Check Point : Arxb25 / 30Latf; Check Point : Arxb36Latf, Arxa25 / 30Latf; Check Point : Arxb45Latf - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

Check Point : ARXB25 / 30LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)

Check Point : ARXB36LATF, ARXA25 / 30LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)

Check Point : ARXB45LATF

p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)
Super low(Blue)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(AC)
(White)
Super low(Blue)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(AC)
(White)
Super low(Blue)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(AC)
(White)
06-102
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
Read Wire
Resistance value(20 ° C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
44.8 ± 8%
37.3 ± 8%
21.3 ± 8%
12.9 ± 8%
12.9 ± 8%
50.9 ± 8%
29.1 ± 8%
8.96 ± 8%
8.96 ± 8%
8.96 ± 8%
40.3 ± 8%
23.8 ± 8%
11.4 ± 8%
7.9 ± 8%
7.9 ± 8%