SERVICE PARTS INFORMATION 12
Outdoor Unit Fan Motor
Check Point : AJ*126L / AJ*126U
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
BLUE
RED
WHITE
YELLOW
BLACK
Check Point : AJ*A90/72L / AJ*A90/72U
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
BLUE
RED
WHITE
YELLOW
BLACK
Pr
Pr
Read Wire
Resistance value
82.0
Blue - Red
Red - White
38.5
22.0
Red - Black
Read Wire
Resistance value
59.5
Blue - Red
Red - White
45.0
22.5
Red - Black
06-105
15%
15%
15%
at 20°C
5%
5%
5%
at 20°C