Check Point : ARXC90LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Check Point : ASYA18 / 24 / 30LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Read Wire
Resistance value(20 ° C)
-
U(Red)
V(White)
-
V(White)
W(Black)
-
W(Black)
U(Red)
Read Wire
Resistance value(20 ° C)
White - Red
Black - Blue
Blue
- Red
06-104
26.1 ± 8%
26.1 ± 8%
26.1 ± 8%
129 ± 8%
21.0 ± 8%
277 ± 8%