor unit, connect the indoor unit to outdoor Caution when wiring cable: units under the same refrigerant system.
Page 11
6.5.2 Wiring procedure How to connect wiring to the terminal • Remove the service panel. And connect the cable to the terminal in accordance with the Caution when wiring cable (1) Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal name plate.
Operation behavior 6.6. External input and external output Each input terminal works as follows. 6.6.1 Terminal position Connector Input signal Status Base heater Normal operation Output 1 (CN136: Black) Input 1 (CN115: Black) CN131 (Yellow) Outdoor unit PC board Low noise mode operation EXT.
7. FIELD SETTING 7.3. Rotary switch setting The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit. Config- CAUTION ure the settings only on the master unit of a refrigerant system. Discharge the static electricity from your body before setting up the DIP switches. If multiple refrigerant systems are connected, set the rotary switch (REF AD) as shown in Never touch the terminals or the patterns on the parts that are mounted on the PC the table below.
Page 14
(1) Turn on the power of the outdoor unit and enter standby mode. Level 1 (stop) • When system is abnormal • When system is normal Level 2 Check the settings as there is an error in the POWER/MODE lamp lights up. (ER- (operated at 40% capacity) settings for outdoor unit address ROR lamp is off.)
7.6.2 Procedures to enable automatic address setting on indoor 7.5. Address setting for signal amplifi ers units 7.5.1 Address setting for signal amplifi ers Check that the rotary switch IU AD on the indoor unit PC board is set to “00”.If it is not set to “00”, it means the address of that device is not set.
Evacuation procedure 8. PIPE INSTALLATION II (1) Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed. Fig. A: Connection diagram Fig. B (2) Remove the charging port cap. (3) Connect a vacuum pump and a pressure gauge to a charging hose and connect it to Service hose Pressure regu- Pressure...
(1) Calculation of additional amount for pipe length 9. TEST RUN Total length of ø 12.70 Total length of ø 9.52 mm liquid pipe mm liquid pipe a × 0.114 a × 0.058 9.1. Indoor unit connection check (kg/m) (kg/m) Normal operation will not be possible without performing the Indoor unit connection check.
9.1.3 Error displays Test operation setting method Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the indoor unit PC board to • When error occurs, “Err” and “Number of errors occurred” are alternately displayed on configure settings according to the procedures below. the 7-segment display every 1 second.