Intelligent controller (CZ-256ESMC2)
Limitation contents for prohibited operation
Prohibition means limitation of the operation contents from the remote
controller. It is also possible to change the prohibition items.
Limitation contents (Limitations can be user defined)
Individual
There is no limitation for the operation of the remote controller.
However, the contents will be changed to the contents of the
controller operated last. (Last-pressed priority.)
Prohibition 1 The remote controller cannot be used for ON/OFF. (All other
operations are possible from the remote controller.)
Prohibition 2 The remote controller cannot be used for ON/OFF, operation
mode change and temperature setting. (All other operations are
possible from the remote controller.)
Prohibition 3 The remote controller cannot be used for operation mode
change and temperature setting. (All other operations are
possible from the remote controller.)
Prohibition 4 The remote controller cannot be used for operation mode change.
(All other operations are possible from the remote controller.)
Note: Avoid joint use of the AMY system and the intelligent controller on the same indoor/ outdoor operation line.
Max. 256 indoor units (4 systems x 64 units) can be controlled. In case
of three or more systems, a communication adapter CZ-CFUNC2 must
be installed on the outside
Operation is possible as batch, in zone units, in tenant and in group units
Touch
panel
Dimensions
Dimensions
H 240 x W 280 x D 138 mm
Power supply AC 100 to 240 V (50 Hz), 20 W
(separate power supply)
I/O part
Remote in put (voltage-free
contact): All ON/OFF
Remote output (voltage-free
contact): All ON, All alarm (external
power supply within DC 30 V, 0.5 A)
Total wiring length: 1 km for each system
Only for embedding in the panel
ON/OFF, operation mode setting, temperature setting, for fan speed
setting, air flow direction setting (when used without a remote
controller), and remote controller local operation prohibition
(prohibition 1, 2, 3, 4) can be done
A system without a remote controller is possible. Joint use with a
remote controller or a system controller is also possible
Use of a schedule timer and holiday setting also can be done
Proportional distribution of the air conditioning energy is possible.
Including csv-file export via CF-card (supplementary accessory)
NEW function: Pulse signal input from electric/gas consumption meter
In case of joint use with a wireless remote control system, there are limitations for the control mode. Please use only with
"Permission" and "Prohibition 1".
INTELLIGENT
CONTROLLER
CZ-256ESMC2
System signal x 4
RS 485
(Polarity shield wire)
Communication adapter
CZ-CFUNC2
System signal x 4
Max. 4 links can be connected for the indoor/outdoor operation line = Max. 64 indoor
DISPLAY SAMPLE
units x 4 (256 units) Max. 30 outdoor units x 4 (120 units)
Web
application
Linked system No. 1
Linked system No. 2
Linked system No. 3
Linked system No. 4