Programming
7.2.18 View Group Points
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for the Panel Programming.
3.
Press 3 to enter the Group Menu.
4.
Press 2 to view the Group Points.
5.
Enter the Group Number, then press <Enter>.
7.2.19 Edit OPG Template
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter the Group Menu.
4.
Press 3 to edit the OPG Template.
5.
Enter the Template Number, then press <Enter>.
6.
Press <Enter> on the template name to edit the name.
You can use text to display a descriptive name for a group.
7.
Press the <Right> arrow to move the cursor to the OPG and select <Yes> or <No>. This option allows you to select which Output
Group to include in the template.
7.3 Point
You may need to change characteristics of individual input points (for example, detectors and switches) even after you use the JumpStart
Auto-Programming. This section explains how to change options for the following options:
•
Type of Point
•
Zone Assignment (input points) •
7.3.1 Point Programming for the SLC
To program for points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the <Up> or <Down> arrows to select the desired module. refer to Section 6.5 Quick Reference Table for available choices.
5.
Enter the number of the point you want to edit, then press <Enter>.
6.
To select the type of device, press the <Up> or <Down> arrows. Refer to Table 7.4 under the column heading "Type Selection" for
a list of choices.
Type
Selection
UNUSED
PHOTO
ION
HEAT
PHOT DUCT
Velociti
2WIRE SMK
Detectors
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
SUP PHOTO DUCT
SUP SMOKE PHOTO
SUP SMOKE ION
SUP HEAT
Velociti Sup
SUP ACCLIMATE
Detectors
SUP HEAT HT
SUP SMOKE
PHOTO/HEAT
SUP SMOKE BEAM
ALRM CO/ALRM FIRE
SUP CO/ALRM FIRE
CO Smoke
ALRM CO/SUP FIRE
Detector
SUP CO/SUP FIRE
MAN_PULL
52
Figure 7.5 View Group Points
•
Latching/Non-Latching
Detector Accessory Base options •
Function
Latching Option
Latching
Non Latching
Latching
Non Latching
Table 7.4 : Point Programming for Internal SLC Modules
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
•
Silenceable/Non-silenceable
Group Assignment (Output Points)
Supervisory switches can be latching or non-latching.
Detectors programmed as Supervisory can be latching or non-latching.
Use this switch type for manual pull stations. This input is always latched. The
switch can clear only when an alarm is reset.
•
Comments
Point
Point Name