Page 61
ITR has successfully completed. 8. If more than 30 minutes pass and “88” is still displayed, the ITR has failed. Contact your LG representative for technical assistance. 9. After a successful ITR, you can go to the LGMV Diagnostics tab, select Test Report, and save the .html data file. The report on the next page is a sample ITR report.
Page 63
The results provided by running an Fd mode must not be con- sidered definitive proof that a system is properly operating. Fd code must not be left on without an LG trained service provider approving and guiding its use.
Page 72
Smart Load Control can be used in almost every application except those where the outdoor unit is supporting a Dedicated Outdoor Air System (contact an LG representative for information). Smart Load Control will not have an impact on operation if the system is running in simultaneous cooling / heating (heat recovery systems only).
Page 86
Use in applications where the LG-trained service technician wants to restart a system for diagnostic purposes, or to operate the system for an extended period with no power to one (1) or more indoor units. The system can operate safely without damage to the compressor if: •...
All error codes can be viewed at the outdoor unit seven segment display (SSD) and with LGMV software. If an error codes shows on one (1) or more indoor unit zone controllers, it will display on LGMV, central controllers, BMS, or any other LG device connected to Comm bus - Internet A/B.
Page 203
1. If Error No. 59 is displayed on the heat recovery unit, and Error No. 204 is displayed on the outdoor unit, these indicate that the outdoor unit software has NOT been upgraded to support heat recovery unit 3A models. Contact your LG representative for information.
Page 235
LATS software programs, and more, visit www.lghvac.com. LG Customer Information Center, Commercial Products 1-888-865-3026 USA LG Electronics, U.S.A., Inc. Follow the prompts for commercial A/C products.