Figure 5 Expansion (dual) rack recommended floor cutouts
.
Item
A
B
C
Allowable tolerance: +/ 0.125 in (+/ 3.2 mm)
XP24000 cutouts
The figures in this section show the locations of floor cutouts under the XP24000 DKC and XP24000
DKU for electrical cables. Position floor cutouts toward the center of the cabinet. The position may be
off-center as long as the cutout is within the allowable range and allows smooth entrance of external
cables. Be sure to check the relationship between the position of the cutout and the opening on the
bottom of the cabinet, since they must align.
option 2
Description
4.50 in. (115 mm)
2.50 in. (57 mm)
6.00 in. (150 mm)
XP24000/XP20000 Disk Array Site Preparation Guide
31