System Operation
.
Detector ID
Fields
State of
Detector
Detector ID
Fields
8.4.11 View Status of a Point
1.
From the Main Menu, select 2 for Point Status.
2.
From the list that displays, press <Enter> to select the module where this point is located. The screen that displays will show you if
the point has a trouble and will provide sensitivity compliance information. (See Section 8.4.10 for
3.
Complete the information about detector sensitivity compliance.
8.4.12 View Alarms, Supervisories or Troubles
When the system is in alarm, (supervisory or trouble), press <Down> arrow to view the location of an alarm, supervisories or trouble.
8.4.13 View System Information
Press 8 from the Main Menu to view the panel model, serial number, system version number and date. Press the <Left> arrow key to
return.
About the Panel
Press 1 to access the About Panel to view the panel model, serial number, system version number and date.
Send/Receive Firmware Updates
The GWF-7075 has the ability to be updated in the field. The latest GWF-7075 Firmware Update Utility can be downloaded from the
Gamewell-FCI Web Site.
1.
Press 2 to send a firmware update or press 3 to receive a firmware update from the System Information Menu.
2.
Use the <Up> or <Down> arrow key to select a panel to send/receive an update to/from. Press <Enter> to start the update process.
Feature Activation
Use this Menu to activate/register additional features.
1.
Press 4 from the System Information Menu. This option displays the Feature Activation Menu.
2.
Press 1 to enter a six digit activation code or press 2 to review the features already activated in this panel.
64
Example of Compliant Detector
Indicates percent
obscurity per foot.
SMOKE ION
MODULE_33
OINT_4
[2001
] [M33:004 ]
NORMAL
>= MORE
ATL-151
(1.1%
ACA=057
M=093
Clear Air=-58
Peak-061
(04%)
>=HLP
Possible States:
NORMAL
- Detector sensitivity-UL Compliant
(and not in alarm)
ALARM
- Detector in alarm
CAL MAINT - Detector needs maintenance, but not
yet in Trouble
CAL TRBLE - Detector-NFPA non-compliant (Other
Trouble messages, for example,
"MISSING" could override this
message.
Example of Compliant CO Detector
CO
SMOKE
2.0%
MODULE_33
SENSOR_ 4
[2001 ][M33:004 ]
Sensitivity
= 2.0%
CO – xxx ppm
Figure 8.3 Checking Detector Sensitivity Compliance
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Example of a Non-Compliant Detector
To access Next
SMOKE ION
1.1%
Display, press
MODULE_33
<Right Arrow>.
[2001
A058
CAL
ATL-151
CAL-indicates
OB/FT)
the Detectors
ACA=-57 M=093
T=109
are non-
Clear
<01%)
compliant with
Peak-061
UL
ATL-Alarm
ACA=-Average
M=Maint
T =Trouble
Indicates percent
Indicates percent
obscurity per foot.
obscurity per foot.
AXXX
Blanks signify a Non-
Compliant Detector.
--------%
POINT_4
][M33:004 ]
A058
TRBLE
>=
MORE
To access Next
Display, press
<Right Arrow>.
(----%
OB/FT)
T=109
Air=058
(01%)
(04%)
>=HLP
To access Help Display,
press <Right Arrow>
Threshold
Clr Air
Threshold
Threshold
Basic Operation