Programming Overview
6.2.1 Input Point Mapping
Input Points are assigned to input zones. Any input point can be
assigned to any input zone. (Input points can be assigned to one
zone only. You can designate an Input Point as "Unused," which
means it has not been assigned to a zone).
P t. 1
P t. 2
P t. 3
P t. 4
P t. 5
P t. 6
P t. 7
P t. 8
P t. 9
P t . 7 0
P t . 7 1
P t . 7 2
P t . 7 3
P t . 7 4
P t . 7 5
Figure 6.2 Input Point Assignment Example
6.2.3 Event Mapping
You can map the following types of Events. For each Event Type, you can activate the Output Groups with specific Output Patterns. refer
to Figure 6.4, 6.5 and 6.6 for Mapping Events.
11 types of Zone Events
Table 6.3 lists the types of Events that correspond to the System category.
System
Manual Pull Alarm
Water Flow Alarm
Detector Alarm
(heat or smoke detectors)
Fire
Zone Aux 1 Alarm
Zone Aux 2 Alarm
Interlock Alert
Trouble
Advisory
Status Point Active
40
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 123
Zone 124
Zone 125
Zone
Interlock Release System Aux 1 Alarm
Pre-Alarm
System Aux 2 Alarm
Fire Supervisory
Status Point
CO Alarm
CO Supervisory
Zone
SBUS Expander Trouble Battery Trouble
SBUS Class A Trouble
SLC Loop Trouble
AC Loss Trouble
Table 6.3
Zone 1:
Manual Pull Alarm
Figure 6.4 Example of Zone Events Mapped to Output Groups and Patterns
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
6.2.2 Output Circuit Mapping
Figure 6.3 is a simple example showing how to assign notification
and relay output circuits to groups. For an example of a simple floor
above/floor below application, see Figure 6.3.
Output Circuit 1
Notification Circuit
Output Circuit 2
Aux. Power Output
Output Circuit 3
Relay 1
Output Circuit 4
Relay 2
Figure 6.3 Assigning Output Circuits to Groups Example
14 types of Panel Events
Panel
Panel
Ground Fault Trouble
Phone Line Trouble
Reporting Account Trouble
Event Types
Pattern 00
Constant
Pattern 02
ANSI 3.41
Mapping Overview
Group 1
Group 2
Aux. power
outputs are
not mapped to
output groups
Group 124
Group 125
6 types of Site Events
Site
Fire Drill
General Fire Alarm
General Fire Supervisory
General Fire Pre-Alarm
Site
General Trouble
Site Silenced
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
In this example,
all notification
outputs are
assigned to
Group 1
JumpStart
creates
Group 124 &
Group 124 for
Relay 1 & 2
F1 Key Active
F2 Key Active
F3 Key Active
F4 Key Active