3-2-4 Custom Auto Heating / Cooling Operation

[Function available in follwing conmditions]
- Remote controller type: UTY-RNRU
- Remote sensor in use
- Prohibit the central function from the Central controller *Reccomend
CUSTOM AUTO Operation
Operation flow chart
T set.C - T set.H
Room temp.
Room temp.
NO
HEATING OPERATION
YES
in OFF state for 6 minutes or
YES
or operation command other than
*Dead Band(DB) means between T set.C and T set.H, however the setting paramater of Dead Band always has a priolity.
Ex) T set. C: 82°F, T set. H : 78°F DB setting: 6°F => T set. C: 82°F, T set. H: 76°F
*When the outdoor unit(s) selected the operation mode at once, the selected operation mode will be kept for 12minutes minimum.
START
6°F
YES
T set.C: Setting temp. in Cool
T set.H: Setting temp. in Heat
1/2 of DB + 3.0°F
NO
DB: Dead Band*
1/2 of DB - 3.0°F
YES
Thermostat remains
longer?
NO
System stops
auto changeover operation?
NO
NO
Room temp.
Room temp.
YES
03-06
YES
T set.C + 1.0°F
NO
T set.H - 1.0°F
YES
COOLING OPERATION
Thermostat remains
in OFF state for 6 minutes or
longer?
NO
System stops
or operation command other than
auto changeover operation?
NO
(DB will be kept from Tset.C basis)
NO
YES
YES