Summary of Contents for Siemens SIMATIC Industrial Flat Panel IFP1500
Page 1
___________________ Industrial Flat Panel IFP1500, IFP1900, Preface IFP2200 ___________________ Overview ___________________ Safety information SIMATIC ___________________ Installing and connecting the device Industrial Monitors ___________________ Industrial Flat Panel IFP1500, Commissioning the device IFP1900, IFP2200 ___________________ Operating the device Operating Instructions ___________________ Maintaining and servicing...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
General knowledge in the field automation control engineering is recommended. Scope of the operating instructions These operating instructions apply to all IFP1500, IFP1900 and IFP2200 Industrial Flat Panels with the order numbers 6AV7863-..Scope of this documentation The SIMATIC Industrial Flat Panel is supplied with the following documents: ●...
Page 4
Within some of the figures, one device is used to represent all Industrial Flat Panels. History The following earlier release versions of these operating instructions have been published: Edition Comment 09/2012 First Edition 06/2014 Description of devices with capacitive multi-touch screen Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Product description ........................9 Scope of delivery.......................... 11 Construction of the devices ......................12 1.3.1 IFP1900, IFP2200 Multitouch ...................... 12 1.3.2 IFP1500, IFP1900, IFP2200 Touch ..................... 14 1.3.3 IFP1500 Touch/Key ........................15 1.3.4 Interfaces ............................. 16 1.3.4.1 Standard versions ........................16 1.3.4.2...
Page 6
ESD guideline ..........................74 7.2.2 Electromagnetic compatibility...................... 76 Dimension drawings ........................77 7.3.1 Dimension drawing of the IFP1500 Monitor and Touch .............. 77 7.3.2 Dimension drawing of the IFP1900 Multitouch ................78 7.3.3 Dimension drawing of the IFP1900 Monitor and Touch .............. 79 7.3.4...
Page 7
USB interface, Type B ......................... 94 7.6.5 USB hub, Type A ......................... 94 Technical Support ..........................95 Service and support ........................95 List of abbreviations ..........................97 Glossary ............................... 99 Index..............................101 Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
SIMATIC Industrial Flat Panels are LCD monitors suitable for industrial use with a brilliant TFT display which can be connected to all SIMATIC IPCs as well as almost all generally available PCs. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 10
● Up to 30 m away from PC possible via DVI ● Power supply (with USB) 24 V DC and 100-240 V AC ● 2 USB ports ● Also available as touch/key version with front USB interface Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
2 m in length, for commissioning USB connecting cable, 2 m Power supply cable 230 V AC "Documentation and Drivers" CD Not with standard display device (monitor) Only for devices with AC power supply Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
This section describes the design of the multi-touch devices, using the IFP1900 Multitouch as an example. Front view and side view ① Display/touch screen ② Recesses for mounting clamps ③ Mounting seal Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 13
Overview 1.3 Construction of the devices Rear view ① Rating plate ② Interface name ③ Equipotential bonding ④ Retaining elements for strain relief of the connecting cables Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Overview 1.3 Construction of the devices 1.3.2 IFP1500, IFP1900, IFP2200 Touch This section describes the design of the monitor and touch devices, using the IFP1500 Touch as an example. Front view and side view ① Display/touch screen ② Recesses for mounting clamps ③...
Overview 1.3 Construction of the devices 1.3.3 IFP1500 Touch/Key Front view ① Display and function keys with LED ② Alphanumeric keys ③ Control keys ④ Cursor keys ⑤ USB port Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
X61/X62 USB Type A supply ② ⑥ X80 connector for 24 V DC power supply X63 USB link interface ③ ⑦ X71 DVI-D interface X60 USB Type B ④ X70 DisplayPort interface Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
6AV7860-1EX23-0AA1 Touch/Key Extended version Name Order number Film for labeling the function keys Print templates for the slide-in labels 6AV7672-0DA00-0AA0 (slide-in labels) are available on the "Documentation and Drivers" CD/DVD. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Failure to follow these precautions is a breach of the Machinery Directive. Such failure may also cause personal injury and damage depending on the machine operated. The machine in which the HMI device is to be operated must conform to Directive 2006/42/EC. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 20
• Remove the sources of radiation from the vicinity of the device. • Switch off radiating devices. • Reduce the radio output of radiating devices. • Observe the information on electromagnetic compatibility (Page 87). Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 21
2.1 General safety instructions Industrial Security Siemens offers products and solutions with Industrial Security functions that support the safe operation of equipment, solutions, machines, devices and/or networks. They are important components in a comprehensive Industrial Security concept. As a result the products and solutions from Siemens are constantly evolving.
Suitable measures for achieving the degree of noise suppression for Limit Class B include, for example: ● Installation of the device in grounded control cabinets ● Use of filters in electrical supply lines Individual acceptance is required. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 23
(e.g. a clean air supply). • Only use suitable detergents. Only use suitable detergents. Read the information about Chemical resistance of the HMI devices and industrial PCs (http://support.automation.siemens.com/WW/view/en/39718396) on the Internet. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 24
This does not limit the function in any way provided the defective pixels are not all in one location. Additional information is available in the section "General Technical Specifications". Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
• Pack the device in the original packaging for transportation and storage. 5. Check the contents of the packaging and any accessories you may have ordered for completeness and damage. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 26
7. Please keep the enclosed documentation in a safe place. It belongs to the device. You need the documentation when you commission the device for the first time. 8. Write down the identification data of the device. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
For information on permitted ambient temperatures, refer to the section Technical specifications (Page 84). Mounting position Select one of the approved mounting positions for your device. The approved mounting positions are described in the following sections. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 28
Mounting in horizontal format All devices are suitable for horizontal mounting positions. A maximum ambient temperature of +50 °C is permitted for vertical mounting of the IFP1500 (0° tilt angle); a maximum of +40 °C is permitted for inclined mounting.
At least 50 mm distance At least 10 mm distance Note Ensure that the maximum ambient temperature is not exceeded when mounting the device in a cabinet and especially in a closed enclosure. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
● Permitted surface roughness in the area of the seal: ≤ 120 µm (R 120) Dimensions of the mounting cutout Width and height should be reversed accordingly when mounting in vertical format. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
4. Cut the corners at a 45° angle so that it is easier to slide the strip into the slot. 5. When the ink has dried, slide the labeling strips into the guide leaving a 3 cm clearance at the end. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 32
It is not necessary to secure the labeling strip. When installing the device, make sure that the labeling strips do not get jammed between the mounting cutout and the device. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
● Position the device so that it is easily accessible for the operator. ● Choose a suitable installation height. ● Ensure that the air vents of the device are not covered as a result of installation. Note the permitted mounting positions. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
To achieve the degree of protection for the device, the mounting clips or brackets must be affixed to the positions shown below. Device Position Touch screen device with: 15" display • 19" display • 22" display • Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
● The mounting clamps included in the accessory kit are ready to hand. Procedure Note If the mounting seal is damaged or protrudes over the device, the degree of protection is not guaranteed. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 36
4. Repeat steps 2 and 3 for all mounting clamps. 5. Check the fit of the mounting seal. Mounting with optional latch fasteners Latch fasteners can be used instead of mounting clamps in steps 1 to 5: Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Installing and connecting the device 3.3 Connecting the device Connecting the device 3.3.1 Overview Connection diagram for standard monitor version Connection diagram for standard touch version Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 38
Installing and connecting the device 3.3 Connecting the device Connection diagram for extended versions Distance up to 5 meters Distance of 5m to 30m Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
An additional earth connection serves as PE conductor for the DC power supply to discharge dangerous currents which trigger an overvoltage circuit breaker. The PE conductor is built into the connector with the AC power supply. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 40
3. Connect the PE conductor or equipotential bonding with the earth connection of the cabinet or plant in which the device is installed. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
The device may only be connected to a 24 V DC power supply that meets the requirements of a safe extra-low voltage (SELV) according to IEC/EN/DIN EN/UL 60950-1. The power supply must meet the requirements of NEC Class 2 or LPS according to IEC/EN/DIN EN/UL 60950-1. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 42
4. Connect the remaining L+ and M ends with the respective terminals on the 24 V DC power supply. 5. Switch on the 24 V DC power supply. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Ensure that the cable set conforms to the respective national safety regulations and is appropriately labeled. For USA and Canada: A CSA or UL-listed power supply cable must be used in the United States and Canada. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 44
● Maximum 4.5 m length ● Tandem grounded safety plug 15 A, min. 250 V Procedure Plug the connector of the supplied power supply cable in the AC power supply connector of the device. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Flat Panel and PC with USB transmitter module by means of the USB-Link interface. Note Data transfer per USB transmitter module via USB1.1. The data transmission rate corresponds to Full Speed according to USB1.1. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Ensuring degree of protection IP65 When you loosen the sealing cover above the USB port to connect a USB component, the degree of protection IP65 is no longer guaranteed for the device. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Use cable ties to secure the connected cables to the selected fixing elements for strain relief. Make sure that the cables are not crushed by the cable tie. The figure below shows the fixing elements of the IFP1500 Touch. Industrial Flat Panel IFP1500, IFP1900, IFP2200...
Page 48
Installing and connecting the device 3.3 Connecting the device Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
1. Switch on the power supply of the Industrial Flat Panel. 2. Turn on the PC. 3. Follow the instructions in the section "Installing the SIMATIC IPC Wizard / IPC Wizard". See also Preface (Page 3) Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
For the SIMATIC IPC Wizard you require the following hardware: ● PC, e.g., SIMATIC IPC ● Keyboard ● Mouse ● 100 MB of free hard disk space on the C:\ partition ● SIMATIC Industrial Flat Panel Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 51
If you install a Microsoft operating system without the matching graphics drivers for the graphics card, the Microsoft operating system installs the VESA graphics driver by default. The Microsoft VESA driver is not supported by the SIMATIC IPC Wizard. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
PC is switched on. – If your SIMATIC IPC was delivered without pre-installed software, start the installation of the SIMATIC IPC Wizard from the "Documentation and Drivers" CD/DVD. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 53
Result You have installed the software of the SIMATIC IPC Wizard. Note If the IPC Wizard is already installed, setup can be restarted with "Start > Siemens Automation> Simatic > IPC_Wizard". The following options are available: • Modify: Add or deselect features •...
Only touch the touch screen with your fingers or a suitable touch stylus. ● On-screen keyboard with touch device (see section "Using the on-screen keyboard") ● External keyboard, connected via USB ● External mouse, connected via USB Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Under extreme environmental conditions such as high atmospheric humidity and temperature, bubbles can form on the touch surface in rare cases. This only affects the appearance and does not represent any functional restriction. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Take the following precautions: • Configure the plant so that safety-related functions are not operated with the touch screen. • Switch off the device for cleaning and maintenance. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 58
– Surface contact with a diameter of > 3 cm, for example, resting the palm of the hand on the touch screen – As soon as the touch screen is no longer touched, input is possible again. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
F1 to F36 are used or if custom key code tables are used. Risk of damage Activating a key using a hard or pointed object, for example a screwdriver, reduces the life of the key or can damage it. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 60
WXYZ9 WXYZ( +-*/=0 +_*?+) >< The characters available for input depend on the text box involved. The figure below shows the entry of an alphanumeric value using the system keys: Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 61
LED by means of the LEDControl program of the IPC Wizard. General control function for use in keyboard shortcuts. General control function for use in keyboard shortcuts. Confirm input Cursor keys Key or keyboard Function shortcut Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 62
Moves the cursor or selection one page up. Moves the cursor or selection one page down. Moves the cursor to the start of the first screen. Moves the cursor to the end of the last screen. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
● Advanced calibration with up to 25 calibration points, recommended if there are special requirements for accuracy: The calibration data are stored in the registry of the operating system on the PC. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
A removed touch controller is displayed in red. If the accuracy of this 3-point calibration is not sufficient, you can clear the "Use eeprom storage" option box and use the extended 25-point calibration instead. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
The entry is confirmed by a check mark, the next selection is displayed. 7. Confirm all input prompts (arrows, or crosses in the center) until the complete screen has been calibrated. 8. Finally, confirm the input prompt "Confirm". Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
In addition, the OSK is opened automatically at Windows logon and at the activation of entry fields. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
– Touch the minimized OSK icon in the left-hand screen margin and drag the OSK onto the desktop. 3. You use the OSK in the Windows logon by activating the keyboard icon. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
The OSK for the Windows logon is opened. 4. After logon call up the OSK as follows using the Start menu: "Start menu > All Programs > Accessories > Ease of Access > On-Screen Keyboard" Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
1. Switch off the device. This prevents the accidental triggering of functions when the screen is touched. 2. Dampen the cleaning cloth. 3. Spray the cleaning agent on the cloth and not directly on the device. 4. Clean the device with the cleaning cloth. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
The devices described in these operating instructions can be recycled thanks to their low level of pollutants. Contact a certified disposal service company for environmentally sound recycling and disposal of your old devices. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
You can download information on the EC Declaration of Conformity, here under the keyword "Declaration of Conformity": Certificate Industrial Flat Panel (http://support.automation.siemens.com/WW/view/en/60242448/134200). Software license agreements If the device is supplied with preinstalled software, you must observe the corresponding license agreements. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 72
Ex tc IIIC T 70 °C Dc IP65 x: Temperature values, see EC design examination certificate The EC type examination certificates are available on the Internet at: Technical Support (http://www.siemens.de/automation/csi_en_WW) Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 73
This product satisfies the requirement of the Korean Certification (KC Mark). 이 기기는 업무용(A급) 전자파 적합기기로서 판매자 또는 사용자는 이 점을 주의하시기 바라며 가정 외의 지역에서 사용하는 것을 목적으로 합니다. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
The following abbreviations are commonly used for electrostatic sensitive devices: ● ESD – Electrostatic sensitive device ● ESD – Electrostatic Sensitive Device as a common international designation Electrostatic sensitive devices can be labeled with an appropriate symbol. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 75
These values conform to the specifications of IEC 61000-4-2. ① Synthetic materials ② Wool ③ Antistatic materials such as wood or concrete Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Installation" installation manual is available for download from the Internet (http://support.automation.siemens.com/WW/view/en/15390415). The following lightning protection element was used during the testing of the Industrial Flat Panel: Dehn BVT AVD 24" (Order No. 918 422) Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Technical information 7.3 Dimension drawings 7.3.6 Dimension drawing of the IFP1500 Touch/Key 7.3.7 Dimensions for labeling strips This section contains the dimensions of the labeling strips for 15" widescreen devices. Labeling strip templates are available in a Word document on the Internet at: Labeling strips for 15"...
Rating plate The rating plate includes information that clearly identifies your device. You need this information when you contact Customer Support. ① Order number ② Serial number ③ Production version Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
• keyboard keyboard Externally via USB Externally via USB • • Device keys • Analog resistive single touch screen Capacitive multi-touch screen Function keys Labeling strips not with 15" devices Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 85
Permitted voltage range 100 ... 240 V Rated current 200 mA Inrush current I 0.5 A Power consumption, typical 40 W Minimum time between two transients 50 s Internal protection Electronic Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Proper transport and storage, installation and assembly as well as careful operation and maintenance are prerequisites for trouble-free and safe operation of the device. Non-compliance will render the warranty for the device null and void. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
If the device is subjected to greater shocks or vibrations, you must take appropriate measures to reduce acceleration or amplitudes. We recommend mounting the device on damping materials, such as rubber-metal vibration dampers. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 88
; 10 days Relative humidity <60%, no condensation S: < 0.1 vpm; Test: 1 cm ; 10 days Relative humidity <60%, no condensation IFP1900 and IFP2200: From 0 to 45° C Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 89
HF power applied to lines Test voltage 10 V, with 80% amplitude modulation of 1 and line shields according KHz in the range of 150 KHz to 80 MHz IEC 61000-4-6 Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Test voltage circuits or ground 24 V 707 V DC or 500 V AC Protection class Protection Class I in accordance with IEC 61140, i.e. PE/ground terminal to profile rail required. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
24 V DC Power Supply 24 V DC power supply Pin no. Meaning +24 V DC 24 V GND is internally connected to signal ground on DVI, for example, device ground and housing. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
+ Data Data channel Ground 7.6.5 USB hub, Type A USB port Pin No. Short name Signal + 5 V (fused) - Data Data channel + Data Data channel Ground Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
You can find additional information and support for the products described on the Internet at the following addresses: ● Technical support (http://www.siemens.de/automation/csi_en_WW) ● Support request form (http://www.siemens.com/automation/support-request) ● After Sales Information System SIMATIC IPC/PG (http://www.siemens.com/asis) ● SIMATIC Documentation Collection (http://www.siemens.com/simatic-tech-doku-portal) ● Your local representative (http://www.automation.siemens.com/mcms/aspa-db/en/Pages/default.aspx) ●...
Page 96
Technical Support A.1 Service and support Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
RoHS Restriction of the use of certain hazardous substances in electrical and electronic equipment Programmable logic controller Device depth TCP/IP Transmission Control Protocol/Internet Protocol Universal Serial Bus Video Graphics Array Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 98
List of abbreviations Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Connection between different programs in order to exchange data. Module Modules are plug-in units for PLCs, programming devices or PCs. Modules exist, for example, as central modules, power-ons, or as mass storage. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
Page 100
Afterwards, the peripheral device can be used immediately. play, without having to configure the operating system manually. The plug and play PC requires both a BIOS that supports plug and play and a corresponding expansion card. Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...
AC power supply, 43 DC power supply, 41 DVI, 45 FCC, 73 PE conductor, 40 FM Approval, 72 USB, 45 Function key USB device, 46 Labeling, 31 Connecting the PE conductor, 40 Industrial Flat Panel IFP1500, IFP1900, IFP2200 Operating Instructions, 06/2014, A5E31298376-AB...