Fujitsu AIRSTAGE ASEG18-24KMTE Design & Technical Manual
Fujitsu AIRSTAGE ASEG18-24KMTE Design & Technical Manual

Fujitsu AIRSTAGE ASEG18-24KMTE Design & Technical Manual

4-unit multi-split type, 5-unit multi-split type

Advertisement

Quick Links

AIR CONDITIONER
4-unit multi-split type,
5-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
ARXH12–18KMTAP
ARXH22KMTAP
ASEH07–14KMCG-B
ASEG18–24KMTE
AUXG07–22KVLA
ARXG07–14KSLAP
ASEH07–14KMCG
ASEG07–14KETF-B
ABEG18–22KRTA
AGEG09–14KVCA
ARXG07–14KLLAP
ARXG18KSLAP
ARXG18KLLAP
ASEG07–14KETF
ASEH07–14KGTG
OUTDOOR
ARXG22KMLB
ASEH05–12KNCA
AOEG30KBTA4
AOEG36KBTA5
DR_MU025ES_13
2024.05.24

Advertisement

loading

Summary of Contents for Fujitsu AIRSTAGE ASEG18-24KMTE

  • Page 1 AIR CONDITIONER 4-unit multi-split type, 5-unit multi-split type DESIGN & TECHNICAL MANUAL INDOOR AUXG07–22KVLA ARXG07–14KSLAP ARXG07–14KLLAP ARXG22KMLB ARXG18KSLAP ARXG18KLLAP ARXH12–18KMTAP ASEH07–14KMCG ASEG07–14KETF ASEH07–14KGTG ASEH05–12KNCA ARXH22KMTAP ASEH07–14KMCG-B ASEG07–14KETF-B OUTDOOR ASEG18–24KMTE ABEG18–22KRTA AGEG09–14KVCA AOEG30KBTA4 AOEG36KBTA5 DR_MU025ES_13 2024.05.24...
  • Page 2 • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of FUJITSU GENERAL LIMITED in the United States, other countries or both. “AIRSTAGE Mobile” is a trademark of FUJITSU GENERAL LIMITED. Android and Google Play are trademarks of Google LLC.
  • Page 3 CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................4 2. Specifications....................16 2-1. Compact cassette type ....................16 2-2. Mini duct type.........................18 2-3. Slim duct type ........................20 2-4. Medium static pressure duct type ..................22 2-5. Wall mounted type ......................25 2-6.
  • Page 4 CONTENTS (continued) 8-1. Compact cassette type ....................145 8-2. Mini duct type.......................146 8-3. Slim duct type ......................147 8-4. Medium static pressure duct type ................148 8-5. Wall mounted type .......................149 8-6. Ceiling type ........................153 8-7. Floor type........................154 9. Noise level curve..................155 9-1. Compact cassette type ....................155 9-2.
  • Page 5 CONTENTS (continued) 15. Function settings ..................277 15-1.Mini duct, Slim duct types indoor unit (setting by DIP switch) ........277 15-2.Medium static pressure duct type (ARXH12–22KMTAP) ..........279 15-3.Indoor unit (setting by wireless remote controller)............280 15-4.Indoor unit (setting by wired remote controller) ............300 15-5.Indoor unit (setting by simple remote controller) ............313 15-6.Function details......................320 15-7.Wired remote controller (UTY-RNNYM) ..............328...
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT (4 UNITS TYPE) ........361 1. Specifications....................362 2. Dimensions....................364 2-1. Model: AOEG30KBTA4 ....................364 3. Installation space ..................365 3-1. Model: AOEG30KBTA4 ....................365 4. Refrigerant circuit ..................368 4-1. Model: AOEG30KBTA4 ....................368 5. Wiring diagram ..................369 5-1. Model: AOEG30KBTA4 ....................369 6.
  • Page 7 CONTENTS (continued) Part 3. OUTDOOR UNIT (5 UNITS TYPE) ........441 1. Specifications....................442 2. Dimensions....................444 2-1. Model: AOEG36KBTA5 ....................444 3. Installation space ..................445 3-1. Model: AOEG36KBTA5 ....................445 4. Refrigerant circuit ..................448 4-1. Model: AOEG36KBTA5 ....................448 5. Wiring diagram ..................449 5-1. Model: AOEG36KBTA5 ....................449 6.
  • Page 8 CONTENTS (continued) 17-2.Points to remember when installing ................529...
  • Page 9 Part 1. INDOOR UNIT COMPACT CASSETTE MINI DUCT TYPE: TYPE: AUXG07–22KVLA ARXG07–18KSLAP SLIM DUCT TYPE: MEDIUM STATIC PRES- SURE DUCT TYPE: ARXG07–18KLLAP ARXG22KMLB ARXH12–22KMTAP WALL MOUNTED TYPE: ASEH07–14KMCG ASEG07–14KETF ASEH07–14KGTG ASEG18–24KMTE ASEH07–14KMCG-B ASEG07–14KETF-B ASEH05–12KNCA CEILING TYPE: FLOOR TYPE: ABEG18–22KRTA AGEG09–14KVCA...
  • Page 10 1. Model lineup Indoor unit AUXG07KVLA ARXG07KSLAP ARXG07KLLAP ARXG22KMLB AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP AUXG18KVLA ARXG18KSLAP ARXG18KLLAP AUXG22KVLA ARXH12KMTAP ASEH07KMCG ASEH07KMCG-B ASEG07KETF ARXH14KMTAP ASEH09KMCG ASEH09KMCG-B ASEG09KETF ARXH18KMTAP ASEH12KMCG ASEH12KMCG-B ASEG12KETF ARXH22KMTAP ASEH14KMCG ASEH14KMCG-B ASEG14KETF ASEG07KETF-B ASEH07KGTG ASEH05KNCA ASEG18KMTE ASEG09KETF-B...
  • Page 11 Outdoor unit AOEG30KBTA4 AOEG36KBTA5 - 3 - 1. Model lineup...
  • Page 12 1-1. Indoor unit connection patterns ¢ 4-unit multi-split type AOEG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — — — — — —...
  • Page 13 AOEG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 14 AOEG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total - 6 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 15 AOEG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total Numbers in column Unit 1 to 4, and Total indicate the indoor unit capacities as follows: 5: 5,000 Btu/h, 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 7 - 1-1.
  • Page 16 ¢ 5-unit multi-split type AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 17 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 18 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 19 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 20 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 21 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total - 13 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 22 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total - 14 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 23 AOEG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total Numbers in column Unit 1 to 5 and Total indicate the indoor unit capacities as follows: 5: 5,000 Btu/h, 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..*: As for the 22 model, wall-mounted type indoor unit is only connectable.
  • Page 24 2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 25 Model name AUXG18KVLA AUXG22KVLA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.30 0.62 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Turbo fan × 1 Motor output HIGH Cooling...
  • Page 26 2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
  • Page 27 Model name ARXG18KSLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.49 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Sirocco fan × 3 Motor output Recommended static pressure 0 to 50...
  • Page 28 2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 29 Model name ARXG18KLLAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.44 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Sirocco fan × 3 Motor output Recommended static pressure 0 to 90 HIGH...
  • Page 30 2-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Model name ARXG22KMLB Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.50 HIGH 1,100 Cooling QUIET Airflow rate HIGH 1,100 Heating QUIET Type ×...
  • Page 31 ¢ Models: ARXH12–22KMTAP Model name ARXH12KMTAP ARXH14KMTAP ARXH18KMTAP Power supply 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.34 0.49 0.52 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Sirocco fan ×...
  • Page 32 Model name ARXH22KMTAP Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.50 HIGH 1,150 Cooling QUIET Airflow rate HIGH 1,150 Heating QUIET Type × Qty Sirocco fan × 2 Motor output Static pressure range 30 to 150...
  • Page 33 2-5. Wall mounted type ASEH07KMCG ASEH09KMCG ASEH12KMCG ASEH14KMCG Model name ASEH07KMCG-B ASEH09KMCG-B ASEH12KMCG-B ASEH14KMCG-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
  • Page 34 ASEG07KETF ASEG09KETF ASEG12KETF ASEG14KETF Model name ASEG07KETF-B ASEG09KETF-B ASEG12KETF-B ASEG14KETF-B Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 35 Model name ASEH07KGTG ASEH09KGTG ASEH12KGTG ASEH14KGTG Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan × 1 Motor output HIGH Cooling...
  • Page 36 Model name ASEH05KNCA ASEH07KNCA ASEH09KNCA ASEH12KNCA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.11 0.12 0.19 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 37 Model name ASEG18KMTE ASEG22KMTE ASEG24KMTE Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power 37.5 47.0 61.6 Running current 0.35 0.39 0.44 HIGH 1,060 1,170 Cooling QUIET Airflow rate HIGH 1,020 1,060 1,170 Heating QUIET...
  • Page 38 2-6. Ceiling type Model name ABEG18KRTA ABEG22KRTA Power supply 1Ø 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.21 0.25 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Sirocco fan × 2 Motor output HIGH Cooling...
  • Page 39 2-7. Floor type Model name AGEG09KVCA AGEG12KVCA AGEG14KVCA Power supply 230 V~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Qty Crossflow fan ×...
  • Page 40 After installation of mobile app, user registration is required. For user registration and setup infor- mation, refer to Setting Manual attached with the product. For the latest version of the wireless LAN control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/ - 32 - 3-1. System requirement...
  • Page 41 4. Dimensions 4-1. Compact cassette type ¢ Models: AUXG07–22KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View B View C - 33 - 4-1. Compact cassette type 4. Dimensions...
  • Page 42  Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700 High ceiling —...
  • Page 43 4-2. Mini duct type ¢ Models: ARXG07–14KSLAP Unit: mm Rear view Drain port P 100 × 6 = 600 Side view (L) Top view Side view (R) Front view Bottom view - 35 - 4-2. Mini duct type 4. Dimensions...
  • Page 44 ¢ Model: ARXG18KSLAP Unit: mm Rear view Drain port P 100 × 8 = 800 Side view (L) Top view Side view (R) Front view Bottom view - 36 - 4-2. Mini duct type 4. Dimensions...
  • Page 45  Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
  • Page 46 4-3. Slim duct type ¢ Models: ARXG07–14KLLAP Unit: mm View A Rear view Drain port 100 x 6 = 600 Side view Top view Front view Bottom view - 38 - 4-3. Slim duct type 4. Dimensions...
  • Page 47 ¢ Model: ARXG18KLLAP Unit: mm Rear view View A Drain port 100 × 8 = 800 Top view Side view Front view Bottom view - 39 - 4-3. Slim duct type 4. Dimensions...
  • Page 48  Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
  • Page 49 4-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Unit: mm Φ205 Φ3.2 Front view 1,177 Gas pipe Drain port Liquid pipe Φ200 Knockout Drain port for fresh air Φ5 Φ3.2 80 80 P125 × 3 = 375 P125 × 3 = 375 Φ5 1,015 1,135...
  • Page 50  Maintenance space requirement Unit: mm • Provide a maintenance access for maintenance purposes. Maintenance access Control box • The maintenance access necessary for fan units and filter maintenance. Maintenance access Intake panel Control box 1,550 • When using a square duct P174 ×...
  • Page 51 ¢ Models: ARXH12–18KMTAP Unit: mm Rear view P100 × 5 = 500 Hole: × Φ4 PCD*160 Φ125 Φ4.5 P100 × 5 = 500 *: PCD (Pitch Circle Diameter) Side view (L) Top view Side view (R) Front view - 43 - 4-4.
  • Page 52  Installation space requirement Unit: mm 20 or more 300 or more 20 or more* Ceiling 2,500 or more (When no ceiling) Floor *: According to the distance between the ceiling and the unit, the construction plan of the mainte- nance access differs.
  • Page 53 Unit: mm • Distance between the ceiling and the unit is from 20 to 300: Choose one of these methods to set up the maintenance access. Pattern A Maintenance access Control box 100 to 200 Pattern B 1,300 or more Control box Bottom view - 45 -...
  • Page 54 ¢ Model: ARXH22KMTAP Unit: mm Rear view 1,000 P100 × 8 = 800 Hole: × Φ4 PCD*160 Φ125 Φ4.5 P100 × 7 = 700 1,040 *: PCD (Pitch Circle Diameter) Side view (L) Top view Side view (R) Front view - 46 - 4-4.
  • Page 55  Installation space requirement Unit: mm 20 or more 300 or more 20 or more* Ceiling 2,500 or more (When no ceiling) Floor *: According to the distance between the ceiling and the unit, the construction plan of the mainte- nance access differs.
  • Page 56 Unit: mm • Distance between the ceiling and the unit is from 20 to 300: Choose one of these methods to set up the maintenance access. Pattern A Maintenance access 1,100 Control box 1,000 100 to 200 Pattern B 1,600 or more Control box 1,000 Bottom view...
  • Page 57 4-5. Wall mounted type ¢ Models: ASEH07–14KMCG and ASEH07–14KMCG-B Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 49 - 4-5. Wall mounted type 4. Dimensions...
  • Page 58  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 50 - 4-5.
  • Page 59 ¢ Models: ASEG07–14KETF and ASEG07–14KETF-B Unit: mm (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 51 - 4-5. Wall mounted type 4. Dimensions...
  • Page 60  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 61 ¢ ASEH07–14KGTG Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 53 - 4-5. Wall mounted type 4. Dimensions...
  • Page 62  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more A: Install so that the flare connection part is outdoors. - 54 - 4-5.
  • Page 63 ¢ Models: ASEH05–12KNCA Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 55 - 4-5. Wall mounted type 4. Dimensions...
  • Page 64  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 30 or more 40 or more Wall hook bracket 107 or more Outline of the indoor unit 163 or more 1,500 or more - 56 - 4-5. Wall mounted type 4.
  • Page 65 ¢ Models: ASEG18–24KMTE Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 57 - 4-5. Wall mounted type 4. Dimensions...
  • Page 66  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more Wall hook bracket 70 or more 117 or more Outline of the indoor unit 160 or more 1,500 or more A: Install so that the flare connection part is outdoors. - 58 - 4-5.
  • Page 67 ¢ Pipe exit length from the rear (for KMCG, KMCG-B, KGTG, and KNCA) Design the system considering the length of the pipes or hose exiting from the rear of the indoor unit. NOTE: Detailed shapes of the indoor unit and the tip of each pipe or hose may vary depending on the model.
  • Page 68 4-6. Ceiling type ¢ Models: ABEG18–22KRTA Unit: mm 1,080 49 84 125 103 Side view Top view ø100-mm hole Rear view Suspension bolt pitch Dimensions Indoor unit (Top view) (Space required for installation) The length of the bolt here is 30 mm. Indoor unit - 60 - 4-6.
  • Page 69 ¢ Installation space requirement Unit: mm Ceiling Indoor unit 30 or more Ceiling 200 or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height (mm) Ceiling mode Standard High ceiling 18, 22 models...
  • Page 70 4-7. Floor type ¢ Models: AGEG09–14KVCA Unit: mm Side view Front view - 62 - 4-7. Floor type 4. Dimensions...
  • Page 71  Installation space Unit: mm 100 or more 80 or more 80 or more 50 or more 150 or below from the floor PROHIBITED Grating WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg)
  • Page 72 5. Wiring diagrams 5-1. Compact cassette type ¢ Models: AUXG07–22KVLA - 64 - 5-1. Compact cassette type 5. Wiring diagrams...
  • Page 73 5-2. Mini duct type and Slim duct type ¢ Models: ARXG07–18KSLAP and ARXG07–18KLLAP WLAN adapter, Converter etc. (Option) - 65 - 5-2. Mini duct type and Slim duct type 5. Wiring diagrams...
  • Page 74 5-3. Medium static pressure duct type ¢ Model: ARXG22KMLB - 66 - 5-3. Medium static pressure duct type 5. Wiring diagrams...
  • Page 75 ¢ Models: ARXH12–22KMTAP - 67 - 5-3. Medium static pressure duct type 5. Wiring diagrams...
  • Page 76 5-4. Wall mounted type ¢ Models: ASEH07–14KMCG and ASEH07–14KMCG-B - 68 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 77 ¢ Models: ASEG07–14KETF and ASEG07–14KETF-B - 69 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 78 ¢ Models: ASEH07–14KGTG - 70 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 79 ¢ Models: ASEH05–12KNCA - 71 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 80 ¢ Models: ASEG18–24KMTE - 72 - 5-4. Wall mounted type 5. Wiring diagrams...
  • Page 81 5-5. Ceiling type ¢ Models: ABEG18–22KRTA - 73 - 5-5. Ceiling type 5. Wiring diagrams...
  • Page 82 5-6. Floor type ¢ Models: AGEG09–14KVCA - 74 - 5-6. Floor type 5. Wiring diagrams...
  • Page 83 6. Air velocity and temperature distributions 6-1. Compact cassette type ¢ Models: AUXG07–09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25...
  • Page 84 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 85 ¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Horizontal louver: Up 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 77 - 6-1.
  • Page 86 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data...
  • Page 87 ¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Horizontal louver: Up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Horizontal louver: Up 0.25 0.25 4 (m) - 79 - 6-1.
  • Page 88 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Horizontal louver: Down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH...
  • Page 89 ¢ Model: AUXG18KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Horizontal louver: Up 0.25 0.25 0.25 Unit: m/s Side view Horizontal louver: Up 0.25 0.25 Unit: m/s Side view Horizontal louver: Down 0.25 0.25 - 81 -...
  • Page 90 ¢ Model: AUXG22KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Horizontal louver: Up 0.25 0.25 0.25 0.25 Unit: m/s Side view Horizontal louver: Up 0.25 0.25 Unit: m/s Side view Horizontal louver: Down 0.25 0.25 - 82 -...
  • Page 91 6-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 92 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 84 - 6-2.
  • Page 93 ¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 94 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 86 - 6-2.
  • Page 95 ¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 96 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 88 - 6-2.
  • Page 97 ¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 98 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 90 - 6-2.
  • Page 99 ¢ Model: ARXG18KSLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 100 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 92 - 6-2.
  • Page 101 6-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up...
  • Page 102 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 94 - 6-3.
  • Page 103 ¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 104 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 96 - 6-3.
  • Page 105 ¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 106 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 98 - 6-3.
  • Page 107 ¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 108 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 100 - 6-3.
  • Page 109 ¢ Model: ARXG18KLLAP NOTE: This data is measured after installing optional Auto Louver Grille Kit. Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left &...
  • Page 110 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution Unit: m/s Side view Horizontal louver: Down Vertical louver: Center • Air temperature distribution Unit: °C Side view Horizontal louver: Down Vertical louver: Center - 102 - 6-3. Slim duct type 6.
  • Page 111 6-4. Wall mounted type ¢ Models: ASEH07–12KMCG, ASEH07–12KMCG-B, ASEG07– 12KETF, ASEG07–12KETF-B, and ASEH07–09KGTG Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up...
  • Page 112 ¢ Models: ASEH14KMCG, ASEH14KMCG-B, ASEG14KETF, ASEG14KETF-B, and ASEH12–14KGTG Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s...
  • Page 113 ¢ Model: ASEH05KNCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 114 ¢ Model: ASEH07KNCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 115 ¢ Model: ASEH09KNCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 116 ¢ Model: ASEH12KNCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 117 ¢ Models: ASEG18–24KMTE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 118 6-5. Ceiling type ¢ Model: ABEG18KRTA Fan speed Operation mode Measuring conditions HIGH Unit: m/s 0.25 Top view Horizontal louver: Up Vertical louver: Center Unit: m/s 0.25 Top view Horizontal louver: Up Vertical louver: Left & Right 0.25 Unit: m/s Side view 0.25 Horizontal louver: Up...
  • Page 119 ¢ Model: ABEG22KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Horizontal louver: Up Vertical louver: Center 0.25 Top view Horizontal louver: Up Vertical louver: Left & Right 0.25 Side view 0.25 Horizontal louver: Up Vertical louver: Center Side view Horizontal louver: Down Vertical louver: Center...
  • Page 120 6-6. Floor type ¢ Models: AGEG09–14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Horizontal louver: Up Vertical louver: Center UPPER LOWER Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up...
  • Page 121 7. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 7-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Quiet (SP mode 03) Hi (SP mode 03) Normal SP upper limit...
  • Page 122  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 114 - 7-1. Mini duct type 7. Fan performance...
  • Page 123 ¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 124  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 116 - 7-1. Mini duct type 7. Fan performance...
  • Page 125 ¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
  • Page 126  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 118 - 7-1. Mini duct type 7. Fan performance...
  • Page 127 ¢ Model: ARXG14KSLAP Hi (SP mode 05) SP mode 05 upper limit Quiet (SP mode 00) Nomal SP Quiet upper limit (Nomal SP) Quiet Hi (Normal SP) (SP mode 05) SP mode 05 lower limit SP mode 00 upper limit (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 128  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 120 - 7-1. Mini duct type 7. Fan performance...
  • Page 129 ¢ Model: ARXG18KSLAP SP mode 05 Hi (SP mode 05) upper limit Quiet (SP mode 05) SP mode 05 lower limit Quiet (Normal SP) Quiet (SP mode 00) Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) SP mode 00 upper limit 1,000 1,100...
  • Page 130  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacity 1,000 1,100 Airflow (m - 122 - 7-1. Mini duct type 7. Fan performance...
  • Page 131 7-2. Slim duct type ¢ Model: ARXG07KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Normal SP upper limit lower limited Quiet (SP mode 00)
  • Page 132  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 124 - 7-2. Slim duct type 7. Fan performance...
  • Page 133 ¢ Model: ARXG09KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) Hi (SP mode00) SP mode 00 upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 09)
  • Page 134  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 126 - 7-2. Slim duct type 7. Fan performance...
  • Page 135 ¢ Model: ARXG12KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Hi (SP mode 00) upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 136  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 128 - 7-2. Slim duct type 7. Fan performance...
  • Page 137 ¢ Model: ARXG14KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) Nomal SP upper limit SP mode 09 lower limit Quiet (Nomal SP) Hi (Normal SP) SP mode 00 upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000...
  • Page 138  Characteristics of air volume and capacity • Cooling Capacity 1,000 Airflow (m • Heating Capacity 1,000 Airflow (m - 130 - 7-2. Slim duct type 7. Fan performance...
  • Page 139 ¢ Model: ARXG18KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) SP mode 00 Hi (Normal SP) upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000 1,100...
  • Page 140  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacitty 1,000 1,100 Airflow (m - 132 - 7-2. Slim duct type 7. Fan performance...
  • Page 141 7-3. Medium static pressure duct type ¢ Model: ARXG22KMLB (Normal mode) Static pressure (Pa) Fan speed Item — — — — — — — 1200 1100 1000 HIGH — — — — — — — — — — — — —...
  • Page 142 ¢ Model: ARXG22KMLB (Static pressure mode 1) Static pressure (Pa) Fan speed Item — — — — — — 1200 1000 HIGH — — — — — — — — — — — — — — — — 1000 — —...
  • Page 143 ¢ Model: ARXG22KMLB (Static pressure mode 2) Static pressure (Pa) Fan speed Item — — — — — — 1160 HIGH — — — — — — — — — — — — — — — — 1020 — — —...
  • Page 144 ¢ Model: ARXG22KMLB (Static pressure mode 3) Static pressure (Pa) Fan speed Item — — — — — — 1100 HIGH — — — — — — — — — — — — — — — — 1000 — — —...
  • Page 145 ¢ Model: ARXH12KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 lower limit Me (SP mode 15) Lo (SP mode 15) Standard SP upper limit SP mode 03 Qu (SP mode 15) upper limit Hi (Standard SP) Standard SP lower limit...
  • Page 146  Characteristics of air volume and capacity • Cooling 1,050 1,150 Airflow (m • Heating 1,050 1,150 Airflow (m - 138 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 147 ¢ Model: ARXH14KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 lower limit Me (SP mode 15) Lo (SP mode 15) Standard SP upper limit SP mode 03 upper limit Qu (SP mode 15) Hi (Standard SP) Me (Standard SP) Standard SP...
  • Page 148  Characteristics of air volume and capacity • Cooling 1,000 1,100 1,200 1,300 Airflow (m • Heating 1,000 1,100 1,200 1,300 Airflow (m - 140 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 149 ¢ Model: ARXH18KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 Me (SP mode 15) lower limit Lo (SP mode 15) Standard SP upper limit Qu (SP mode 15) SP mode 03 upper limit Hi (Standard SP) Me (Standard SP) Standard SP...
  • Page 150  Characteristics of air volume and capacity • Cooling 1,040 1,140 1,240 1,340 Airflow (m • Heating 1,040 1,140 1,240 1,340 Airflow (m - 142 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 151 ¢ Model: ARXH22KMTAP Fan performance curve 1 Hi (SP mode 15) SP mode 15 upper limit SP mode 15 lower limit Me (SP mode 15) Lo (SP mode 15) Standard SP upper limit Qu (SP mode 15) Hi (Standard SP) Me (Standard SP) Standard SP lower limit Lo (Standard SP)
  • Page 152  Characteristics of air volume and capacity • Cooling 1,050 1,150 1,250 1,350 1,450 1,550 1,650 Airflow (m • Heating 1,050 1,150 1,250 1,350 1,450 1,550 1,650 Airflow (m - 144 - 7-3. Medium static pressure duct type 7. Fan performance...
  • Page 153 8. Airflow Conversion factor: • 1 m /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 8-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA...
  • Page 154 8-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet High Cooling Quiet ARXG18KSLAP High...
  • Page 155 8-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet High Cooling Quiet ARXG18KLLAP High...
  • Page 156 8-4. Medium static pressure duct type Airflow Model Operation mode Fan speed High 1,100 Cooling Quiet ARXG22KMLB High 1,100 Heating Quiet High Cooling Quiet ARXH12KMTAP High Heating Quiet High Cooling Quiet ARXH14KMTAP High Heating Quiet High Cooling Quiet ARXH18KMTAP High Heating Quiet High...
  • Page 157 8-5. Wall mounted type Airflow Model Operation mode Fan speed High Cooling ASEH07KMCG Quiet High ASEH07KMCG-B Heating Quiet High Cooling ASEH09KMCG Quiet ASEH09KMCG-B High Heating Quiet High Cooling ASEH12KMCG Quiet ASEH12KMCG-B High Heating Quiet High Cooling ASEH14KMCG Quiet High ASEH14KMCG-B Heating Quiet High...
  • Page 158 Airflow Model Operation mode Fan speed High Cooling ASEG12KETF Quiet ASEG12KETF-B High Heating Quiet High Cooling ASEG14KETF Quiet High ASEG14KETF-B Heating Quiet High Cooling Quiet ASEH07KGTG High Heating Quiet High Cooling Quiet ASEH09KGTG High Heating Quiet High Cooling Quiet ASEH12KGTG High Heating Quiet...
  • Page 159 Airflow Model Operation mode Fan speed High Cooling Quiet ASEH05KNCA High Heating Quiet High Cooling Quiet ASEH07KNCA High Heating Quiet High Cooling Quiet ASEH09KNCA High Heating Quiet High Cooling Quiet ASEH12KNCA High Heating Quiet High Cooling Quiet ASEG18KMTE High 1,020 Heating Quiet High...
  • Page 160 Airflow Model Operation mode Fan speed High 1,170 Cooling Quiet ASEG24KMTE High 1,170 Heating Quiet - 152 - 8-5. Wall mounted type 8. Airflow...
  • Page 161 8-6. Ceiling type Airflow Model Operation mode Fan speed High Cooling Quiet ABEG18KRTA High Heating Quiet High Cooling Quiet ABEG22KRTA High Heating Quiet - 153 - 8-6. Ceiling type 8. Airflow...
  • Page 162 8-7. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGEG09KVCA High Heating Quiet High Cooling Quiet AGEG12KVCA High Heating Quiet High Cooling Quiet AGEG14KVCA High Heating Quiet - 154 - 8-7. Floor type 8. Airflow...
  • Page 163 9. Noise level curve 9-1. Compact cassette type ¢ Model: AUXG07KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 164 ¢ Model: AUXG12KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 165 ¢ Model: AUXG18KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET NC-25 QUIET NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 166 9-2. Mini duct type ¢ Model: ARXG07KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 167 ¢ Model: ARXG12KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 168 ¢ Model: ARXG18KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 169 9-3. Slim duct type ¢ Model: ARXG07KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 170 ¢ Model: ARXG12KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 171 ¢ Model: ARXG18KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 HIGH NC-45 NC-40 NC-40 HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 QUIET NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 172 9-4. Medium static pressure duct type ¢ Model: ARXG22KMLB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET NC-20 QUIET NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
  • Page 173 ¢ Model: ARXH14KMTAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 174 ¢ Model: ARXH22KMTAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 175 9-5. Wall mounted type ¢ Models: ASEH07KMCG, ASEH07KMCG-B, ASEG07KETF, and ASEG07KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000...
  • Page 176 ¢ Models: ASEH09KMCG, ASEH09KMCG-B, ASEG09KETF, and ASEG09KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 177 ¢ Models: ASEH14KMCG, ASEH14KMCG-B, ASEG14KETF, and ASEG14KETF-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 178 ¢ Model: ASEH09KGTG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 179 ¢ Model: ASEH14KGTG  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 180 ¢ ASEH07KNCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 181 ¢ ASEH12KNCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 QUIET NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢...
  • Page 182 ¢ Model: ASEG22KMTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH NC-50 NC-50 HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 183 9-6. Ceiling type ¢ Model: ABEG18KRTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 184 9-7. Floor type ¢ Model: AGEG09KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 185 ¢ Model: AGEG14KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 HIGH NC-55 NC-55 HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 186 9-8. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 178 - 9-8. Sound level check point 9. Noise level curve...
  • Page 187 ¢ Mini duct type, Slim duct type, and Medium static pressure duct type Product Measuring duct Measuring duct (Set the static pressure as rating in this area.) Microphone Microphone Front view Side view NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
  • Page 188 ¢ Floor type Microphone Microphone ● ● Airflow Airflow - 180 - 9-8. Sound level check point 9. Noise level curve...
  • Page 189 10. Electrical characteristics Power supply Wiring spec. of connection cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Input Cross- sectional Limited wiring power area length Type Model name AUXG07KVLA 0.19 0.15 AUXG09KVLA 0.19 0.15 AUXG12KVLA 0.24 0.19 Compact cassette...
  • Page 190 Power supply Wiring spec. of connection cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Input Cross- sectional Limited wiring power area length Type Model name ABEG18KRTA 0.39 0.21 Ceiling ABEG22KRTA 0.49 0.25 AGEG09KVCA 0.19 0.15 Floor AGEG12KVCA 0.23 0.18...
  • Page 191 11. Safety devices Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse AUXG07KVLA AUXG09KVLA Activate: 100 ±15 °C Fan motor stop AUXG12KVLA Compact cassette Reset: 95 ±10 °C AUXG14KVLA AUXG18KVLA Fan motor restart AUXG22KVLA ARXG07KSLAP ARXG09KSLAP...
  • Page 192 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASEH07KMCG ASEH07KMCG-B Activate: 170 °C ASEH09KMCG Fan motor stop ASEH09KMCG-B ― ASEH12KMCG Reset: 145 °C ASEH12KMCG-B Fan motor restart ASEH14KMCG ASEH14KMCG-B ASEG07KETF ASEG07KETF-B Activate: 110 ±15 °C Fan motor speed down ASEG09KETF Reset: 110 ±15 °C...
  • Page 193 12. External input and output 12-1. Compact cassette type, Medium static pressure duct type (ARXH12–22KMTAP), and Ceiling type • Compact cassette type and Ceiling type Rotary switch CN65 CN47 (Ext. I/O PCB) (Ext. out) Terminal (Ext.in) Fig. Indoor unit PCB Fig.
  • Page 194 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 195  Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External Input and Output PCB.
  • Page 196 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22 AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 197 ¢ Setting of external input and output • Indoor unit Input Connecting point Function setting number 46 Function Operation/Stop mode 1 (Setting prohibited) Terminal Forced stop mode Operation/Stop mode 2 Output Connecting point Function setting number 60 Function Operation/Stop 01 to 08 (Setting prohibited) CN47 Error status...
  • Page 198 ¢ Details of control input function  Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Off → On Operation — Input of indoor unit Terminal On →...
  • Page 199  Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Forced stop Off → On (R.C. disabled) — Input of indoor unit Terminal Normal On → Off (R.C.
  • Page 200  Operation/Stop mode 2 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Operation Off → On (R.C. enabled) — Input of indoor unit Terminal Stop On → Off (R.C.
  • Page 201  Forced thermostat off External Input and Output External input Input signal Command Rotary switch Off → On Thermostat off External Input and 2, B, C, D Ex IN 1 Output PCB On → Off Normal operation Ex IN 1 Compressor Room temp.
  • Page 202 ¢ Details of control output function  Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Operation 60-00 — Output of indoor unit CN47 On → Off Stop Off → On Operation External Input and —...
  • Page 203  Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Off → On Fan run 60-10 — Output of indoor unit CN47 On → Off Fan stop Off → On Fan run External Input and —...
  • Page 204 12-2. Mini duct type, Slim duct type, and Medium static pressure duct type (ARXG22KMLB) Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows. • Mini duct type, Slim duct type, and Medium static pressure duct types : CN47 (Ext.
  • Page 205 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
  • Page 206 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
  • Page 207 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
  • Page 208 • When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal Stop (Remote controller On → Off disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
  • Page 209  Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
  • Page 210 12-3. Wall mounted type (KMCG, KMCG-B, KETF, KETF-B, KGTG, and KMTE) External Input and Output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Input External input External output Connector...
  • Page 211 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 212  External Input and Output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 213 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 214  External Input and Output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Combination of external input and output"...
  • Page 215 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External Input and Output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input Function Rotary...
  • Page 216  Input signal type External Input and Output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External Input and Output PCB. The width of pulse must be longer than 200 msec.
  • Page 217 ¢ Details of function  Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation External Input and 46-00...
  • Page 218 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Forced stop External Input and 46-02 CN313 Output PCB On →...
  • Page 219 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting Input and Output PCB Off → On Operation Stop External Input and 46-03 CN313 (Remote Output PCB On →...
  • Page 220 • Forced thermostat off function Rotary SW on Input Function setting / External Input External input Command signal and Output PCB Thermostat 60-00 Off → On External Input and 60-09 CN313 Output PCB Normal On → Off 60-10 operation Input Compressor Room temp.
  • Page 221  Control output function • Operation/Stop status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB 60-00 / 1 Off → On Operation Output of indoor unit CN47 60-00 / 2 On → Off Stop 60-00 / 1 Off →...
  • Page 222 • Indoor unit fan operation status Rotary SW on Output Function setting / External Input External output Command signal and Output PCB Off → On Fan run 60-10 / C Output of indoor unit CN47 On → Off Fan stop 60-00 / 2 Off →...
  • Page 223 12-4. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
  • Page 224 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
  • Page 225 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
  • Page 226 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
  • Page 227 • When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation Stop — CN14 (Remote On → Off controller disabled) 46-03 Input of indoor unit Off →...
  • Page 228  Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 229 • Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
  • Page 230 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 222 - 12-4.
  • Page 231 • Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 232 13. Group connection NOTE: Group control cannot be used together with WLAN Adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 233 14. Remote controller 14-1. Wireless remote controller (AR-REW4E and AR-REJ1E) ¢ Overview AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button...
  • Page 234 AR-REJ1E Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button TIMER CANCEL button CLOCK ADJUST button NOTE: Functions may differ by type of the indoor unit.
  • Page 235 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 236 14-2. Wireless remote controller (AR-REW3E) ¢ Overview Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 237 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 238 14-3. Wireless remote controller (AR-REW2E) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 239 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 125 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 240 14-4. Wireless remote controller (AR-REM7E) ¢ Overview Signal transmitter MODE button FAN button 10 °C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 241 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 242 14-5. Wireless remote controller (AR-RMB1E and AR-RMB1E-B) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button...
  • Page 243 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 244 14-6. Wireless remote controller (UTY-LNTY: Optional part) and IR receiver kit with Wireless remote controller (UTY-LBTYM or UTY-LBTYH: Optional part) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button...
  • Page 245 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 246  IR receiver (UTY-LBTYM) Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight  IR receiver (UTY-LBTYH) Unit: mm 23.3 48.6 Ø 5.0 (Hole) Ø...
  • Page 247 14-7. Wireless remote controller (AR-RPF4E) ¢ Overview a MODE button • Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT). • Starts/ends the remote controller custom code (max. 4 types) change. b FAN SPEED button • Press the FAN SPEED button while the air conditioner is operating, to control fan speed.
  • Page 248 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 162 × 45 × 18 Weight 65.5 (without batteries)  Holder Unit: mm Top view Ø 3.9 (Hole) Hole 26.6 49.3 Front view Side view Size (H ×...
  • Page 249 14-8. Wired remote controller (UTY-RNNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 250 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 251 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 252 14-9. Wired Remote Controller (UTY-RVRY [Optional part]) • Easy finger touch operation with LCD panel. • Screen with anti-fingerprint coating • Various information display (Room temp., Operation mode, Set temp. Fan speed, Timer) • Control up to 16 indoor units •...
  • Page 253 Temperature setting screen a Page indicator Shows the oder of pages and displayed page. b Operation On/Off button Tap to start operation or stop the air conditioner. c Bluetooth icon Displays when Bluetooth is enabled. d Information area The displayed contents differ depending on the screen and settings.
  • Page 254 ¢ System diagrams • Multiple remote control Up to 3 remote controllers can be used to operate the indoor units. I.U. I.U. I.U. I.U. – Remote controller • A, B: UTY-RVRY • C, D: Other than UTY-RVRY (2-wire type only) –...
  • Page 255 • Group control With remote controllers, up to 16 indoor units can be simultaneously operated. I.U. I.U. I.U. I.U. – Remote controller • A, F: UTY-RVRY – Remote controller cable • A, F ≤ 70 ft, A + B + C + D + E + F ≤ 70 m •...
  • Page 256 ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit When there is When there is a functional a functional grounding grounding Remote controller Remote controller Remote controller Group control: Indoor units When there is a functional grounding Remote controller - 248 - 14-9.
  • Page 257 ¢ Dimensions Unit: mm Hole: 8.2 × 20.5 Hole: 9 × 4.5 33.5 Hole: 6 × 4.5 Hole: 12.5 × 4.5 ¢ Installation space • This product cannot be installed in a wall. • Even when you install a remote controller to one of a switch box and the surface of a wall, secure the space shown in following figure.
  • Page 258 ¢ Installation For details of installation, refer to the INSTALLATION MANUAL for this product. • Connector removal Open the front case and remove the connector of the remote controller cable from the connector of the PCB on the front case (back side). Fron case (back side) Rear case Connector...
  • Page 259 • Rear case installation – When attaching to switch box: Seal the wiring hole of the remote controller cable with putty. Trap (remote controller cable) Connector Putty Self-tapping screw Rear case Trap – When attaching to the wall directly: Wall Seal the wiring hole of the remote controller cable with putty.
  • Page 260 • Remote controller cable connection – Fasten the outside covering of the connection cable with the cable tie. Cable tie – Connect the connector of the remote controller cable to the connector of the PCB on the front case (back side). Clamp Rear case Front case...
  • Page 261 ¢ Specifications Input voltage DC 12 Power consumption Max. 1.0 Display 4-inch TFT LCD (480 × 480 pixels) with touch screen Usage temperature range °C 0 to 40 Usage humidity range 20 to 90 (no condensation) Storage temperature range °C -10 to 60 Storage humidity range 20 to 90 (no condensation)
  • Page 262 14-10. Wired remote controller (UTY-RLRY: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
  • Page 263 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 264 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
  • Page 265 14-11. Wired remote controller (UTY-RVNYM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 257 - 14-11.
  • Page 266 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 267 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 259 - 14-11.
  • Page 268 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 269 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 270 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 271 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
  • Page 272 14-12. Wired remote controller (UTY-RNRYZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
  • Page 273 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 274 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRYZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
  • Page 275 14-13. Wired remote controller (UTY-RCRYZ1: Optional part) ¢ Overview a Display panel b MODE button c Menu button buttons (Set temperature buttons) e FAN button f On/off button g Wireless remote controller signal receiving section - 267 - 14-13. Wired remote controller (UTY-RCRYZ1: Optional part) 14.
  • Page 276 ¢ System diagrams • Single remote control I.U. Remote controller cable A ≤ 500 m ¢ Electrical wiring Indoor unit Remote controller - 268 - 14-13. Wired remote controller (UTY-RCRYZ1: Optional part) 14. Remote controller...
  • Page 277 ¢ Specifications Unit: mm Hole × 2 (for M4 screws) Size (H × W × D) 86 × 86 × 32 Weight  Wiring specifications Cable size Wire type Remarks Remote controller 0.33 to 1.25 mm Non polar 2-core Use sheathed twist pair cable.* cable (22 to 16 AWG) *: Use shielded cable (locally purchased) in accordance with the regional cable standard.
  • Page 278 • Pattern B 1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown below. 20 mm Remote controller cable (Non-polar) 2.
  • Page 279 14-14. Simple remote controller (UTY-RSNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 280 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 281 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 282 14-15. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 283 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 284 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
  • Page 285 15. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 15-1. Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 286 ¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
  • Page 287 15-2. Medium static pressure duct type (ARXH12–22KMTAP) By using some components on the PCB, you can change the function settings. Related components on the PCB and the applicable settings Component Setting content Drainage function setting Setting change prohibited DIP switch101 Fan delay setting Setting change prohibited ...
  • Page 288 15-3. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 289 ¢ AR-REW3E (for Wall mounted type KGTG), AR-REW4E (for Wall mounted type KETF[-B]), AR-REW2E (for Wall mounted type KMTE), and AR-REM7E (for Floor type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
  • Page 290  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 291 Press the MODE button once to transmit the function mode information. Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 292  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 293  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 294 ¢ AR-RMB1E(-B) (for Wall mounted type KMCG and KMCG-B)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details. 10°C HEAT button POWERFUL button Changes the displayed digits.
  • Page 295  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and SET TEMP. buttons, press the RESET button. POWERFUL SET TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 296 Press the MODE button once to transmit the function mode information. 2 short beeps Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 297  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 298  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 299 ¢ UTY-LNTY (for Compact cassette type) or AR-REJ1E (included in UTY-LBTYM for Duct type, UTY-LBTYH for Ceiling type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details.
  • Page 300  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the ECONOMY and SET TEMP. buttons, press the RESET button. ECONOMY SET TEMP. ( RESET Function setting mode display - 292 - 15-3.
  • Page 301 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
  • Page 302 Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 303  Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed.  Resetting the power after setting up all indoor units Important: •...
  • Page 304  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 305 ¢ AR-RPF4E (for Wall mounted type KNCA) The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment. Before connecting the power supply of the indoor unit, reconfirm following items: •...
  • Page 306 STEP 2: Selecting the function number and setting value 1. Press the TEMP./SELECT ( ) buttons to select the function Function number number. To switch between the left and right digits, press the MODE button. 2. Press the FAN SPEED button to proceed the setting value. To re- turn the function number selection, press the FAN SPEED button again.
  • Page 307  Custom code setting on AR-RPF4E To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 308 15-4. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 309 ¢ UTY-RNNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 310 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 311 ¢ UTY-RLRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 312 Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
  • Page 313 ¢ UTY-RVNYM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 314 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 315 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 316 ¢ UTY-RNRYZ*  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 317 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 318 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 319 ¢ UTY-RVRY  Function setting procedure Tap the menu as shown below. Enter the Admin password. Enter the Installer password. Tap “Address” on the Function Setting screen. Pull-down window of indoor unit address is displayed. Select the address of the indoor unit whose function number is to be set.
  • Page 320 Pull-down window of Function No. is displayed. Set the Function No to be set. Tap “Setting No.” on the Function Setting screen. Pull-down window of “Setting No.” is displayed. Set the Setting No. Tap “Set” on the verification screen. to return to the Initial Setting screen. - 312 - 15-4.
  • Page 321 15-5. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 322 ¢ UTY-RSNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 323 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 324  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 325 ¢ UTY-RSRY/UTY-RHRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 326 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 327 Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
  • Page 328 15-6. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Medium static pressure Functio Compact...
  • Page 329 Wall mounted Functio Functions KETF n no. KMCG (-B) KGTG KNCA KMTE (-B) Filter sign ● ● ● ● ● Ceiling height — — — — — Static pressure — — — — — Outlet directions — — — — —...
  • Page 330 2) Ceiling height (for Compact cassette type and Ceiling type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 4. "Dimensions"...
  • Page 331 5) Static pressure (for Mini duct type, Slim duct type, and Medium static pressure duct type (ARXH12–22KMTAP)) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa...
  • Page 332 6) Horizontal louver direction switching for dew condensation prevention (for Ceiling type only) Automatically switches the position of the horizontal louver if the airflow direction is set at lower than the dew condensation limit position in cooling or drying operation. Select suitable adjustment position according to the customer’s preference.
  • Page 333 8) Room temperature control for wired remote controller sensor (for other than Floor type and KNCA) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”.
  • Page 334 11) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 12) External input control “Operation/Stop” mode or “Forced stop” mode can be selected. Function number Setting value Setting description...
  • Page 335 15) Switching functions for external output terminal (For other than KETA[-B] and KNCA models in Wall-mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
  • Page 336 15-7. Wired remote controller (UTY-RNNYM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 337  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 338 15-8. Wired remote controller (UTY-RVNYM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 339 15-9. Wired remote controller (UTY-RLRY) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 340 15-11. Simple remote controller (UTY-RSNYM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 341 16. Accessories 16-1. Compact cassette type ¢ Models: AUXG07–22KVLA Part name Exterior Part name Exterior Operation manual Drain hose insulation Operation manual Hose band (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Template (Carton top) (small) M10 nut A Cable tie (with flange) M10 nut B...
  • Page 342 16-2. Mini duct type ¢ Models: ARXG07–14KSLAP Part name Exterior Part name Exterior Operation manual Drain hose Operation manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small)
  • Page 343 ¢ Model: ARXG18KSLAP Part name Exterior Part name Exterior Operation manual Drain hose Operation manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small) Insulation Filter (large)
  • Page 344 16-3. Slim duct type ¢ Models: ARXG07–18KLLAP Part name Exterior Part name Exterior Operation manual Cable tie (Large) Installation manual Cable tie (Small) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (Large) Coupler heat insulation Filter (Small) (Small) (For 7/9/12/14 models)
  • Page 345 16-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Part name Exterior Part name Exterior Operation manual Cable tie (medium) Operation manual Cable tie (small) (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Hanger (small) M10 nut A Drain hose insulation (with flange) M10 nut B...
  • Page 346 16-5. Wall mounted type ¢ Models:ASEH07–14KMCG, ASEH07–14KMCG-B, and ASEH07– 14KGTG Part name Exterior Part name Exterior Operation manual Cloth tape Self-tapping screw Installation manual (large) Self-tapping screw Remote controller (small) Battery Wall hook bracket Remote controller Filter holder holder Installation spacer Air cleaning filters Operation manual (CD-ROM)
  • Page 347 ¢ Models: ASEG07–14KETF and ASEG07–14KETF-B Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder Template (for pipe cover cutting) ¢...
  • Page 348 ¢ Models: ASEG18–24KMTE Part name Exterior Part name Exterior Operation manual Cloth tape Operation manual Self-tapping screw (CD-ROM) (large) Self-tapping screw Installation manual (small) Remote controller Wall hook bracket Remote controller Filter holder holder Battery Air cleaning filters - 340 - 16-5.
  • Page 349 16-6. Ceiling type ¢ Models: ABEG18–22KRTA Part name Exterior Part name Exterior Operation manual Insulation Operation manual Drain hose (CD-ROM) Installation manual Hose band Template Cable tie (large) M10 nut A Cable tie (small) (with flange) M10 nut B Remote controller cable (with spring lock hole cap washer)
  • Page 350 16-7. Floor type ¢ Models: AGEG09–14KVCA Part name Exterior Part name Exterior Operation manual (CD- Operation manual ROM) Installation manual Cloth tape Self-tapping screws Wall hook bracket (large) Self-tapping screws Remote controller (small) Battery Air cleaning filters Remote controller holder - 342 - 16-7.
  • Page 351 17. Optional parts 17-1. Controllers ¢ Lineup Type Indoor unit type Wireless Remote Controller AR-REM7E AR-REW2E AR-REW3E AR-REW4E Compact cassette — — — — Mini duct — — — — Slim duct — — — — Medium KMLB — — —...
  • Page 352 Type Indoor unit type Wired Remote Controller UTY-RNNYM UTY-RVNYM UTY-RVRY UTY-RLRY Compact cassette ◌ ◌ ◌ ◌ Mini duct ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ Medium KMLB ◌ ◌ ◌ ◌ static pressure KMTAP — — ◌...
  • Page 353 ●: Accessory, ◌: Optional, —: Not applicable • *1: Optional Communication Kit (UTY-TWRXZ2) is necessary for the installation. • *2: Optional Communication Kit (UTY-TWRXZ3) is necessary for the installation. - 345 - 17-1. Controllers 17. Optional parts...
  • Page 354 ¢ Parts Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design Wired Remote that uniquely transforms itself to blend Controller UTY-RVRY with any interior. (Touch Panel) Wire type: Non-polar 2-wire Easy finger touch operation with LCD panel.
  • Page 355 Exterior Part name Model name Summary Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and Simple Remote temperature setting. UTY-RHRY Controller Wire type: Non-polar 2-wire Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation Simple Remote UTY-RSNYM...
  • Page 356 17-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-UFYF-W ¢ Part Exterior Part name Model name Summary This cassette grille can be installed Cassette Grille UTG-UFYF-W appropriately on the grid type ceiling common in the office. - 348 - 17-2.
  • Page 357 17-3. Others ¢ Lineup Type Air Outlet Shutter Insulation Kit for Fresh Air Intake Half Concealed Indoor unit type Plate High Humidity UTR-YDZB UTZ-KXGC UTZ-VXAA UTR-STA Compact cassette ◌ ◌ ◌ — Mini duct — — — — Slim duct —...
  • Page 358 Type External Input and Output Indoor unit type External Connect Kit UTY-XWZX UTY-XWZXZ5 UTY-XWZXZG UTY-XCSXZ2 UTY-XCSX Compact cassette — — ◌ — ◌ Mini duct — — ◌ — — Slim duct — — ◌ — — Medium KMLB — —...
  • Page 359 Type Indoor unit type Communication Kit Air Cleaning Filter UTY-TWRXZ2 UTY-TWRXZ3 UTR-FA16-5 UTD-HFNB UTD-HFNC Compact cassette — — — — — Mini duct — — — — — Slim duct — — — — — Medium KMLB — — — —...
  • Page 360 • *1: Optional Communication Kit (UTY-TWRXZ2) is necessary for the installation. • *2: Optional Communication Kit (UTY-TWRXZ3) is necessary for the installation. • *3: For details of wireless LAN control, refer to “Design & Technical manual” or “Setting manual” of WLAN control system.
  • Page 361 ¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote Sensor temperature of arbitrary place in the UTY-XSZX Unit room. Thermo-sensor for sensing the Remote Sensor temperature of arbitrary place in the UTY-XSZXZ* Unit room. Width: 683 mm Auto Louver UTD-GXTA-W Grille Kit...
  • Page 362 Exterior Part name Model name Summary Air Cleaning Filter can be mounted to Air Cleaning UTR-FA16-5 the indoor unit. Filter (For antibacterial) Air Cleaning Air Cleaning Filter can be mounted to UTD-HFNB Filter the indoor unit. Air Cleaning Air Cleaning Filter can be mounted to UTD-HFNC Filter the indoor unit.
  • Page 363 Exterior Part name Model name Summary External Input For installing the External input and and Output PCB UTZ-GXDA output PCB. External Input For installing the External input and and Output PCB UTZ-GXEA output PCB. For Ceiling type Communication Use to connect Non-polar 2-core wired UTY-TWRXZ3 remote controller.
  • Page 364 Exterior Part name Model name Summary This converter is required when Network connecting single split system to VRF UTY-VTGX Converter network system. Network This converter is required when Converter connecting single split system to VRF UTY-VTGXV (AC power network system. supply) Air conditioner switching can be External Switch...
  • Page 365 18. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 18-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 366 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 367 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 18-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 368 - 360 - 18-2. Points to remember when installing 18. Indoor unit installation precautions...
  • Page 369 Part 2. OUTDOOR UNIT (4 UNITS TYPE) MULTI-SPLIT TYPE: AOEG30KBTA4...
  • Page 370 1. Specifications Type Inverter heat pump Model name AOEG30KBTA4 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ×4 Rated Btu/h 27,300 Cooling 2.4—10.1 Min.—Max. Btu/h 8,200—34,500 Capacity Rated Btu/h 32,800 Heating 3.0—11.2 Min.—Max.
  • Page 371 Specifications for ErP Lot10 Model name AOEG30KBTA4 Cooling Energy efficiency class Heating (Average) Cooling 8.0 (35 °C) Pdesign Heating (Average) 6.5 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 1,978 Cooling Sound power level HIGH dB (A) Heating...
  • Page 372 2. Dimensions 2-1. Model: AOEG30KBTA4 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 364 - 2-1. Model: AOEG30KBTA4 2. Dimensions...
  • Page 373 3. Installation space 3-1. Model: AOEG30KBTA4 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 374  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 375  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 376 4. Refrigerant circuit 4-1. Model: AOEG30KBTA4 Pressure switch CONDENSER - 368 - 4-1. Model: AOEG30KBTA4 4. Refrigerant circuit...
  • Page 377 5. Wiring diagram 5-1. Model: AOEG30KBTA4 - 369 - 5-1. Model: AOEG30KBTA4 5. Wiring diagram...
  • Page 378 6. Capacity table 6-1. Combinations ¢ Model: AOEG30KBTA4  Cooling Indoor unit combination (Wall-mounted KG/KM type only) Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min.
  • Page 379 Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.60 1.60 2.06 2.74 8.00 10.10...
  • Page 380 Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.65 2.12 4.24 —...
  • Page 381 Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 0.87 1.57 2.43 3.13 8.00 10.1...
  • Page 382  Heating Indoor unit combination (Wall-mounted KG/KM type only) Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total...
  • Page 383 Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class 1.60 2.06 2.74 3.20 9.60...
  • Page 384 Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SEER Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class — 1.56 4.02 4.02 —...
  • Page 385 Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SEER Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class 2.10 2.10 2.70 2.70 9.60...
  • Page 386 6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOEG30KBTA4 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 387 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 388 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 389 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.71 1.74 1.76 1.78 1.80 10.2 1.81...
  • Page 390  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 391 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.88 5.37 3.28 5.66 3.78 6.06 4.24 6.48 4.64 6.68 5.32 -5.0 4.75...
  • Page 392  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 393 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68 5.47 -5.0 4.75...
  • Page 394  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 395 Model: ARXG18KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68 5.47 -5.0 4.75...
  • Page 396  Medium static pressure duct type (ARXH12–22KMTAP) Model: ARXH12KMTAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 3.37 2.27 3.81 2.59 4.02 2.99 4.30...
  • Page 397  Wall mounted type Model: ASEH07KMCG, ASEH07KMCG-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67...
  • Page 398 Model: ASEG07KETF, ASEG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 399 Model: ASEH07KGTG Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 400 Model: ASEH05KNCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.41 0.79 1.59 0.90 1.68 1.04 1.80 1.17 1.92 1.28 1.98 1.47 -5.0 1.41...
  • Page 401 Model: ASEG18KMTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 3.21 5.37 3.65 5.66 4.21 6.06 4.73 6.48 5.17 6.68 5.92 -5.0 4.75...
  • Page 402  Ceiling type Model: ABEG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68...
  • Page 403  Floor type Model: AGEG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 404 6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOEG30KBTA4 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96...
  • Page 405 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 406 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 407 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 408  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 409 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.66 4.55 4.44 4.33 4.22 -10.0 -11.0 5.80 5.67 5.53 5.39 5.25 -5.0 -7.0 6.91 6.74 6.58 6.41 6.25 -2.0 8.12 7.93 7.73 7.54 7.35 8.93 8.71...
  • Page 410  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 411 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 412  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 413 Model: ARXG18KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 414  Medium static pressure duct type (ARXH12–22KMTAP) Model: ARXH12KMTAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.63 2.57 2.51 2.44 2.38 -10.0 -11.0 3.28 3.20 3.12 3.04 2.97 -5.0 -7.0 3.90 3.81 3.71 3.62 3.53 -2.0...
  • Page 415  Wall mounted type Model: ASEH07KMCG, ASEH07KMCG-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61...
  • Page 416 Model: ASEG07KETF, ASEG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94...
  • Page 417 Model: ASEH07KGTG Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 418 Model: ASEH05KNCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.15 1.12 1.10 1.07 1.04 -10.0 -11.0 1.43 1.40 1.37 1.33 1.30 -5.0 -7.0 1.71 1.67 1.62 1.58 1.54 -2.0 2.01 1.96 1.91 1.86 1.82 2.21 2.15...
  • Page 419 Model: ASEG18KMTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 420  Ceiling type Model: ABEG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96...
  • Page 421  Floor type Model: AGEG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.97 1.93 1.88 1.83 1.79 -10.0 -11.0 2.46 2.40 2.34 2.28 2.22 -5.0 -7.0 2.92 2.86 2.79 2.72 2.65 -2.0 3.44 3.36 3.28 3.19...
  • Page 422 7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOEG30KBTA4 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 423 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.992 0.985 0.971 0.957 0.943 1.003 0.996 0.989 0.975 0.961 0.947 1.007 1.000 0.993...
  • Page 424 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.992 0.982 0.970 0.952 0.937 0.999 0.996 0.986 0.974 0.956 0.941 1.005 1.000 0.990...
  • Page 425 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.992 0.994 0.994 0.984 0.968 0.993 0.996 0.998 0.998 0.988 0.972 0.997 1.000 1.002...
  • Page 426 8. Additional charge calculation 8-1. Model: AOEG30KBTA4 Refrigerant type Refrigerant amount 2,200 Refrigerant charge Total pipe length 40 or less 70 (Max.) 20 g/m Additional charge amount - 418 - 8-1. Model: AOEG30KBTA4 8. Additional charge calculation...
  • Page 427 9. Airflow 9-1. Model: AOEG30KBTA4  Cooling 2,400 1,413  Heating 2,950 1,736 - 419 - 9-1. Model: AOEG30KBTA4 9. Airflow...
  • Page 428 10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOEG30KBTA4  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 429 11. Electrical characteristics Model name AOEG30KBTA4 Voltage 230 ~ Power supply Frequency 18.5 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 430 12. Safety devices Model Type of Protection form protection AOEG30KBTA4 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10°C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10°C Reset Fan motor restart 110°C...
  • Page 431 13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 432 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 433 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 434 13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 435 14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 436 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 437 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 438 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 439 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 440 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 441 14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 442 Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 443 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 444 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 445 14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant pipe. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. ¢...
  • Page 446 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 447 15. Accessories 15-1. Model: AOEG30KBTA4 Part name Exterior Part name Exterior Adapter K Installation manual 12.70 mm (1/2 in) to 9.52 mm (3/8 in) Drain pipe - 439 - 15-1. Model: AOEG30KBTA4 15. Accessories...
  • Page 448 16. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 16-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 449 Part 3. OUTDOOR UNIT (5 UNITS TYPE) MULTI-SPLIT TYPE: AOEG36KBTA5...
  • Page 450 1. Specifications Type Inverter heat pump Model name AOEG36KBTA5 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ×5 Rated Btu/h 32,400 Cooling 3.0—11.0 Min.—Max. Btu/h 10,200—37,500 Capacity 10.6 Rated Btu/h 36,200 Heating 3.5—12.0 Min.—Max.
  • Page 451 Specifications for ErP Lot10 Model name AOEG36KBTA5 Cooling Energy efficiency class Heating (Average) Cooling 9.5 (35 °C) Pdesign Heating (Average) 7.0 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 2,130 Cooling Sound power level HIGH dB (A) Heating...
  • Page 452 2. Dimensions 2-1. Model: AOEG36KBTA5 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 444 - 2-1. Model: AOEG36KBTA5 2. Dimensions...
  • Page 453 3. Installation space 3-1. Model: AOEG36KBTA5 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 454  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 455  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 456 4. Refrigerant circuit 4-1. Model: AOEG36KBTA5 Pressure switch CONDENSER - 448 - 4-1. Model: AOEG36KBTA5 4. Refrigerant circuit...
  • Page 457 5. Wiring diagram 5-1. Model: AOEG36KBTA5 - 449 - 5-1. Model: AOEG36KBTA5 5. Wiring diagram...
  • Page 458 6. Capacity table 6-1. Combinations ¢ Model: AOEG36KBTA5  Cooling Indoor unit combination (Wall-mounted KG/KM type only) Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min.
  • Page 459 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 2.00 2.00 2.00 2.50 —...
  • Page 460 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.51 1.51 1.94 1.94 2.60 9.50...
  • Page 461 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — — 1.90 3.80 3.80 —...
  • Page 462 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.08 1.51 3.02 3.89 —...
  • Page 463 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.64 1.64 2.19 4.02 —...
  • Page 464 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.19 1.66 1.66 1.66 3.33 9.50...
  • Page 465 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.61 1.61 1.61 2.15 2.51 9.50...
  • Page 466  Heating Indoor unit combination (Wall-mounted KG/KM type only) Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max.
  • Page 467 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 1.86 1.86 3.17 3.71 —...
  • Page 468 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class 1.54 1.99 1.99 1.99 3.09 10.60...
  • Page 469 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — — 2.27 2.27 6.06 —...
  • Page 470 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 1.39 2.51 3.35 3.35 —...
  • Page 471 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 2.54 2.54 2.54 2.97 —...
  • Page 472 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class 0.97 1.36 1.36 2.33 3.49 9.50...
  • Page 473 NOTES: • 5: 5,000 Btu/h, 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h, 18: 18,000 Btu/h, 22: 22,000 Btu/h, 24: 24,000 Btu/h • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V –...
  • Page 474 6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOEG36KBTA5 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 475 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.39 2.43 10.3 2.45 11.0 2.48 11.8...
  • Page 476 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.39 2.43 10.3 2.45 11.0 2.48 11.8...
  • Page 477 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.39 2.43 10.3 2.45 11.0 2.48 11.8...
  • Page 478  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 479 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 2.94 5.48 3.35 5.78 3.86 6.19 4.33 6.62 4.74 6.82 5.43 -5.0 4.85...
  • Page 480  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 481 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82 5.58 -5.0 4.85...
  • Page 482  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 483 Model: ARXG18KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.80 2.99 5.42 3.41 5.72 3.92 6.12 4.41 6.54 4.82 6.74 5.52 -5.0 4.80...
  • Page 484  Medium static pressure duct type (ARXH12–22KMTAP) Model: ARXH12KMTAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 3.37 2.27 3.81 2.59 4.02 2.99 4.30...
  • Page 485  Wall mounted type Model: ASEH07KMCG, ASEH07KMCG-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67...
  • Page 486 Model: ASEG07KETF, ASEG07KETF-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 487 Model: ASEH07KGTG Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 488 Model: ASEH05KNCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.41 0.79 1.59 0.90 1.68 1.04 1.80 1.17 1.92 1.28 1.98 1.47 -5.0 1.41...
  • Page 489 Model: ASEG18KMTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.27 5.48 3.73 5.78 4.30 6.19 4.83 6.62 5.28 6.82 6.05 -5.0 4.85...
  • Page 490  Ceiling type Model: ABEG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82...
  • Page 491  Floor type Model: AGEG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 492 6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOEG36KBTA5 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88...
  • Page 493 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 494 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 495 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.61 2.66 2.72 2.77 2.83 -10.0 -11.0 2.95 3.01 3.07 3.13 3.20 -5.0 -7.0 2.66 2.71 2.77 2.82 2.88 -2.0...
  • Page 496  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 497 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 5.55 5.41 5.28 5.15 5.02 -10.0 -11.0 6.44 6.29 6.13 5.98 5.83 -5.0 -7.0 6.80 6.64 6.48 6.31 6.15 -2.0 7.78 7.60 7.41 7.23 7.04 8.95 8.73...
  • Page 498  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 499 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 500  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 501 Model: ARXG18KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 502  Medium static pressure duct type (ARXH12–22KMTAP) Model: ARXH12KMTAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.12 3.05 2.98 2.90 2.83 -10.0 -11.0 3.63 3.54 3.46 3.37 3.28 -5.0 -7.0 3.83 3.74 3.65 3.56 3.47 -2.0...
  • Page 503  Wall mounted type Model: ASEH07KMCG, ASEH07KMCG-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50...
  • Page 504 Model: ASEG07KETF, ASEG07KETF-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94...
  • Page 505 Model: ASEH07KGTG Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 506 Model: ASEH05KNCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.37 1.33 1.30 1.27 1.24 -10.0 -11.0 1.59 1.55 1.51 1.47 1.44 -5.0 -7.0 1.68 1.64 1.60 1.56 1.52 -2.0 1.92 1.87 1.83 1.78 1.74 2.21 2.15...
  • Page 507 Model: ASEG18KMTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 508  Ceiling type Model: ABEG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73...
  • Page 509  Floor type Model: AGEG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.34 2.29 2.23 2.18 2.12 -10.0 -11.0 2.72 2.66 2.59 2.53 2.46 -5.0 -7.0 2.87 2.80 2.74 2.67 2.60 -2.0 3.29 3.21 3.13 3.05...
  • Page 510 7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOEG36KBTA5 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 511 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 Indoor unit is higher — — 0.977 0.963 0.950 0.936 than outdoor unit * — 0.992 0.985 0.971 0.957 0.943 0.996 0.996 0.989 0.975 0.961 0.947 1.000 1.000 0.993...
  • Page 512 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 Indoor unit is higher — — 0.974 0.962 0.945 0.930 than outdoor unit * — 0.992 0.982 0.970 0.952 0.937 0.996 0.996 0.986 0.974 0.956 0.941 1.000 1.000 0.990...
  • Page 513 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 Indoor unit is higher — — 0.986 0.986 0.977 0.961 than outdoor unit * — 0.992 0.994 0.994 0.984 0.968 0.996 0.996 0.998 0.998 0.988 0.972 1.000 1.000 1.002...
  • Page 514 8. Additional charge calculation 8-1. Model: AOEG36KBTA5 Refrigerant type Refrigerant amount 2,500 Refrigerant charge Total pipe length 40 or less 75 (Max.) 20 g/m Additional charge amount - 506 - 8-1. Model: AOEG36KBTA5 8. Additional charge calculation...
  • Page 515 9. Airflow 9-1. Model: AOEG36KBTA5  Cooling 2,450 1,501  Heating 2,900 1,766 - 507 - 9-1. Model: AOEG36KBTA5 9. Airflow...
  • Page 516 10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOEG36KBTA5  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 517 11. Electrical characteristics Model name AOEG36KBTA5 Voltage 230 ~ Power supply Frequency 20.0 Maximum operating current * Starting current 11.1 Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 518 12. Safety devices Model Type of Protection form protection AOEG36KBTA5 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
  • Page 519 13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 520 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 521 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 522 13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 523 14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 524 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 525 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 526 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 527 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 528 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 529 14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 530 Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 531 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 532 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 533 14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant pipe. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. ¢...
  • Page 534 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 535 15. Accessories 15-1. Model: AOEG36KBTA5 Part name Exterior Part name Exterior Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Adapter H: mm (in) Drain pipe 9.52 (3/8) to 12.70 (1/2) Cable tie (small) - 527 - 15-1. Model: AOEG36KBTA5 15.
  • Page 536 16. Optional parts Exterior Part name Model name Summary Set temperatures on timers to best meet individuals’ needs. Includes a large backlit LCD and 4-way navigation pad. Remote controller cable: 0.33 mm² (22AWG) NOTES: • The remote controller cable supplied with this controller is for indoor use.
  • Page 537 17. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.