SERVICE PARTS INFORMATION 11
Resistor, Cement
Check Point 1 : Appearance check
No fissures, breaks, damage, etc. at the body and terminals section?
Check Point 2 : Electric check
1. Surge prevention resistor (connected to magnetic contactor)
Set the tester to the "Resistance" mode, and measure the resistance value between the terminals.
(No polarity)
Judge the result of
9.9
to 10.1
Other than the above
2. Discharge resistor (connected to electrolytic capacitor)
Set the tester to the "Resistance" mode, and measure the
resistance value between the terminals. (No polarity)
Judge the result of
53.2k
to 58.8k
Other than the above Deteriorated, defective
as follows:
Normal
Deteriorated, defective
as follows:
Normal
04-105