1. Specifications Wall mounted Type Inverter, Heat pump Model name ASHH09KHCBN ASHH12KHCBN ASHH14KHCBN Power supply intake Outdoor unit Voltage System power supply Frequency Available voltage range 207—253 Indoor unit power supply (from outdoor unit) Rated Btu/h 8,500 11,900 14,300 Cooling 0.7—4.7 0.7—5.1 0.8—5.9...
Page 7
Wall mounted Type Inverter, Heat pump Model name ASHH09KHCBN ASHH12KHCBN ASHH14KHCBN 14.5 Weight Gross 18.0 Liquid Ø6.35 (Ø1/4) Size mm (in) Connection pipe Ø9.52 (Ø3/8) Method Flare Material Polypropylene + Linear low-density polyethylene Drain hose Tip diameter Ø13.8 (I.D.), Ø15.8 to Ø16.7 (O.D.) °C 18 to 32 Cooling...
After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 4 - 2-1. System requirement...
3. Dimensions 3-1. Models: ASHH09KHCBN, ASHH12KHCBN, and ASHH14KHCBN Unit: mm Outline of unit for pipe inlet Ø65 for pipe inlet Ø65 - 5 - 3-1. Models: ASHH09KHCBN, ASHH12KHCBN, and ASHH14KHCBN 3. Dimensions...
Page 10
¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm Outline of unit 75 or more 70 or more 127 or more 133 or more 1,500 or more - 6 - 3-1. Models: ASHH09KHCBN, ASHH12KHCBN, and ASHH14KHCBN 3.
3-2. Pipe exit length from the rear Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 5-1.
6. Fan performance 6-1. Air velocity distributions ¢ Model: ASHH09KHCBN Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center...
Page 16
¢ Model: ASHH12KHCBN Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
Page 17
¢ Model: ASHH14KHCBN Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
8. Safety devices Model Type of ASHH09KHCBN Protection form protection ASHH12KHCBN ASHH14KHCBN Circuit protection Current fuse (PCB*) 250 V, 3.15 A 150 ±15°C Activate Fan motor stop Fan motor Thermal protector protection program 120 ±15°C Reset Fan motor restart *PCB: Printed Circuit Board - 19 - 8.
9-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
Page 26
¢ External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
Page 27
¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External Input and Output PCB.
9-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
Page 29
¢ External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V ±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Setting of external input and output"...
9-3. Setting of external input and output • Indoor unit Input Connection point Function setting number 46 Function Operation/Stop mode 1 (R.C. enabled) (Setting prohibited) CN46 Forced stop mode Operation/Stop mode 2 (R.C. disabled) Output Connection point Function setting number 60 Function Operation/Stop 01 to 08...
9-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Off → On Operation — Input of indoor unit CN46 On →...
Page 32
¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Forced stop Off → On (R.C. disabled) — Input of indoor unit CN46 Normal On → Off (R.C.
Page 33
¢ Operation/Stop mode 2 • In the case of “Edge” input External Input and Output PCB Function External input Input signal Command setting Rotary SW302 switch Operation Off → On (R.C. enabled) — Input of indoor unit CN46 Stop On → Off (R.C.
Page 34
¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D CN313 Output PCB On → Off Normal operation CN313 Compressor Room temp. Set temp. - 30 - 9-4.
9-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 1, 2 Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
Page 36
¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
10. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
11. Remote controller 11-1. Wireless remote controller ¢ Overview a MODE button b FAN SPEED button c POWERFUL button d SET button (Left/right airflow) e ECONOMY button f 10 °C HEAT button g OUTDOOR LOW NOISE button h ENERGY SAVING button i RESET button j TEST RUN button k WLAN button...
Page 39
¢ Specifications Controller Unit: mm Top view Front view Side view Size (H × W × D) 181 × 58 × 17 Weight 116 (without batteries) Holder Unit: mm Top view Ø (Hole) Hole 26.3 62.8 Front view Side view Size (H ×...
12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 12-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
Page 41
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign 30/31...
Page 42
2) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
Page 43
3) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 44
6) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 7) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 45
10) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—08 (Setting prohibited) Error status Indoor unit fan operation status (Setting prohibited) - 41 -...
12-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
14. Optional parts 14-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy Wired Remote UTY-RNRGZ* operation in a dark room. Controller Wire type: Non-polar 2-wire High visibility and easy operation. Room temperature can be accurately Wired Remote UTY-RLRG...
14-2. Others Exterior Part name Model name Summary Air Cleaning Filter can be mounted to Air Cleaning UTR-FA16-5 the indoor unit. Filter (For antibacterial) Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZX Connect Kit Connecting point: CN46 and CN47 on Main PCB Required when external device is connected.
1. Specifications Type Inverter, Heat pump Model name AOHH09KHCBN AOHH12KHCBN AOHH14KHCBN Power supply 230 V~ 50 Hz Power supply intake Outdoor unit Available voltage range 207—253 V Starting current Cooling 1,850 2,630 2,530 Airflow rate Heating 1,690 2,140 2,070 Type × Qty Propeller fan ×...
2. Dimensions 2-1. Model: AOHH09KHCBN Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 49 - 2-1. Model: AOHH09KHCBN 2. Dimensions...
2-2. Models: AOHH12KHCBN and AOHH14KHCBN Unit: mm 4-M10 hole Pitch of bolts for installation Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 50 - 2-2. Models: AOHH12KHCBN and AOHH14KHCBN 2. Dimensions...
3. Installation space 3-1. Models: AOHH09KHCBN, AOHH12KHCBN, and AOHH14KHCBN ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 56
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 57
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOHH09KHCBN, AOHH12KHCBN, and AOHH14KHCBN NOTE: Values mentioned in the table are calculated based on the maximum capacity.
10. Electrical characteristics Model name AOHH09KHCBN AOHH12KHCBN AOHH14KHCBN Voltage Power supply Frequency 12.5 15.5 Max operating current* Starting current Circuit breaker current Power cable Wiring Cross-sectional spec.* Connection area cable* Limited wiring length NOTES: • *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
11. Safety devices Model Type of Protection form protection AOHH09KHCBN AOHH12KHCBN AOHH14KHCBN 250 V, 25 A Current fuse (PCB*) Circuit 250 V, 5 A protection Current fuse (Base pan heater) 250 V, 3.15 A 125 ±10°C Activate Fan motor stop Fan motor Thermal protection program protection...
12. Accessories 12-1. Models: AOHH09KHCBN, AOHH12KHCBN, and AOHH14KHCBN Part name Exterior Part name Exterior Installation manual - 64 - 12-1. Models: AOHH09KHCBN, AOHH12KHCBN, and AOHH14KHCBN 12. Accessories...