Internal User Only 2017 Trouble Shooting Guide Book Visual Elements Logo Life’s Good...
Page 2
Navigation Bar The different category are shown at the side. So, you can go directly to the index page with a single click. CONTACT US The satisfaction of our customers is very importance to us. This PDF will help you quickly find the informa- tion you are looking for and you can submit your comments, concerns or suggestions via the feedback link below.
1. Unit Conversion 2. Temperature Vs. Pressure of Ref. Power Saturation temperature vs. saturation pressure table for each refrigerant Absolute pressure = Guage pressure(kPa) + 101.325(kPa) kcal/h Btu/h (US) RT (Japan) RT Nominal HP kPa : kgf/㎠ x 101.97 kcal/h 3.986 0.0003306...
1. Nomenclature Multi V 5 Indoor Unit Multi V 5 Outdoor Unit Model Generation Model Generation Combinations of functions E : High Efficiency A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) Air Discharge Type T : Top Discharge G: Low Static...
2. Line Up / Capacity Multi V Hydro Kit Multi V 5 Indoor Unit ■ Standard Model ARN H G K2 Capacity(Btu/h(kW)) Chassis Category Name (1.6) (2.2) (2.8) (3.6) (4.5) (5.6) (6.2) (7.1) (8.2) (9.0) (10.6) (12.3) (14.1) (15.8) (22.4) (28.0)
Page 12
실외기 Multi V 5 Outdoor Unit 실외기 Multi V 5 Combination of Outdoor Unit CHASSIS Model Name Capacity(kW) Model Module(HP) Number Model Name ARUM080LTE5 22.4 of Units ARUM100LTE5 28.0 ARUM120LTE5 33.6 ARUM080LTE5 ARUM100LTE5 ARUM140LTE5 39.2 ARUM120LTE5 ARUM160LTE5 44.8 ARUM140LTE5 ARUM180LTE5 50.4...
Multi V 5 Outdoor Units 3. Piping Diagrams 3. Piping Diagrams 3.1 8 / 10 / 12 / 14 / 16 HP (1 Comp) HR Unit 8 / 10 / 12 / 14 / 16 HP (1 Comp) 3.1.1 Heat Recovery System...
Page 14
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Heating Operation ■ Oil Return/ Defrost Operation Heating Operation Oil Return/ Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 15
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Cooling-based Simultaneous Operation ■ Heating-based Simultaneous Operation Cooling-based Simultaneous Operation Heating-based Simultaneous Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 16
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Balanced Simultaneous Operation ■ Upper HEX Defrost Operation Balanced Simultaneous Operation Upper HEX Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 17
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Low HEX Defrost Operation 3.1.2 Heat Pump System Heat Pump System Low HEX Defrost Operation ■ Cooling Operation Cooling Operation High Temperature High Pressure Vapor...
Page 18
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Heating Operation Heating Operation ■ Oil Return/ Defrost Operation Oil Return/ Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 19
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Upper HEX Defrost Operation ■ Low HEX Defrost Operation Low HEX Defrost Operation Upper HEX Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 20
Multi V 5 Outdoor Units Multi V 5 Outdoor Units 3. Piping Diagrams 3. Piping Diagrams 3.2 18 / 20 / 22 / 24 / 26HP (2 Comp) ■ Heating Operation 18 / 20 / 22 / 24 / 26HP (2 Comp) Heating Operation 3.2.1 Heat Recovery System...
Page 21
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Oil Return/ Defrost Operation ■ Cooling-based Simultaneous Operation Oil Return/ Defrost Operation Cooling-based Simultaneous Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 22
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Heating-based Simultaneous Operation ■ Balanced Simultaneous Operation Heating-based Simultaneous Operation Balanced Simultaneous Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 23
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Upper HEX Defrost Operation ■ Low HEX Defrost Operation Upper HEX Defrost Operation Low HEX Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 24
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Heating Operation 3.2.2 Heat Pump System Heat Pump System Heating Operation ■ Cooling Operation Cooling Operation High Temperature High Pressure Vapor High Temperature High Pressure Vapor...
Page 25
Multi V 5 Multi V 5 Outdoor Units Outdoor Units 3. Piping Diagrams 3. Piping Diagrams ■ Oil Return/ Defrost Operation ■ Upper HEX Defrost Operation Oil Return/ Defrost Operation Upper HEX Defrost Operation High Temperature High Pressure Vapor High Temperature High Pressure Liquid...
Page 27
Hydro Kit 2. High Temperature 1. Medium Temperature Hydro Kit (For High Temperature) R134a CYCLE Water Tank Outdoor Unit Water Flow Switch SIDE Outlet Liquid Water Inlet Strainer Check Side Strainer Strainer Valve Bypass Flow Valve Switch Water Outlet Side LIQUID Water Strainer...
Ⅲ. Trouble Shooting Guide Checking Point 1. LGMV 2. Lack of Cooling 3. Lack of Heating 4. Check The Amount of Refrigerant 5. Cycle Changes by Amount of Refrigerant...
1. LGMV 2. Lack of Cooling 2.1 Not reach target low pressure Checking Item Symptom Judgment Countermeasure Check the indoor EEV opening pulse. When the opening pulse is small or closed, please lower the degree of superheat of the corresponding indoor unit Check the indoor unit EEV Inlet temp.
3. Lack of Heating 2.2 Not reach target low pressure 3.1 Reach target high pressure Checking Item Symptom Judgment Countermeasure Checking Item Symptom Judgment Countermeasure Not reach the target Refrigerant overcharging Check the amount of refrigerant low pressure under Bypass by defec- Recheck the load design, Check the Check the outdoor valve full / partial / single...
4. Check The Amount of Refrigerant 3.2 Not reach target high pressure 4.1 Cooling Checking Item Symptom Judgment Countermeasure Item Refrigerant shortage Refrigerant overcharging Not reach the target low • EEV open Bypass by defective EEV close pressure under full / Check the outdoor valve Indoor unit EEV (approx.
Page 36
4.2 Heating 4.3 Normal cycle Item Refrigerant shortage Refrigerant overcharging EEV close EEV open Indoor unit EEV (approx. 200 pls or less) (approx. 1350 pls) The degree of subcooling (@ indoor unit) below 3 ℃ above 7 ℃ (Condense Temp. - Pipein Temp.) Low pressure below target low pressure...
5. Cycle Changes by amount of refrigerant 20170217 Trouble Shooting Guide Book_Multi5_신규추가 4.4 Abnormal cycle (Refrigerant Overcharging / Shortage) 5.1 Cooling cycle 5. Cycle Changes by amount of refrigerant 5.1.1 A cycle changes by refrigerant overcharging 5.1 Cooling cycle When overcharging a refrigerant more than necessary, an extra refrigerant will be stored in con- 5.1.1 A cycle changes by refrigerant overcharging densing HEX and liquid pipe because of high density.
20170217 Trouble Shooting Guide Book_Multi5_신규추가 5.2 Heating cycle 5.2.1 A cycle changes by refrigerant overcharging 5.2 Heating cycle When overcharging a refrigerant more than necessary, an extra refrigerant will be stored in con- Ⅲ. Trouble Shooting Guide densing HEX and liquid pipe because of high density. Overcharged refrigerant can make changing 5.2.1 A cycle changes by refrigerant overcharging the cycle as below.
1. Error Code Display Self-Diagnosis Function Display Title Cause of Error Error Indicator Hydro KitIndoor unit Inlet and Outlet pipe Pipe temperature sensor is open or short - This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. Temperature sensor Error - Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as Hydro Kit Indoor unit Inlet pipe Temperature...
Page 40
Display Title Cause of Error Display Title Cause of Error Outdoor Unit Inverter Compressor2 Discharge Outdoor Unit Inverter Compressor2 Discharge Tem- 1 0 6 Outdoor Unit Fan IPM Fault Error Instant Over Current at Outdoor Unit Fan IPM Temperature Sensor Fault perature Sensor open or short Outdoor Unit Fan DC Link Low Voltage Outdoor Unit Fan DC Link Input Voltage is under...
Page 43
• Local IDU Modem Error No. Error Type Error Point Main Reasons Connector to main PCB Communication error The indoor unit did not re- 1. IDU PCB or ODU PCB defect between IDU and ceive the signal from ODU For 9600 bps comm., the red LED will always turn on. 2.
Page 74
Error No. Error Type Error Point Main Reasons Check address of All IDU's address 1. Communication Wiring defect (Central con- Is central control addressing (Duplication & Omission of IDU address) normal? troller - ODU) Abnormal - All IDUs should have unique central control address Network error of 2.
Page 77
2.3 Checking Method (Flow Chart) 2.4 Process of Replacing the Compressor Please follow the below process when you replace the compressor. Checking start · Before replacing the compressor, check whether the failure of the compressor. · Change the oil for compressor after replacing the compressor for 2~3 times. 1.
Page 78
2.5 Precautions of Replacement 2.7 Compressor Specification 1. Be sure to use the compressor suitable for the model The specification of compressor being adapted to Multi V is below. 2. Be careful not to damage the pipe When the compressor is not working, please check the compressor referring to the below specification. 3.
Page 79
3. EEV ■ Heating 3.1 Failure Judge Method 1. Main EEV ■ Cooling 1) Basic control : Suction the degree of superheat control 2) Failure phenomenon 1. Main EEV ① Upper EEV open failure 1) Basic control Excessive drop of low pressure, Upper and lower heat exchanger temperature difference 10 ℃ or - Variable path mode : Upper EEV Full Close / Lower EEV Full Open more - Low temperature cooling mode : Upper EEV Full Open / Lower EEV Close...
Page 80
■ Physical Failure Judge Method 3.2 Checking Method (Flow Chart) 2-1. EEV 불량 판단 _ 물리적 불량 판단 방법 LGE Internal Use Only 1. Main PCB reset to initialize EEV ■ Outdoor Unit EEV : Full Open (1,950 pls) → Full Close (1,950 pls + 200 pls) → Open (32 pls - 4Way valve on) or Open (1 950 pls - 4Way valve off) ①...
Page 81
■ VI EEV ■ Sub Cooling EEV Checking start Checking start There is a temperature Powered up for the Power is normally difference between front first time, feel the initial Replace PCB supplied to the VI EEV? and rear of the sub cooling vibration? EEV during normal cooling mode?(EEV Open...
Page 82
4. Solenoid Valve Check that the output signal of the control board matches the operation of the solenoid valve. 3.3 Precautions of Replacement 4.1 Variable Path Valve 1. EEV should be judged correctly and replaced 2. Replaced EEV should be returned for cause analysis 3.
Page 83
■ Checking Method (Flow Chart) 4.2 Sub Cooling Bypass Valve 1. When the compressor starts, the sub cooling bypass valve is ON for minute. At this time, check whether Checking start the noise or pipe vibration occurs In solenoid valve 2.
Page 84
4.3 Oil Return Valve 4.4 Hot gas Bypass Valve for Continuous Heating 1. It is located at the bottom of the accumulator and operates after the compressor running to supply oil to 1. Defrost operation eliminates ice attached on heat exchanger, recovering performance of heat exchanger. the compressor.
8. Outdoor Fan & Fan Motor 8.1 Outdoor Fan 8.3 Checking Method (Flow Chart) 1. The outdoor fan is controlled by the inverter motor which can control the number of rotations. Checking start 2. The outdoor fan is controlled by the high/low pressure of the outdoor unit after the operation of compressor.
11. Humidity Sensor ■ Checking Method (Flow Chart) If the humidity sensor has problem such as sensor open or short, no error display is shown at outdoor unit. Normally LGMV shows humidity ratio such as below display box of LGMV. Checking start However, if the humidity sensor open/short occurred, it displays as "0".
12. Pressure Switch 13. Main PCB 13.1 Failure Judge Method 15. Main PCBA Checking start 1.1 불량 판단 방법 1. Error code check 1) 에러 코드 확인 Error Code Error diagnosis ·Check restart after power reset 에러 코드 ·Check main PCB power supply. In the pressure condition that the pressure CH50...
14. External PCB 13.2 Failure Cause 14.1 Failure Judge Method 1. Error code check 1. High voltage (T-N more than 484V, N phase wiring fault) → CH50 2. Rainwater inflow by Control box / Front Panel / Service port open, Control box screw loosening Error Code Error diagnosis 16.
15. Inverter PCB 17. Inverter PCBA 14.2 Failure Cause 15.1 Failure Judge Method 1.1 불량 판단 방법 1. Error code check 1. High voltage (T-N more than 484V, N phase wiring fault) → CH50 2. Rainwater inflow by Control box / Front Panel / Service port open, Control box screw loosening Error Code Error diagnosis 3.
16. Fan PCB 15.2 Failure Cause 16.1 Failure Judge Method 18. Fan PCBA 1. Error code check 1. High voltage (T-N more than 484V, N phase wiring fault) → CH50 2. Rainwater inflow by Control box / Front Panel / Service port open, Control box screw loosening Error Code Error diagnosis 1.1 불량...
17. Communication PCB 16.2 Failure Cause 17.1 Failure Judge Method 1. Error code check 1. High voltage (T-N more than 484V, N phase wiring fault) → CH50 2. Rainwater inflow by Control box / Front Panel / Service port open, Control box screw loosening Error Code Error diagnosis 3.
20. Fan IPM 20.1 Fan IPM Checking Method 팬 IPM 검사 방법 <UXA 샤시> <UXB 샤시> U,V,W U,V,W DC_Link Connector Connector DC_Link Connector Connector P Terminal N Terminal P Terminal N Terminal U Terminal U Terminal W Terminal W Terminal V Terminal V Terminal 1.
21. Central Controller PC Status ■ Network Environment Checking Checking Item Error diagnosis Error diagnosis · Check network setting PC Network Setting · Check LAN cable Case 1. The ACP directly connect with PC through a cross cable. But, you cannot access the ACP ·...
Page 97
2. Countermeasure 21.2. PC Software 2.1 If you using JAVA7, you can solve the problem through how to set the security level to "medium" ■ Checking Method (Flow Chart) on the [security] tab. [Start Menu -> All Programs -> JAVA Click -> Configure Java-click] But if you ever become a concern about security, we recommend that ACP's IP add to excep- tions listed sites.
* Gen 4 or Higher outdoor units : Multi V 5, Multi V IV or Multi V Water IV with Gen 4 or Higher software (see table below for Gen 4 or higher serial numbers) or Multi V S. Fd 8 All IDU operation (Cooling) ●...
Page 100
Model Type Model Type Mode Display Function Selection Content Page Mode Display Function Selection Content Page Heat Heat Heat Heat Recovery Pump Recovery Pump FN 1 Cool & Heat Selector ● Id 1 EEV Pulse of Non-Operating IDU in Heating ●...
3. FDD Mode 3.1 FDD Check List 3.2 FDD Code Display ■ Please check the following. Code Display Cause 130% more than outdoor unit rated capacity or 80% less than outdoor unit rated capacity 1. Automatic address setting has been preceded by a test drive will proceed on the premise. After installation, auto address must be checked because it is related the number of Installation System Unstable Error Temperature Range Error...
Page 103
LGE Internal ITR (Cooling / Heating / Automatic) Use Only 3.4 Automatic ITR (Cooling / Heating) WARNING · When perform the leakage test and air purge, please use a vacuum pump or an inert gas. (nitrogen) ITR (Cooling / Heating / Automatic) It is a function to get information about amount of refrigerant and EEV status in IDU, ODU if normal or not.
Page 104
LGE Internal ITR (Cooling / Heating / Automatic) ■ The Display of Results 2. Heating Use Only • If the system is in operation before entering the heating test operation, "IDU / STOP" is displayed, Judgment Code Display then the indoor unit is turned off and the FDD operation is entered. please enter the total amount of refrigerant accurately before entering mode.
Page 105
■ ITR Result Report 3.5 All IDU operation (Cooling / Heating) It is a function to continuously operate in cooling / heating for one hour. ■ Setting the function Function All IDU operation (Cooling) Fd 8 All IDU operation (Heating) Fd 9 ■...
4. Function Mode ■ Detailed information 4.1 Cool & Heat selector • This function is used with heat pump only. It is a function to control the cooling / heating limit through the switch of cool & heat selector and ODU •...
Page 107
■ Detailed information 4.2 High Static Pressure Compensation • This function is used with heat pump and heat recovery. This function secures the air flow rate of ODU, in case the static pressure has been applied like using duct • All modes of operation involving compressor operation are a change in the setting impact. at fan discharge of ODU.
Page 108
• Cooling mode is a change in the setting impact. operating conditions in the evening while the outdoor unit is operating in the cooling mode. • Multi V 5 continuously monitors the building's cooling demand. On a rolling 24 hour basis, the peak ■ Setting the function cooling demand is maintained and an internal timer begins counting hours since the peak demand was set.
• Schematic Diagram 4.4 Overall Defrost 1) Overall Defrost It is a function to select the overall or partial defrost when the defrost is in operation. ■ Setting the function Function Option Overall Defrost Fn 4 on, oFF 2) Partial Defrost (Heat Pump) ■...
Page 110
4.5 ODU Addressing 4.6 Snow Removal & Rapid Defrost It is the outdoor unit address setting function for outdoor unit when central controller is installed. It is a function to prevent accumulation of snow in the snowy area or to judgment the fast defrost in the humid area.
Page 111
4.7 Airflow Adjusting for IDU 4.8 Target Pressure Adjusting It is the function to cope with the overload by changing air flow in the room to the low air flow when the It is a function to change the target pressure of ODU according to field installation conditions (ex. pressure compressor Hz is the maximum but the high pressure is low.
4.9 Low Ambient Kit 4.10 High Efficiency Mode It is a function to Informs the Multi V microprocessor controller the low ambient kit is installed. High efficiency mode refers to increasing the compressor capability to cool at high ambient temperatures. This function automatically lowers the target low pressure as the outdoor ambient temperature rises while the outdoor unit operates in cooling mode (i.e.
4.11 Auto Dust Removal Mode 4.12 Compressor Max. Frequency Limit This function is able to improve the heat exchange efficiency to maintain clean state on heat exchanger of It is a function to limit the maximum speed (frequency) of inverter compressor. ODU.
Page 114
4.13 ODU Fan Max. RPM Limit 4.14 Smart Load Control It is a function to limit the maximum RPM of ODU. Smart Load Control function enables comprehensive understanding of environmental conditions in order to optimize energy efficiency. This technology allows active control of discharge refrigerant temperature which eventually increases the efficiency for average outdoor unit in comparison to the previous models.
Page 115
■ Detailed information App. The Logic of Dual Sensing SLC (Smart Load Control) • This function is used with heat pump and heat recovery. • Dual Sensing SLC is controlled by 3 factors. (in case of cooling operation) • Heating, Cooling and Dry modes are a change in the setting impact. : Outdoor temperature.
Page 116
- When used heating operation in case of high humidity condition, deforest will be delayed because target high/low pressure will be changed. • Activation function by using humidity sensor (Option "on") Multi V Ⅳ Multi V Ⅳ Multi V 5 Multi V 5 Multi V 5 Comfort...
This function allows the field connection of the AC-EZ central controller to the indoor unit communications This function is used when the current management is required by proportionally reducing the maximum buss on Multi V 5. MFA specification of the product.
• If the Smart Plug function is turned on, the power consumption data may be viewed using one of · If do not use a function, set an off-mode. LG's central control/monitoring devices such as ACP, AC Smart, or the multi site communications manager. For installations where a third party BMS system Is present, consumption data is also made available for viewing at the BMS front end using LG's BACnet gateway.
5. SVC Mode 4.20 Optional Base Panel Heater 5.1 Pump Down It is a function to prevent freezing of ODU base pan in a cold area. This function gathers the refrigerant present in the system to ODU. Use this function to store refrigerant of system in ODU for leakage or IDU replacement. ■...
Page 120
The maximum amount of refrigerant for Multi V 5 is size dependent and varies be- tween 14.3 and 37.5 lbs / frame. If the system charge is greater than the volume that can be ■...
Page 121
LGE Internal Pump Out Use Only ■ Example (Slave2 ODU inverter compressor failure) ■ Detailed information ■ Example (Slave2 ODU inverter compressor failure) • This function is used with heat pump and heat recovery. • For Heat Recovery System • For Heat Recovery System *Note : In systems with short piping systems, the amount of refrigerant that can be pumped from the outdoor unit may be limited and additional refrigerant storage containers may need to be used.
Page 122
LGE Internal Pump Out Use Only ■ Example (Slave2 ODU inverter compressor failure) ■ Example (Slave2 ODU inverter compressor failure) 5.3 Vacuum • For Heat Pump System • For Heat Pump System This function is used for creating vacuum in the system after compressor replacement, ODU parts replace- ment or IDU addition/replacement.
Page 123
LGE Internal Back Up Use Only LGE Internal Back Up Use Only ■ Auto Back Up ■ Auto Back Up Back Up 5.4 Back Up This function allows the system to operate in case of inverter compressor failure by This function allows the system to operate in case of inverter compressor failure by backing up com- This function is used when backing up outdoor units or compressors.
5.5 Forced Oil Return 5.7 Display Cycle Information This function is used in recovering the oil level of the compressor through recollecting the accumulated oil This function is to display the main parameter value displayed by LGMV in real time through the 7-segment in the pipe.
5.8 Noise Reduction 5.9 Entry Heating Oil Return It is a function to reduce the noise of the entire system. This function is for performing oil recovery operation while heating operation. The refrigerant noise claim occurs due to repetition of oil recovery operation, this function will be checked and applied.
5.10 Heating Fan Low Noise 5.11 Number of Partial Defrosts It is a function to reduce outdoor fan max rpm by adjusting low target pressure while heating mode. This function is used for continuous heating control by option setting split defrost (heating cycle, upper / lower valve control) ■...
6. IDU Mode 5.12 Level Changes of CH200 6.1 EEV Pulse of Non-operating IDU in Heating It is a function to change CH200 error level. It is the function to adjust EEV pulse of no IDU in heating. ■ Setting the function ■...
6.2 Set IDU Superheat / Set IDU Subcool 6.3 Set Auto Pipe Detection / Start Auto Pipe Detection This function is used to set additional superheat and subcool in the indoor unit. The function that sets connection relationship automatically between the indoor unit and heat recovery unit. ■...
6.4 Set Zone Master ·Execute auto pipe detection again whenever the indoor PCB and HR unit PCB is replaced. - Operation error occurs unless power is supplied to the indoor and HR units. It is a function to operate according to the mode of the master indoor unit when several indoor units are ·...
6.5 Operating IDU Low Noise 6.6 In Cooling IDU EEV Max. Pulse This function is used to reduce refrigerant noise when the indoor unit starts to run It is the function to prevent excessive opening by setting EEV maximum pulse of indoor unit in cooling. for heat recovery system.
App. The Logic of Comfort Cooling 6.7 Comfort Cooling • Comfort Cooling means the superheat control of indoor unit. It is function to reduce the ODU energy consumption by the continuous operation without thermo off. : Changes the refrigerant flow rate of each indoor unit by EEV •...
6.8 Non-operating IDU Subcool 6.9 Set IDU Superheat For Fan It is function to reduce refrigerant noise that might be heard when non-operating IDU EEV is opened to It is a function to alleviate dew condensation on indoor unit panel by setting additional superheat according recover liquid accumulated inside IDU.
Page 133
2017 Trouble Shooting Guide Book Visual Elements Logo Publisher LG Electronics Air Conditioning & Energy Solution Company, SAC Engineering Division Issued date May 2017 Adress LG Twin Towers, 20, Yeouido-dong, Yeongdeungpo-gu, Seoul 150-721, Korea http://kic.lgeaircon.com All rights are reserved by LG Electronics.